4.5.3 DWT-III - Cluster contacts
• Visual check and cleaning
Open insulation shutter by using device for cluster contact
If necessary (dust, oxidation, blackened, etc.) clean the cluster contacts with dry clothe. If necessary
remove the cluster contacts.
• Check the presence of damaging and replacement
If cleaning is not enough, or there are traces of damaging, remove insulation shutters and replace the
cluster contacts (spare parts):
1.5 Nm
1.5 Nm
5 Nm
1.5 Nm
1.5 Nm
5 Nm