When demand ventilation control is not being used, the minimum
position potentiometer should be used to set the occupied ventilation
position. The maximum demand ventilation position should be
turned fully clockwise. Adjust the minimum position potentiometer
to allow the minimum amount of outdoor air, as required by local
codes, to enter the building. Make minimum position adjustments
with at least 10
_
F (12.2
_
C) temperature difference between the
outdoor and return--air temperatures. To determine the minimum
position setting, perform the following procedure:
1. Calculate the appropriate mixed air temperature using the
following formula:
(T
o
x OA/100) + (T
R
x RA/100) = T
M
T
O
= Outdoor--Air Temperature
OA = Percent of Outdoor Air
T
R
= Return--Air Temperature
RA = Percent of Return Air
T
M
= Mixed--Air Temperature
As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor--air temperature is
60
_
F (15.6
_
C), and return--air temperature is 75
_
F
(23.9
_
C). (60 x .10) + (75 x .90) = 73.5
_
F (23.1
_
C)
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory--installed jumper is in place across
terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to
Fig. 44 and that the minimum position potentiometer is
turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer until
the measured mixed--air temperature matches the calculated
value.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the Economizer damper is desirable when
requiring additional temporary ventilation. If a field--supplied
remote potentiometer (Honeywell part number S963B1128) is
wired to the Economizer controller, the minimum position of the
damper can be controlled from a remote location. To control the
minimum damper position remotely, remove the factory installed
jumper on the P and P1 terminals on the Economizer controller.
Wire the field--supplied potentiometer to the P and P1 terminals on
the Economizer controller. See Fig. 43 and Fig. 44.
604D
--
--
A
Summary of Contents for LEGACY 604D-A
Page 4: ...4 A09471 Fig 2 604D A24 36 Unit Dimensions 604D A ...
Page 5: ...5 A09472 Fig 3 604D A42 60 Unit Dimensions 604D A ...
Page 12: ...12 A10197 Fig 11 Connection Wiring Schematics 208 230 1 60 604D A ...
Page 13: ...13 A10197 Fig 11 Cont Ladder Wiring Schematics 208 230 1 60 604D A ...
Page 14: ...14 A10194 Fig 12 Connection Wiring Schematics 208 230 3 60 604D A ...
Page 15: ...15 A10194 Fig 12 Cont Ladder Wiring Schematics 208 230 3 60 604D A ...
Page 16: ...16 A10195 Fig 13 Connection Wiring Diagram 460 3 60 604D A ...
Page 17: ...17 A10195 Fig 13 Cont Ladder Wiring Diagram 460 3 60 604D A ...
Page 25: ...25 A09070 Fig 17 Cooling Charging Table Subcooling 604D A ...
Page 43: ...43 A10059 Fig 44 Economizer Wiring Diagram 604D A ...
Page 45: ...45 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 604D A ...
Page 46: ...46 A10199 Fig 46 Connection Wiring Diagram 460 3 604D A ...
Page 47: ...47 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 604D A ...