background image

2

S

Evolution

r

Connex

t

Wall Control (p/n SYSTXCBBECC01,

SYSTXBBECW01, or SYSTXBBECN01) — Each installation

has only one Master wall/zoning control. This is the command
center for the entire system. It will typically be located in Zone 1

to sense and control the temperature in this zone. If desired, a

Remote Room Sensor or a Smart Sensor may be used to sense the
Zone 1 temperature. This can give the installer some flexibility in

locating the Master Evolution

r

Connex

t

wall control to another

area.

S

Remote Room Sensor (p/n SYSTXBBRRS01) — Any zone may

use a Remote Room Sensor (including Zone 1). This is a
temperature sensor only, having no additional user inputs. In

applications where zone temperature averaging may be desired,
this may be done using 4 Remote Room Sensors in a series /

parallel wiring configuration (See Fig. 11 for Remote Room

Sensor Averaging).

S

Smart Sensor (p/n SYSTXBBSMS01) — Any zone may use a

Smart Sensor (including Zone 1). It provides a temperature
display and buttons to adjust the desired temperature in that zone

only. It also displays the outdoor temperature and indoor
humidity.

Be sure to select the desired sensor type for each zone. Zone sensors

other than the Evolution

r

Connex

t

wall control must be purchased

separately. Installation Instructions for these sensors are included

with them.

INSTALLATION

Step 1 — Check Equipment and Job Site

INSPECT EQUIPMENT—File claim with shipping company,

prior to installation, if shipment is damaged or incomplete.

Step 2 — Component Location and Wiring

Considerations

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing sensor, turn off all power to unit. There may

be more than one power disconnect.

!

WARNING

NOTE

: All wiring must comply with national, local, and state

codes.

LOCATING Evolution

r

DAMPER CONTROL

All system wiring is run back to the Evolution

r

Damper Control.

Select a location near the Evolution

r

furnace or fan coil where

wiring from the Evolution

r

Connex

t

wall control, each Remote

Room Sensor or Smart Sensor, each damper actuator, and the

equipment itself can come together easily.
The Evolution

r

Damper Control is approved for indoor use only

and should never be installed with any of its components exposed
to the elements. The Evolution

r

Damper Control (and the zone

dampers) may be installed in any area where the temperature

remains between --4

F to 158

F (--20

C to 70

C), and where

there is no condensation. The cover must be installed to prevent

damage from other sources. Do not locate where it will be
accessible to children. It may be mounted in either vertical or

horizontal position. Remember that wiring access is likely the most

important consideration.

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
To prevent possible damage to the Evolution

r

Damper

Control, do not mount on plenum, ductwork, or flush against

surface.

CAUTION

!

LOCATING MASTER ZONING WALL CONTROL

The Evolution

r

Connex

t

wall control is the command center for

the Evolution

r

Zone System. It should be located where it is easily

accessible and visible to home or business owner. It is also

normally the Zone 1 sensor and as such needs to be located to

properly measure the temperature in Zone 1. If these two
requirements conflict, a separate Remote Room Sensor can be

added for Zone 1.
When a Remote Room Sensor is connected to Zone 1 terminals

(ZS1 and ZS1C) of the Evolution

r

Damper Control, the system

automatically switches to using this sensor for Zone 1 and ignores
the sensor within the Evolution

r

Connex

t

wall control. This

arrangement allows the Evolution

r

Connex

t

wall control to be

located at any convenient place within the home or business. In this

arrangement, only the Zone 1 Remote Room Sensor must be
located in Zone 1.

NOTE

: The Evolution

r

Connex

t

wall control also controls

humidity functions. If the wall control is not used to control Zone 1
temperature, it must still be located in a suitable area where
humidity control will not be affected.

LOCATING SENSORS

For proper operation, each sensor must accurately measure the

temperature

within

its

zone.

For

accurate

temperature

measurement, the following guidelines should be followed:

Sensor should be mounted:

S

Approximately 5 ft. (1.5m) from floor.

S

Close to the center of its zone, preferably on an inside wall.

S

On a section of wall without pipes or duct work.

Sensor should NOT be mounted:

S

Close to a window, on an outside wall, or next to a door leading to

the outside.

S

Where it will be exposed to direct light and heat from a lamp, sun,
fireplace, or other temperature radiating object which may cause a

false reading.

S

Close to or in direct airflow from supply registers.

S

In areas with poor air circulation, such as behind a door or in an

alcove.

WIRING CONSIDERATIONS

Ordinary thermostat wire is ideal when wiring the Evolution

r

Zoning System (shielded cable is not necessary). Use 20 AWG or

larger for typical installations. Lengths over 100 ft. should use 18
AWG or larger wire. Remote Room Sensors require only two

conductors, but it is recommended that at least four conductors be
run. This will allow a Smart Sensor to replace the Remote Room

Sensor with no wiring changes at a later date. The Evolution

r

Connex

t

wall control requires four conductors, each damper

actuator requires three conductors. Cut off or fold back and tape

any unneeded wires. Plan the routing of wiring early to avoid
possible problems later. Remember, all wires converge at the

Evolution

r

Damper Control, so its location is important.

Summary of Contents for Evolution SYSTXBB4ZC01

Page 1: ...ing zoning systems This instruction covers the physical installation and start up of the Evolutionr Damper Control Use this instruction to guide the actual installation process after all the air side decisions have been made One Damper Control is capable of handling up to four zones of operation When greater than four zones are required a second Damper Control Module is needed for zones 5 through ...

Page 2: ...ortant consideration ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent possible damage to the Evolutionr Damper Control do not mount on plenum ductwork or flush against surface CAUTION LOCATING MASTER ZONING WALL CONTROL The Evolutionr Connext wall control is the command center for the Evolutionr Zone System It should be loca...

Page 3: ... and slip in design and may be installed in any position Install the damper so that the actuator is visible for inspection and accessible in the event it would need to be serviced The black mark on the end of the damper shaft represents the position of the damper blade To wire the damper locate the terminals labeled OPN open COM common CLS closed and wire appropriately see Fig 1 for Damper 24 VAC ...

Page 4: ...e end of the flexible ductwork over the zone damper end See Fig 5 2 Secure flexible duct to the zone damper using SMACNA or other approved method 3 Properly seal the joint using duct tape mastic or other ap proved method Do not allow mastic to come in contact with the actuator 4 If dampers are applied in an unconditioned space insulate them using 1 1 2 inch to 2 inch insulation See Fig 6 FLEXIBLE ...

Page 5: ...OOM SENSOR WILL OVERRIDE USER INTERFACE TEMPERATURE SENSOR Zone 2 Damper Zone 3 Damper Zone 4 Damper Status LEDs DIP Switch Zones 1 4 Damper Control Module Zones 1 4 ABCD Connection A Green RS485 B Yellow RS485 C White 24VAC COM D Red 24VAC HOT Dampers CLS_ Close COM_ Common OPN_ Open F U S E 1 2 ON A B C D Zoning User Interface Smart Sensor s Connection A B C D Indoor Unit A B C D A B C D 2 spd O...

Page 6: ...mp applications measures the temperature of the air leaving the indoor coil The sensor is installed downstream of the indoor coil but before the electric heaters It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet Anchor firmly in place with cable ties so that it cannot interfere with the blower wheel See Fig 9 LED INDICATORS Un...

Page 7: ... Control display says Outdoor Unit Not Found when applied with a two speed communicat ing outdoor unit Recheck the wiring to the ABCD connector on the outdoor unit Make sure all colors match for every terminal Evolutionr Connext Wall Control cannot find Zones 5 8 1 Make sure zone module 5 8 has the dip switches set to the far right 2 Recheck the wiring to the ABCD connections Evolutionr Connext wa...

Page 8: ...310 W Morris St S Indianapolis IN 46231 Edition Date 9 15 U S Export Classification EAR99 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II DAMP4ZC 03 Replaces II DAMP4ZC 02 ...

Reviews: