APPENDIX I:
Sweet Potato Operation
Application:
This application note will cover two types of storages. First are the conventional storages with
fresh air doors, such as a conventional potato storage. The second will be storages that have
no fresh air doors, but have roof vents, intake fans and exhaust fans.
In both cases, the Aux 2 switch will turn the Cure or Warming mode on. The Aux2_Config
needs to be set to 188.
To activate the Cure or Warming mode, the time clock must be
set to all Blue.
Aux2_Config must be set to
188
The warming mode is only used when trying to
cure or warm up the product. During this time
the time clock should be set to all blue and the
Aux 2 switch should be set to Auto.
Once the
cure cycle is complete, the Aux 2 switch
should be turned off.
With all of the time clock in Blue and the Aux 2
in Auto, the system will either run in Warming
or Cooling. If the Outside air is less than the
Start temperature then the system will run in Cooling. If the Outside air is greater than the
Start temperature then the system will run in Warming. When the Aux 2 switch is off, then the
system will run in Cooling only.