Bubble BELFORT MARINE Installer'S Instructions Download Page 13

 

 

13 

Chimney heights must be a minimum of 1.8 meter for 
low fire use and 2.2 meter for high fire use. 

Check the stove is fitted with adequate clearances 
from combustibles. 

Check that the combustion air restrictor is 
functioning correctly. 

LIGHTING. 

WARNING FOR BOILER STOVES. 

If the stove is fitted with a boiler, air locks or poor 
water flow through it may cause damage. 

Make sure that the boiler has been vented of all air 
BEFORE ATTEMPTING TO LIGHT THE STOVE. 

Lighting the stove takes a little time and patience; the 
following procedure should be adopted. 

Open the front door.  

Remove the coal kit if it has been supplied with the 
stove.  

Remove the inner mesh catalyser  

Remove the lower burning ring.  

Turn the oil on at full rate and allow oil to flow into 
the bottom of the pot to form a pool about the size of 
a small digestive biscuit and then turn the oil off.  

Do not allow any depth of oil to build up.

 

Light a small piece of firelighter (about the size of a 
pineapple chunk) and place it into the centre of the 
pot. 

Replace the lower burning ring, the mesh catalyser and 
the coal kit and then leave the door slightly open 
whilst the firelighter gets the oil going. 

After 30 to 40 seconds, you will notice the flame start 
to establish itself and spread around the bottom of 
the pot. 

When this occurs, close the door and turn the oil on to 
its minimum setting. 

After two or three minutes the flame should then 
slowly change from yellow into blue flame combustion 
and settle down to a steady burn.  

Note there may be the occasional growl or audible 
vibration whilst the burner settles down into blue 
flame combustion. 

Allow the burner 10 – 15 minutes to stabilise and the 
increase the flow of oil as required, moving by one 
increment of the dial only. 

Do not leave the appliance unattended during the 
lighting and stabilising procedure.

 

COMMISSIONING THE HIGH AND LOW FIRE.

 

There are two types of valve fitted to Bubble stoves 
and access to the low fire adjustment is different. 

On the OCI ships valve the plastic drive knob has to 
be removed to gain access to the low fire screw. 

On the Toby valve the low fire screw is clearly visible 
as per TOBY MANUAL FIG 2 

The valve has been flow rated before leaving the 
factory and it should not need adjusting, if it does it is 
necessary to remove the plastic drive cover (OCI 
VALVE) which is held in place by a single fastener in 
the side face of the knob. 

Once the knob has been removed the low fire 
adjusting screw is clearly visible. 

When the burner has established good blue flame 
combustion turn it up to half output. (Setting 3 on the 
fuel flow control knob) and let it stabilize. 

Allow at least half an hour for the chimney to warm up 
thoroughly before making any adjustments to the high 
or low fire screws. 

Turn the stove down onto minimum firing rate and let 
it stabilize. 

After stabilization there should be a dull red glow in 
the bottom of the lower catalyser with wispy blue 
flames flicking in to the glowing edge of it. 

If the flame falls into a dirty rolling yellow flame and 
the lower catalyser is not dull red then the low fire 
will need to be increased until it can support the 
required blue flame combustion.  

To increase the low fire oil flow, screw the adjusting 
screw in by quarter turn increments. 

When you are happy with the low fire, set the high 
fire. 

Turn the oil flow knob up to setting 4, let the flame 
stabilize, and look at it, if it is stable and blue, turn it 
up slowly using the control knob, letting it stabilize 
after each movement, if the flame starts to go yellow 
with long flame combustion, it is running fuel rich and 
the high fire screw needs adjusting to reduce the flow 
of oil. (Screw the adjuster screw in to reduce the high 
fire oil flow.) 

Before adjusting the high fire screw, turn the flame 
down and let it stabilize in blue flame combustion, 

Summary of Contents for BELFORT MARINE

Page 1: ...Draught copy needs finishing www oilstoves co uk BELFORT MARINE OIL STOVE INSTALLER INSTRUCTIONS ISSUE 2 08 02 03...

Page 2: ...TRIM 8 TANK 8 OIL LINE 8 WATER CONTAMINATION 8 REMOTE SENSING FIREVALVE 9 ISOLATION VALVES 9 SLEEVING 9 5 FIREPLACE 9 6 FITTING DRY STOVES 9 SELECT LOCATION 9 FIT OIL TANK 9 RUN OIL LINE 9 TRIAL FIRE...

Page 3: ...AIR LOCKED SYSTEM PIPEWORK 14 INADEQUATE SYSTEM PRESSURE HEAD 14 INOPERATIVE CIRCULATING PUMP 14 INADEQUATE PIPE SIZEING 14 INADEQUATE CALORIFYER DESIGN 14 INADEQUATE STOVE LOCATION 14 FLOW OF WATER...

Page 4: ...R GLASS 16 LABOUR COSTS 16 TRAVELING COSTS 16 CONSEQUENTIAL LOSS 16 CONSEQUENTIAL DAMAGE 16 If you have any difficulties please phone our technical help line on 01302 742520 fax 01302 750573 E mail sa...

Page 5: ...glass front door opened or cracked or without the lighting port plug fitted 8 The door glass may require light cleaning occasionally depending upon the continuous running time of the stove 9 The stov...

Page 6: ...rom the oil control valve 8 With the increased flow of oil extra heat is generated which in turn stimulates the chimney to work harder and consequently draw more air into the pot to maintain an adequa...

Page 7: ...the excess oil as per instructions in the faultfinding section The stove must be securely fastened down so that it can resist impact or collision and it must be level in both directions The stove must...

Page 8: ...inimum pressure head of out 8 is required This head is measured from the base of the oil tank to the top of the oil control valve In some cases this head can be affected by the ballast or trim of the...

Page 9: ...eeve must be fitted and sealed with a suitable sealant 5 5 F FI IR RE EP PL LA AC CE E Try to use materials which are easy to keep clean and fireproof such as tiles asbestolux or vermiculite boarding...

Page 10: ...PLATE FIT DECK FLANGE If you are going to use a standard deck flange for 6 inch extensions you will have to cut off the lower extension with a grinder to allow fitting of the fire stop spacer The dec...

Page 11: ...ake sure that the vertical sides of the fireplace can easily accommodate the pipe work When installing water heating Bubble stoves the space heating output will be reduced The boiler is high water con...

Page 12: ...y as to make it easily replaceable this means lock shielded valves at either side and easy access 7 7 C CO OM MM MI IS SS SI IO ON NI IN NG G If the stove has been fitted to an existing heating system...

Page 13: ...d stabilising procedure COMMISSIONING THE HIGH AND LOW FIRE There are two types of valve fitted to Bubble stoves and access to the low fire adjustment is different On the OCI ships valve the plastic d...

Page 14: ...1 Turn off the oil flow until the burner has settled down to a steady burn rate and then turn the fuel on again but don t let the flame go out otherwise the burner MUST be allowed to cool down fully...

Page 15: ...ag into the stove and sponge from the pot into the bag when the excess oil has been removed put the plastic bag and sponge into another plastic bag and dispose of it 8 OPERATING OIL FLOW RATES OIL Flo...

Page 16: ...rranty form and returned it to us the information recorded on the warranty form helps us to deal with any problems you may encounter Where we do not hold returned warranty forms replacement parts woul...

Page 17: ...15...

Page 18: ...16...

Page 19: ...17...

Page 20: ...wledged that due to this process there may be some omissions and errors This publication is intended only to assist the reader in the use of this product and therefore Harworth Heating Ltd shall not b...

Reviews: