background image

3

NOTE

: Wiring of the ABCD bus only requires a four--wire

connection; however, it is good practice to run thermostat cable
having more than four wires in the event of a damaged or broken
wire during installation.
The following color code is recommended for each ABCD bus

connection:

A

— Green = Data A

B

— Yellow = Data B

C

— White = 24 VAC (Com)

D

— Red = 24VAC (Hot)

It is not mandatory that the above color code be used, but each bus
connection in the system

MUST

be wired consistently.

Step 3 — Install Components

INSTALL Evolution

r

DAMPER CONTROL

The Evolution

r

Damper Control is designed so that wires can enter

it from behind, above, or below. Plan wire routing before mounting
Damper Control.

1. Remove cover to access mounting holes.
2. Mount back plate to wall using screws and wall anchors

provided.

3. Level back plate and tighten screws.

INSTALL MASTER ZONING WALL CONTROL

See the Evolution

r

Connex

t

wall control Installation Instructions

for details.

NOTE

: Improper wiring of the ABCD connector will cause the

Evolution

r

Zoning System to operate improperly. Check to make

sure all wiring is correct before proceeding with installation or
turning on power.

INSTALL REMOTE ROOM SENSORS

1. Separate the sensor cover and mounting back plate by

squeezing the top and bottom of the cover together firmly

by grasping the raised top and bottom ridges. This will re-
lease the cover. Mount to the wall using the screws and an-
chors provided.

2. Pull a 2--conductor wire through hole on right--hand side.
3. Recommended connection is BLACK to either terminal,

WHITE to remaining terminal (sensor terminals are not
marked for polarity because polarity is not important).
Stranded or common bell wire may be used. Lengths up to

1000 ft. will contribute no noticeable error.

4. Push any extra wire into the wall and seal the hole to pre-

vent air leaks. Align the sensor cover with the base plate,
then press firmly until the cover snaps into place.

INSTALL ZONING SMART SENSOR

See the Evolution

r

Zoning Smart Sensor Installation Instructions

for details.

Step 4 — Install Zone Dampers

Proper selection and sizing of dampers is very important for proper

system operation. Be sure to consult the Damper Product Data
Sheet and Evolution

r

Zoning Design Guide for assistance in

making these selections. Selection and sizing information is not
provided in this installation instruction. Zone dampers are available

in round, rectangular, and slip--in design, and may be installed in

any position. Install the damper so that the actuator is visible for
inspection and accessible in the event it would need to be serviced.

The black mark on the end of the damper shaft represents the
position of the damper blade. To wire the damper, locate the

terminals labeled: OPN (open); COM (common); CLS (closed; and

wire appropriately (see Fig. 1 for Damper 24 VAC connection).

SET SCREW

MOUNTING HUB

ANTI-ROTATION

MOUNTING SCREW

3/16"

GAP

D

AMPER

3/16"

GAP

SET SCREW

MOUNTING HUB

ACTUATOR

HOUSING

QUICK BLADE

RELEASE

(CLS) CLOSED
(COM) COMMON

(OPN) OPEN

ANTI-ROTATION

MOUNTING SCREW (5/16")

PLASTIC COVER

CLS COM OPN

CLS

COM

OPN

Fig. 1 -- Damper 24VAC Connections

C03024

If the duct system requires multiple dampers for a single zone, up
to five dampers (maximum) may be wired in parallel. For all

applications, including retrofit, it is recommended to use only
current dampers with direct--drive style actuators.

DO NOT

use

older damper with crank--arm style actuators.
If an actuator is removed from a damper for any reason, it must be

properly aligned when it is reinstalled. This can be done by

rotating the actuator and the blade to their closed positions and
then tightening the actuator (set screw) to the shaft. This assures

alignment at the closed position. (Pressing the quick blade release
button allows the actuator to be manually turned.)

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Condensation can damage the actuator. When dampers are

located in an unconditioned space, condensation is likely to

occur in cooling. To prevent condensation and losses, all

dampers and ductwork in unconditioned space must be

insulated or otherwise protected.

CAUTION

!

Whenever condensation might occur, it is recommended that a

plastic actuator cover (p/n, DAMPACTXXCOV) be used over the
actuator. This cover can help prevent condensation on the actuator

by helping to keep out ambient humidity. Insulation may be

applied over the cover to minimize heat transfer.
To install, place the cover over the actuator and seal it in place over

the surrounding insulation with duct tape on all four sides. Sealing
need not be perfect because there will be positive pressure inside

the cover. Do not mount the dampers with their actuators hanging

directly beneath the ductwork. It is best to mount the actuator
facing in either the three or nine o’clock position.
For specific duct types, follow the instructions below:

NOTE

:

All zone dampers and ductwork must be properly

supported according to local codes or SMACNA standards.

Summary of Contents for Evolution SYSTXBB4ZC01

Page 1: ...ing zoning systems This instruction covers the physical installation and start up of the Evolutionr Damper Control Use this instruction to guide the actual installation process after all the air side decisions have been made One Damper Control is capable of handling up to four zones of operation When greater than four zones are required a second Damper Control Module is needed for zones 5 through ...

Page 2: ...ortant consideration ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent possible damage to the Evolutionr Damper Control do not mount on plenum ductwork or flush against surface CAUTION LOCATING MASTER ZONING WALL CONTROL The Evolutionr Connext wall control is the command center for the Evolutionr Zone System It should be loca...

Page 3: ... and slip in design and may be installed in any position Install the damper so that the actuator is visible for inspection and accessible in the event it would need to be serviced The black mark on the end of the damper shaft represents the position of the damper blade To wire the damper locate the terminals labeled OPN open COM common CLS closed and wire appropriately see Fig 1 for Damper 24 VAC ...

Page 4: ...e end of the flexible ductwork over the zone damper end See Fig 5 2 Secure flexible duct to the zone damper using SMACNA or other approved method 3 Properly seal the joint using duct tape mastic or other ap proved method Do not allow mastic to come in contact with the actuator 4 If dampers are applied in an unconditioned space insulate them using 1 1 2 inch to 2 inch insulation See Fig 6 FLEXIBLE ...

Page 5: ...OOM SENSOR WILL OVERRIDE USER INTERFACE TEMPERATURE SENSOR Zone 2 Damper Zone 3 Damper Zone 4 Damper Status LEDs DIP Switch Zones 1 4 Damper Control Module Zones 1 4 ABCD Connection A Green RS485 B Yellow RS485 C White 24VAC COM D Red 24VAC HOT Dampers CLS_ Close COM_ Common OPN_ Open F U S E 1 2 ON A B C D Zoning User Interface Smart Sensor s Connection A B C D Indoor Unit A B C D A B C D 2 spd O...

Page 6: ...mp applications measures the temperature of the air leaving the indoor coil The sensor is installed downstream of the indoor coil but before the electric heaters It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet Anchor firmly in place with cable ties so that it cannot interfere with the blower wheel See Fig 9 LED INDICATORS Un...

Page 7: ... Control display says Outdoor Unit Not Found when applied with a two speed communicat ing outdoor unit Recheck the wiring to the ABCD connector on the outdoor unit Make sure all colors match for every terminal Evolutionr Connext Wall Control cannot find Zones 5 8 1 Make sure zone module 5 8 has the dip switches set to the far right 2 Recheck the wiring to the ABCD connections Evolutionr Connext wa...

Page 8: ...310 W Morris St S Indianapolis IN 46231 Edition Date 9 15 U S Export Classification EAR99 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II DAMP4ZC 03 Replaces II DAMP4ZC 02 ...

Reviews: