4.5.2 DWT-II - Insulation shutter
• Check the correct working of insulation shutter
by using device for cluster contacts inspection (spare parts), simulate the insertion: the shutters
must get up completely.
• Visual check of insulation shutter
If there are some parts damaged, Replace those damaged parts (Spare parts)
1.5 Nm