background image

8

Copyright 2015 Bryant Heating and Cooling Systems

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Edition Date: 9/15

U.S. Export Classification: EAR99.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: II---DAMP4ZC---03

Replaces: II--- DAMP4ZC--- 02

Summary of Contents for Evolution SYSTXBB4ZC01

Page 1: ...ing zoning systems This instruction covers the physical installation and start up of the Evolutionr Damper Control Use this instruction to guide the actual installation process after all the air side decisions have been made One Damper Control is capable of handling up to four zones of operation When greater than four zones are required a second Damper Control Module is needed for zones 5 through ...

Page 2: ...ortant consideration ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent possible damage to the Evolutionr Damper Control do not mount on plenum ductwork or flush against surface CAUTION LOCATING MASTER ZONING WALL CONTROL The Evolutionr Connext wall control is the command center for the Evolutionr Zone System It should be loca...

Page 3: ... and slip in design and may be installed in any position Install the damper so that the actuator is visible for inspection and accessible in the event it would need to be serviced The black mark on the end of the damper shaft represents the position of the damper blade To wire the damper locate the terminals labeled OPN open COM common CLS closed and wire appropriately see Fig 1 for Damper 24 VAC ...

Page 4: ...e end of the flexible ductwork over the zone damper end See Fig 5 2 Secure flexible duct to the zone damper using SMACNA or other approved method 3 Properly seal the joint using duct tape mastic or other ap proved method Do not allow mastic to come in contact with the actuator 4 If dampers are applied in an unconditioned space insulate them using 1 1 2 inch to 2 inch insulation See Fig 6 FLEXIBLE ...

Page 5: ...OOM SENSOR WILL OVERRIDE USER INTERFACE TEMPERATURE SENSOR Zone 2 Damper Zone 3 Damper Zone 4 Damper Status LEDs DIP Switch Zones 1 4 Damper Control Module Zones 1 4 ABCD Connection A Green RS485 B Yellow RS485 C White 24VAC COM D Red 24VAC HOT Dampers CLS_ Close COM_ Common OPN_ Open F U S E 1 2 ON A B C D Zoning User Interface Smart Sensor s Connection A B C D Indoor Unit A B C D A B C D 2 spd O...

Page 6: ...mp applications measures the temperature of the air leaving the indoor coil The sensor is installed downstream of the indoor coil but before the electric heaters It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet Anchor firmly in place with cable ties so that it cannot interfere with the blower wheel See Fig 9 LED INDICATORS Un...

Page 7: ... Control display says Outdoor Unit Not Found when applied with a two speed communicat ing outdoor unit Recheck the wiring to the ABCD connector on the outdoor unit Make sure all colors match for every terminal Evolutionr Connext Wall Control cannot find Zones 5 8 1 Make sure zone module 5 8 has the dip switches set to the far right 2 Recheck the wiring to the ABCD connections Evolutionr Connext wa...

Page 8: ...310 W Morris St S Indianapolis IN 46231 Edition Date 9 15 U S Export Classification EAR99 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II DAMP4ZC 03 Replaces II DAMP4ZC 02 ...

Reviews: