42
6.4.1.
Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to
be exercised. With self--identifying electric heaters, three stages of electric heat are
available to be exercised in any combination. Non--identifying heaters will only
provide one stage of heat. After the selections are made, touch
START
.
S
Low Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
Medium Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
6.4.2.
Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high
heat run time are selected. The furnace will execute its ignition start--up sequence.
This sequence will be displayed on the screen. After the gas valve and blower
motor turn on, the screen will show the current operating status of the furnace. After
the selections are made, touch
START
.
S
Low Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
S
High Heat:
Selectable from 0 to 120 minutes
d
Default = 5 minutes
6.4.3.
Hydronic
This option allows the hydronic heat relay to be exercised. First, it will energize the
relay and turns on the blower. This sequence will be displayed on the screen. After
the selections are made, touch
START
.