Default settings
9
5
ekr 500 web guiding controller
EDV No.: MD.299.01.06
Chapter: 9
with removable control panel
Date:
29.07.08
Page:
75/86
9 Default
settings
9.1 Device
addresses
The device addresses of the controller and the control panel are
preset by manufacturer.
The settings usually do not have to be modified.
Check the device address settings if faulty operation or non-
defined controller or control panel processes occur.
9.1.1 Device address
of the controller
The device address of the controller is preset to “
1
“ by
manufacturer (delivery state).
You are only allowed to modify the device address
if authorised to do so by the manufacturer!
The setting of the device address of the controller is carried out via
the rotary switch
S1
on the processor board.
Danger from mains voltage!
Never open the controller
before switching off the
mains!
Set device adress:
1. Switch off controller line voltage.
2. Open the controller enclosure cover.
3. Check that the rotary switch
S1
on the processor board is set
correctly. The rotary switch
S1
must be set to position “
1
“.
4. Switch the rotary switch
S1
to position “
1
“ if necessary.
5. Close the controller enclosure cover.
6. Switch on controller line voltage again.
Rotary switch S1
0 1 2
3
45
67
8
9