![Bryant DURAPAC 579F Installation, Start-Up And Service Instructions Manual Download Page 27](http://html1.mh-extra.com/html/bryant/durapac-579f/durapac-579f_installation-start-up-and-service-instructions-manual_2822196027.webp)
—
27
—
Table 23 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates standard low/medium static drive package.
**Indicates alternate high static-drive package.
††Due to belt and pulley size, pulley cannot be set to this number of
turns open.
NOTE:
For speeds not listed above, field-supplied drives are required.
Table 24 — Evaporator-Fan Motor Data
LEGEND
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range
of the motors can be utilized with confidence. Using the fan motors up to the horsepower (brake kilowatt) rat-
ings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not
be affected.
NOTE:
All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the
Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
Table 25 — Evaporator-Fan Motor Efficiency
NOTE:
All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
UNIT 579F
MOTOR PULLEY TURNS OPEN
0
1/
2
1
1
1/
2
2
2
1/
2
3
3
1/
2
4
4
1/
2
5
5
1/
2
6
180†
††
††
1179
1150
1121
1093
1064
1035
1006
978
949
920
891
180**
††
††
1550
1522
1488
1455
1422
1389
1356
1323
1289
1256
1227
216†
††
††
1095
1077
1058
1040
1021
1002
984
965
947
928
910
216**
††
††
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
240†
††
††
1225
1209
1187
1165
1143
1120
1098
1076
1053
1031
1002
240**
††
††
1458
1434
1407
1381
1354
1328
1301
1275
1248
1222
1193
300†
††
††
1283
1269
1247
1225
1203
1182
1160
1138
1116
1095
1066
300**
††
††
††
††
1551
1524
1497
1470
1443
1415
1388
1361
1332
UNIT
579F
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
CONTINUOUS BkW*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
180
208/230
4.25
3.17
3,775
10.5
460
4.25
3.17
3,775
4.8
216
208/230
5.90
4.40
5,180
15.8
460
7.9
240
208/230
8.70
6.49
7,915
22.0
460
9.50
7.08
8,640
13.0
300
208/230
10.20
7.61
9,510
28.0
460
11.80
8.80
11,000
14.6
BHP —
Brake Horsepower
BkW —
Brake Kilowatts
UNIT
579F
MOTOR EFFICIENCY
(%)
180 (3.7 Hp)
85.8
216 (5 Hp)
87.5
240 (7.5 Hp)
88.5
300 (10 Hp)
89.5