34
6.3.4.5.
AC/Heat Pump RPM Max
Used with variable capacity heat pumps,
this option clamps the operating speed
of the heat pump to this maximum value. Used to reduce operating noise while in
high heating capacity. Reducing this value will reduce the heating capacity of the
heat pump. After the selection is made, touch
SAVE
.
S
AC Heat Pump Max RPM:
Adjustable from 4500 – 7000
d
Default = 4500 RPM
d
Default = Off
6.3.4.6.
Defrost Fan Delay
Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12
seconds. This helps to reduce any nuisance refrigerant noise caused by the
switching reversing valve. This setup is only available on communicating heat
pumps. After the selection is made, touch
SAVE
.
S
Defrost Fan Delay:
Yes or No
d
Default = No
6.3.4.7.
Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor
unit control. This setup is only available on communicating heat pumps. After the
selection is made, touch
SAVE
.
S
Brownout Disable:
On or Off
d
Default = Off
6.3.5.
Heat Source Lockout
First touch
SETUP
, then touch
HEAT SOURCE LOCKOUTS
to set up the
parameters for the AC/Heat Pump unit.