XT-70 Control Panel
12
Secondary Modes:
None:
There are no secondary modes currently active.
Ramp:
The setpoint and target are different values and the system is in the
Ramp mode. The Ramp mode can ramp the setpoint up or down.
Fan Manual:
The fan MOA switch is in the Manual position. The system will run as
normal.
Cell Pump Fail:
The Cell Pump Fail will trigger when the cell MOA switch is turned to
Auto and the Cell pump input (IN2) is off. There is a programmable
delay timer (CPF_timer) associated with this alarm..
Refrig Fail:
The Refrig Fail Alarm will trigger when the refrigeration MOA switch is
turned to Auto, the refrigeration input (IN3) is off and the system is in
Refrigeration mode. The system will continue to run in Cooling mode if
outside cooling is available.
Plen Sensor Fail:
The Plenum Sensor Fail alarm is triggered by a programmable differ-
ence between Plen 1 and Plen 2. There is a programmable timer
Associated with this alarm.
OSA Sensor Fail:
The Outside Air Sensor Fail alarm is triggered by an out-of-range out-
side air sensor. There is a programmable timer associated with this
alarm.
Fan Boost:
The fan boost has programmable parameters that allow you to specify
certain intervals for the fans to speed up stir the air and then go back to
original speed. On the initial change the fans will speed up 5% per
Minute. On termination the fans will change immediately to the original
speed.
Low Dev:
The Low Dev alarm will trigger when the plenum temperature drops
below the low dev setting, the timer has expired and the fans are run-
ning. There is a programmable timer associated with this alarm.
High Dev:
The High Dev alarm will trigger when the plenum temperature rises
above the high dev setting, the timer has expired and the fans are
running. There is a programmable timer associated with this alarm.
OSH Sensor Fail:
The Outside Humidity Sensor Fail alarm is triggered by a out-of-range
outside humidity sensor. There is a programmable timer
associated with this alarm.
Low Humidity:
The Low Humidity alarm is triggered when the plenum humidity level
drops below the low humidity setting. The system must be in a valid
operating mode. There is a programmable timer associated with this
alarm.
High CO2:
The High CO
2
alarm is triggered by a CO
2
level greater than the high
CO
2
setting. The system must be in a valid operating mode. There is a
programmable timer associated with this alarm.
4.2