background image

22

23

24

•  Average currents
•  Medium maximum currents
•  Average power and maximum average power
•  Hour meter
•  Active Energy
•  Reactive Energy
•  Partial 3-phase active energy
•  Software version

SINGLE-PHASE LINE:

•  Voltage - Current
•  Active / reactive / apparent power
•  Frequency / 3-phase power factor
•  Average and maximum average current
•  Average Power and maximum average power
•  Hour meter
•  Active Energy
•  Reactive Energy
•  Partial 3-phase active energy
•  Software version

PHASES’ SEQUENCE DETECTION

Press 

OK

. to check the connection of the phases. The error message ERR 123 

appears on the display if the connection is wrong.

HOUR METER

The hour meter counts the hours and minutes of operation. The function is active 
when the system detects the presence of the L1 phase.

TECHNICAL FEATURES

Current inputs: 

TA with secondary rated current 5A (Imax = 1.2 Inom, Ioverload = 20 Inom / 0.5 sec.)

Voltage inputs: 

V phase-phase = 40 ÷ 450V

Dimensions: 

4 DIN modules

Operating temperatures:  

–5 ÷ 55 °C

DISPLAY

Display menu is subdivided into different pages and it changes according to the 
selected connection type.
To scroll the display pages press 

To return to the previous pages press 

4 WIRE LINE:

•  Phase voltage
•  Currents
•  Linked voltages
•  Phase active power P1 / P2 / P3
•  Phase reactive power Q1 / Q2 / Q3
•  3-phase powers: active / reactive / apparent
•  Neutral current / frequency / 3-phase power factor
•  Average currents
•  Average maximum currents
•  Average power and maximum average power
•  Hour meter
•  Active Energy
•  Reactive Energy
•  Partial 3-phase active energy
•  Software version

3-WIRE LINE:

•  Linked voltages
•  Currents
•  3-phase power: active / reactive / apparent
•  Frequency / 3-phase power factor

Interface

RS485

RT=  Characteristic impedance of the cable

         (e.g. 120

 for Belden cable 9841 - 9842).

The end resistances are only inserted 

on the first and last RS-485 nodes in the 

terminals where the cable is connected.

M7TIC/CM

M7TIC/CM

24V

14

  Press 

 to select the desired connection:

 

3n3E

 3-phase 4-wire line, 3 measuring systems

 

3-3E

 3-phase 3-wire line, 2 measuring systems

 

3-2E

 3 phase 3-wire line, 2 measuring systems (Aron)

 

1n1E

 single-phase line

15

  Press 

OK

16

  The display shows 

PMd/ tyPE/ VA (or the last set value)

17

  Press the 

/

 keys to load the quantity that can be associated to the average 

power:

   

W

 active power

   

VA

 reactive power

   

VAR

 apparent power

18

   Press 

OK

19

  The display shows 

PMD/ time / 0015 (or the last set value)

20

  Press the 

/

 keys to load the average power delay time. The delay time can 

be selected on fixed steps: 5 / 8 / 10 / 15 / 20 / 30 / 60

    minutes.

21  

Press 

OK

22

  The display shows 

Addr/ 255 (or the last set value)

23

  Press the 

/

 keys to load the desired address number

 

24

  Press 

OK

 

25

  The display shows 

bAUd   9.6 (or the last set value)

26

  Press the 

/

▼ 

keys to load the desired Baud rate 

27

  Press 

OK

28

  The display shows  

PAr  /  nonE (or the last set value)

 

29

  Press the 

/

▼ 

keys to load the desired parity

 

30

  Press 

OK

31  

The display shows

 

Cont/ 10 (or the last set value)

32

  Press the 

/

▼ 

keys to load the desired contrast level

 

33

  Press 

OK

34

  The display shows 

PASS/0000

35

  Press 

▲ 

to load the access keys (usually 2001)

 

36

  Press 

OK

37  

The display shows

 

ct / 0001

 (or the last set value)

38

  Press the 

/

▼ 

keys to load the external C.T. transformer ratio max. 9999 (e.g. 

800/5A = ratio 160)

 

39 

  Press 

OK

40  

The display shows

 

Vt / 0001.0

 

(or the last set value)

 

41  

Press the

 

/

 

keys to load the external V.T. transformer ratio max. 10.0 (e.g. 

600/100V  =  ratio  6.0).  For  direct  connection,  i.e.  without  external  VT,  it  is 

necessary to load a transformer ratio equal to 

1,0

42  

Press 

OK

43

   The display shows 

SAVE 

for a short time and then the meter automatically 

leaves the programming menu and goes back to the opening screen.

Summary of Contents for M7TIC/CM

Page 1: ...E DI ACCESSO 1 AZZERAMENTO ENERGIA PARZIALE ATTIVA TRIFASE AZZERAMENTO CORRENTI MASSIME AZZERAMENTO POTENZA MEDIA AZZERAMENTO CONTAORE INSERZIONE GRANDEZZA ASSOCIATA POTENZA MEDIA TEMPO INTEGRAZIONE P...

Page 2: ...stato 20 Agire sui tasti per impostare il tempo di integrazione potenza media Il tempo di integrazione selezionabile a passi fissi 5 8 10 15 20 30 60 minuti 21 Premere OK 22 Sul display appare Addr 25...

Page 3: ...t celles du secteur Lors de c blage respecter scrupuleusement le sch ma de saisie une connexion erron e est source in vitable de fausses mesures ou de dommage l appareil PARAM TRES PROGRAMMABLES CODE...

Page 4: ...s pour programmer le rapport de es 600 100V rapporto 6 0 Pour l activation directe savoir sans TV externe il est n cessaire de programmer un rapport de transformation de 1 0 42 Appuyer sur OK 43 Sur l...

Page 5: ...ltage inputs direct or with voltage transformers Caution do not connect the TA secondaries to the earth I1 I2 1 2 I3 V1 V2 V3 Vn SG RS 485 24V I N P U T O U T P U T V1 V2 V3 Vn 4 WIRE NETWORK 3 WIRE N...

Page 6: ...ble 9841 9842 The end resistances are only inserted on the first and last RS 485 nodes in the terminals where the cable is connected M7TIC CM M7TIC CM 24V 14 Press to select the desired connection 3n3...

Page 7: ...cal o est disponible en formato Modbus RTU en RS 485 E 1 Presione contempor neamente OK 2 En la pantalla se visualiza PASS 0000 la cifra activa parpadea 3 Utilice las teclas para establecer la contras...

Page 8: ...s bornes en donde se conecta el cable M7TIC CM M7TIC CM 24V 14 Presione para seleccionar la conexi n deseada 3n3E l nea trif sica 4 hilos 3 sistemas de medida 3 3E l nea trif sica 3 hilos 3 sistemas d...

Reviews: