7
We reserve the right to make technical modifications.
W
• http://www.buderus-commercial.co.uk
Installation instructions Logamax plus GB162-80/100 cascade unit • Version 01/2006
Dimensions
3
Cascade
system
Length (mm)
Width (mm)
X1 + Y1
TR2
575 + 38 =
613
992
TR3, TR4
1100 + 42 =
1142
992
TR5, TR6
1625 + 45 =
1670
992
TR7, TR8
2150 + 45 =
2195
992
Table 3 TR-back-to-back configurations
Caution!
The dimensional tolerance is ± 5%.
Cascade
system
Length (mm)
Width (mm)
X1 + Y1
TL2
1100 + 38 =
1138
575
TL3
1625 + 38 =
1663
575
TL4
2150 + 42 =
2192
575
TL5
2675 + 45 =
2720
575
TL6
3200 + 45 =
3245
575
TL7
3725 + 45 =
3770
575
TL8
4250 + 45 =
4295
575
Table 4 TL-inline configurations
Cascade system
Header (inch)
Length
(mm)
B1
(mm)
B2
(mm)
B3
(mm)
L1
(mm)
F1
(flange dimension in mm)
TL2, TL3, TR2
2½ "
straight
488
–
–
–
488
Blank flange C2631 37.2 NW
65/76.1 PN6
right-angled
213
213
621
133
–
TL4, TR3, TR4
3 "
straight
571
–
–
–
571
Blank flange C2631 37.2 NW
80/88.9 PN6
right-angled
252
252
728
157
–
TL5, TL6, TL7, TL8
TR5, TR6, TR7, TR8
4 "
straight
651
–
–
–
651
Blank flange C2631 37,2 NW
100/114.3 PN6
right-angled
313
313
849
198
–
Table 5 Header dimensions
Fig. 6
Dimensions of cascade systems 2
180
992
1710
328
247
92
71
310