BTU VENTILATION CORPORATION
●
OFFICE 888-884-8070
●
FAX 218-346-7485
●
www.btucorp.com
XT-70 Control Panel
102
Purge Cycles During Cure without a CO2 sensor:
Without a CO2 sensor, a purge must be activated by time only. This purge currently re-
quires heat. The purge config would need to be set to 1. This is Time only with no CO2 sen-
sor.
When the purge config is set to 1, the above parameters will show on the Miscellaneous
screen. These parameters will initiate a purge cycle according to the settings. To disable
the time purge, set the parameters to 0.
To do a purge in the Cooling mode the heat
switch must be in Auto.
In Timed or Refrig, the system will pulse the fresh air doors to
Max Open for the length of the cycle. In theory, this will only occur when there is no
cooling air available, thus the air being brought in will be warmer than the pile.
When the CO2 purge
is triggered in the
Cooling mode, it will
be because the OSA
is cold and the fresh
air doors are only
slightly cracked. The
return air heaters will
cause the air to warm
by 3 to 4 degrees,
causing the fresh air
doors to open and
the fans to speed up
to purge the storage.
Back to Start
Time Purge
Mode =
Cooling
OSA < XX
Heat Switch
Auto
Heat on for
YY minutes
Mode =
Timed
Mode =
Refrig
OSA < XX
no
Pulse Fresh Air
Doors to Max Open
for XX minutes
RUN
Hours > ZZ
yes
ZZ Hours
= 0
Mode =
Cooling
Door Closed
Mode =
Cooling
Door Closed
no
yes
yes
no
yes
no
no
yes
no
no
no
yes
yes
yes
no
yes
yes
no