29
PURON
R
(R--410A) QUICK REFERENCE GUIDE
S
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S
Puron refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S
Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard.
S
Use hoses with minimum700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Do not use liquid--line filter driers with rated working pressures less than 600 psig.
S
Do not leave Puron suction line filter driers in line longer than 72 hours.
S
Do not install a suction--line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A factory approved liquid--line filter drier is required on every unit.
S
Do NOT use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S
Do not vent Puron into the atmosphere.
S
Observe all
warnings
,
cautions
, and
bold
text.
S
All indoor coils must be installed with a hard shutoff Puron TXV metering device.
604D
--
--
A
Summary of Contents for LEGACY 604D-A
Page 4: ...4 A09471 Fig 2 604D A24 36 Unit Dimensions 604D A ...
Page 5: ...5 A09472 Fig 3 604D A42 60 Unit Dimensions 604D A ...
Page 12: ...12 A10197 Fig 11 Connection Wiring Schematics 208 230 1 60 604D A ...
Page 13: ...13 A10197 Fig 11 Cont Ladder Wiring Schematics 208 230 1 60 604D A ...
Page 14: ...14 A10194 Fig 12 Connection Wiring Schematics 208 230 3 60 604D A ...
Page 15: ...15 A10194 Fig 12 Cont Ladder Wiring Schematics 208 230 3 60 604D A ...
Page 16: ...16 A10195 Fig 13 Connection Wiring Diagram 460 3 60 604D A ...
Page 17: ...17 A10195 Fig 13 Cont Ladder Wiring Diagram 460 3 60 604D A ...
Page 25: ...25 A09070 Fig 17 Cooling Charging Table Subcooling 604D A ...
Page 43: ...43 A10059 Fig 44 Economizer Wiring Diagram 604D A ...
Page 45: ...45 A10200 Fig 45 Cont Ladder Wiring Diagram 230 3 604D A ...
Page 46: ...46 A10199 Fig 46 Connection Wiring Diagram 460 3 604D A ...
Page 47: ...47 A10199 Fig 46 Cont Ladder Wiring Diagram 460 3 604D A ...