background image

5

Crankcase Heater

The crankcase heater prevents refrigerant migration and

compressor oil dilution during shutdown when compressor is not
operating. If the crankcase heater is de--energized for more than 6

hours, both compressor service valves must be closed.

NOTE

:

Crankcase heaters are only factory--supplied on

538A030--060 units. Addition of an accessory crankcase heater is
required for long line and low ambient cooling applications on 018
and 024 size units. See Residental Long Line Guideline.
The crankcase heater is powered by the high--voltage power of the
unit. It is connected across the line side of the contactor and is

thermostatically controlled.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury

or death.
Use extreme caution when troubleshooting this device as line

voltage is continually present.

To troubleshoot:

1. Apply voltmeter across crankcase heater leads to see if heat-

er voltage is on. Do not touch heater. Carefully feel area

around crankcase heater; if warm, crankcase heater is func-
tioning.

2. With power off and heater leads disconnected, check across

leads with ohmmeter. Do not look for a specific resistance
reading. Check for resistance or an open circuit, and change

heater if an open circuit is detected.

Service Valves

The service valves in the outdoor unit come from the factory

frontseated. This means the refrigerant charge is isolated from the

line--set connection ports. To prevent damage to the valve, use a
wet cloth or other accepted heat sink material on the valve before

brazing.
The service valve cannot be field repaired, therefore, only a

complete valve or valve stem seal and service port caps are

available for replacement.

Refrigerant Charging

!

WARNING

PERSONAL

INJURY

AND/OR

EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Wear safety glasses and gloves when handling refrigerant.

Do not overcharge system -- this can cause compressor

flooding.

!

WARNING

PERSONAL

INJURY

AND/OR

EQUIPMENT

DAMAGE HAZARD

Failure to follow this warning could result in personal injury

and/or equipment damage.
Service valves must be fully backseated to close service

port. There is no Schrader valve at the service port, and

failure to backseat the valve could result in loss of system

charge or personal injury.

NOTE

:

Do not vent or de--pressurize unit refrigerant to

atmosphere. Remove and recover refrigerant following accepted
practices.
All units are shipped with the refrigerant charge listed on the
nameplate.
Refer to Product Data and consider the following when working

with Puron (R--410A) refrigerant:

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400
psig, DOT (Department of Transportation) 4BA400 or

DOT BW400.

S

Puron systems should be charged with liquid refrigerant.
Use a commercial type metering device in the manifold

hose when charging into suction line with compressor op-
erating.

S

Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low--side retard.

S

Use hoses with 700 psig service pressure rating.

S

Puron refrigerant, as with other HFCs, is only compatible
with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Polyol Ester oils absorb moisture rapidly. Do not expose oil
to atmosphere.

S

Polyol Ester oils may cause damage to certain plastics and
roofing materials.

S

Wrap all filter driers and service valves with wet cloth when
brazing.

S

factory approved, liquid--line filter drier is required on ev-

ery unit.

S

Do not use a TXV (thermostatic expansion valve) designed
for use with R--22 refrigerant. Refer to separate indoor unit
installation instructions for more details.

S

f using a suction line drier, do not leave in place for more
than 72 hours.

Check Charge

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be
favorable for subcooling charging. Favorable conditions exist

when the outdoor temperature is between 70

_

F and 100

_

F (21

_

C

and 38

_

C), and the indoor temperature is between 70

_

F and 80

_

F

(21

_

C and 27

_

C). Follow the procedure below:

Unit is factory charged for 15 ft (4.6 m) of line--set. Adjust charge

by adding or removing 0.6 oz/ft of 3/8 liquid line above or below

15 ft (4.6 m) respectively.
For standard refrigerant line lengths (80 ft/24 m or less), allow

system to operate in cooling mode at least 15 minutes. If conditions
are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly
charged system.
If the indoor temperature is above 80

_

F (27

_

C), and the outdoor

temperature is in the favorable range, adjust system charge by

weight based on line length and allow the indoor temperature to
drop to 80

_

F (27

_

C) before attempting to check system charge by

subcooling method as described above.
If the indoor temperature is below 70

_

F (21

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15 ft (4.6 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

538A

Reviews: