MOUNTING INSTRUCTIONS

Item 

M7TIC/CM

 does not need any special mechanical or electrical mounting contrivance.

It is designed to be mounted on DIN rail 35 mm. Working is not affected, in any way, by the mounting position.
Before mounting NEMO it is necessary to verify the type of connection as well as the line configuration on which it has to be connected.
Please make sure that data on the label correspond to the real network ones.
In the wiring scrupulously respect the wiring diagram; an error in connection unavoidably leads to wrong measurements or damages to the meter.

PROGRAMMABLE PARAMETERS

ACCESS CODE

Access  to  programming  is  protected  by  a  software  key  composed  of  a  4-digit 
numeric combination.
When one wants to enter the programming mode, the meter prompts the operator 
to type the access combination, allowing or denying, according to loaded code, 
the possibility to modify the parameters.
Programming is subdivided on two levels (with different access keys):

PROGRAMMING

Programming menu is subdivided in different pages: 

•  ACCESS CODE 1

•  PARTIAL ACTIVE 3-PHASE ENERGY RESET

•  MAXIMUM CURRENTS RESET

•  AVERAGE POWER RESET

•  HOUR METER RESET

•  CONNECTION

•  QUANTITY RELATED TO THE AVERAGE POWER

•  AVERAGE POWER DELAY TIME

•  RS485 COMMUNICATION 

•  CONTRAST

•  ACCESS CODE 2

•  C.T. TRANSFORMER RATIO
•  V.T. TRANSFORMER RATIO

For programming are used the 3 keys on the front board: 

OK

  

to confirm the loaded data

  

increases the loaded value

  

to shift the cursor

OK

 + 

   to enter/leave programming menu

OK

 + 

   to return to the previous programming menu page

DESCRIPTION

Item 

M7TIC/CM 

is an electronic device intended for use in monitoring systems, which can measure all the magnitudes of one-phase and three-phase lines.

The information can be shown on local display or is available in Modbus RTU format on RS-485.

GB

+

Tx/Rx Rs485 

-

Tx/Rx Rs485 

SG

Signal mass

24V     power supply 

24V     power supply

Note: 

use power suppliers 

with double insulation or equivalent

 

   - Current transformer inputs

+

Line voltage inputs

(direct or with voltage transformers)

Caution: 

do not connect 

the TA secondaries to the earth

I1 

I2 

1  2 

I3 

V1  V2  V3  Vn 

SG 

RS - 485 

24V 

I N P U T 

O U T P U T 

V1 V2 V3 Vn 

4-WIRE NETWORK

3-WIRE NETWORK:

ONE-PHASE LINE:

do not connect Vn

(do not connect I2 only when 2 

measuring systems are present)
do not connect V2 and V3

do not connect l2 and l3

LEVEL 1

1 RESET

  1.1 Partial 3-phase active energy

  1.2 Maximum currents
  1.3 Average power
  1.4 Hour meter

2 CONNECTION

  2.1  4-wire line, 3 measuring systems
  2.2  3-wire line, 3 measuring systems

  2.3  3-wire line, 2 measuring systems (Aron phases L1-L3  )
  2.4  single-phase line

 

3  AVERAGE POWER

  3.1 Quantity: active, reactive or apparent 3-phase power
  3.2 Delay time: 5/8/10/15/20/30/60 minutes.

4

 

RS485 COMMUNICATION

  4.1 Address number:1÷247
  4.2 Transmission speed: 9600-19200 bit/second
  4.3 Parity

5

 

CONTRAST: 1/10

LEVEL 2

1 TRANSFORMERS RATIOS

  1.1 External C.T. transformer ratio

  1.2 External V.T. transformer ratio

  1

  Simultaneously press 

OK

/

  2

  The display shows 

PASS / 0000

 (active digit blinks)

  3

  Press the 

/

 to load the access key (usually 1000). To access transformers 

ratios programming, point 33, enter the 2001 key and press 

OK

  4

  Press 

OK

  5

  The display shows 

rES / ACtP /no

 partial 3-phase active energy reset

  6

  If you don’t want to reset the partial energy counter, press 

OK

  and go to point 

7. To reset the partial energy counter press the 

/

▼ 

until 

rES / ACtP / YES 

is 

displayed and press

 OK

  7

  The display shows 

rES / lMd / /\ / no 

maximum currents reset

  8

  If you don’t want to reset the maximum currents counter, press 

OK

 and go to 

point 9. To reset the maximum currents counter press the 

/

 keys until the 

display shows 

rES / lMd / /\ / YES 

and then press 

OK

  9

  The display shows 

rES / Pmd /\ / no

 average power reset

10

   If you don’t want to reset the average power counter, press 

OK 

and go to point 

11. To reset the average power counter, press the 

/

 until the display shows 

rES / PMd /\ / YES 

and then press 

OK

11

  The display shows 

rES tIME / no

 hour meter reset

12

  If you don’t want to reset the hour meter, press 

OK

 

and go to point 13. To reset 

the hour meter, press the 

/

 until the display shows 

rES tIME / YES 

and 

then press 

OK

13

  The display shows 

3-4n/3n3E (or the last set connection)

Summary of Contents for M7TIC/CM

Page 1: ...E DI ACCESSO 1 AZZERAMENTO ENERGIA PARZIALE ATTIVA TRIFASE AZZERAMENTO CORRENTI MASSIME AZZERAMENTO POTENZA MEDIA AZZERAMENTO CONTAORE INSERZIONE GRANDEZZA ASSOCIATA POTENZA MEDIA TEMPO INTEGRAZIONE P...

Page 2: ...stato 20 Agire sui tasti per impostare il tempo di integrazione potenza media Il tempo di integrazione selezionabile a passi fissi 5 8 10 15 20 30 60 minuti 21 Premere OK 22 Sul display appare Addr 25...

Page 3: ...t celles du secteur Lors de c blage respecter scrupuleusement le sch ma de saisie une connexion erron e est source in vitable de fausses mesures ou de dommage l appareil PARAM TRES PROGRAMMABLES CODE...

Page 4: ...s pour programmer le rapport de es 600 100V rapporto 6 0 Pour l activation directe savoir sans TV externe il est n cessaire de programmer un rapport de transformation de 1 0 42 Appuyer sur OK 43 Sur l...

Page 5: ...ltage inputs direct or with voltage transformers Caution do not connect the TA secondaries to the earth I1 I2 1 2 I3 V1 V2 V3 Vn SG RS 485 24V I N P U T O U T P U T V1 V2 V3 Vn 4 WIRE NETWORK 3 WIRE N...

Page 6: ...ble 9841 9842 The end resistances are only inserted on the first and last RS 485 nodes in the terminals where the cable is connected M7TIC CM M7TIC CM 24V 14 Press to select the desired connection 3n3...

Page 7: ...cal o est disponible en formato Modbus RTU en RS 485 E 1 Presione contempor neamente OK 2 En la pantalla se visualiza PASS 0000 la cifra activa parpadea 3 Utilice las teclas para establecer la contras...

Page 8: ...s bornes en donde se conecta el cable M7TIC CM M7TIC CM 24V 14 Presione para seleccionar la conexi n deseada 3n3E l nea trif sica 4 hilos 3 sistemas de medida 3 3E l nea trif sica 3 hilos 3 sistemas d...

Reviews: