Table 14 — Fan Performance — 579F216 and 240 (Low Heat Units)
LEGEND
NOTES:
1. Standard low-medium static drive range for size 216 is 910 to 1095 rpm.
Standard low-medium static drive range for size 240 is 1002 to 1225 rpm.
Alternate high-static drive range for size 216 is 1069 to 1287. Alternate high-
static drive range for size 240 is 1193 to 1458 rpm. Other rpms require a
field-supplied drive.
2. Maximum continuous bhp for size 216 is 5.90. Maximum continuous bhp for
size 240 is 8.7 (208/230 v) or 9.5 (460 v). The maximum continuous watts for
size 216 is 5180. The maximum continuous watts for size 240 is 7915
(208/230 v) or 8640 (460 v). Do not adjust motor rpm such that motor maxi-
mum bhp and/or watts is exceeded at the maximum operating cfm.
3. Static pressure losses (i.e.,EconoMi$erIV) must be added to external static
pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing losses. See
Table 21 for accessory/FIOP static pressure information.
6. Extensive motor and drive testing on these units ensures that the full horse-
power and watts range of the motor can be utilized with confidence. Using
the fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your local
Bryant representative for details.
Table 15 — Fan Performance — 579F300 (Low Heat Units)
LEGEND
NOTES:
1. Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
2. Maximum continuous bhp is 10.2 (208/230 v) or 11.8 (460 v) and the maxi-
mum continuous watts are 9510 (208/230 v) or 11,000 (460 v). Do not adjust
motor rpm such that motor maximum bhp and/or watts is exceeded at the
maximum operating cfm.
3. Static pressure losses (i.e., EconoMi$erIV) must be added to external static
pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing losses. See
Table 21 for accessory/FIOP static pressure information.
6. Extensive motor and drive testing on these units ensures that the full horse-
power and watts range of the motor can be utilized with confidence. Using
the fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your local
Bryant representative for details.
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5,500
755
2.27
1908
831
2.58
2171
901
2.91
2443
968
3.24
2723
1031
3.58
3009
1091
3.93
3302
6,000
810
2.72
2287
881
3.04
2556
947
3.37
2833
1010
3.71
3116
1070
4.05
3406
1127
4.40
3702
6,500
866
3.22
2710
932
3.55
2985
994
3.88
3266
1054
4.23
3554
1111
4.57
3847
1166
4.93
4146
7,000
923
3.78
3177
985
4.11
3458
1044
4.45
3744
1100
4.80
4036
1155
5.15
4333
1207
5.51
4635
7,500
980
4.39
3690
1038
4.73
3976
1094
5.07
4267
1148
5.43
4564
1200
5.78
4864
1250
6.15
5170
8,000
1038
5.06
4251
1093
5.40
4542
1146
5.75
4838
1197
6.11
5138
1246
6.47
5443
1294
6.84
5752
8,500
1096
5.78
4859
1148
6.13
5156
1198
6.49
5456
1247
6.85
5761
1294
7.22
6070
1340
7.59
6382
9,000
1154
6.56
5517
1204
6.92
5818
1251
7.28
6123
1298
7.65
6432
1343
8.02
6745
1388
8.40
7062
9,500
1213
7.40
6224
1260
7.77
6531
1306
8.13
6840
1350
8.51
7154
1394
8.88
7471
1436
9.26
7791
10,000
1272
8.30
6983
1317
8.67
7294
1360
9.05
7608
1403
9.43
7926
1445
9.81
8247
1486
10.19
8570
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
1.6
1.8
1.9
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5,500
1149
4.28
3602
1204
4.65
3907
1258
5.02
4217
1284
5.20
4375
1309
5.39
4533
6,000
1183
4.76
4003
1236
5.13
4310
1288
5.50
4622
1313
5.68
4780
1337
5.87
4939
6,500
1219
5.29
4450
1270
5.66
1459
1320
6.03
5073
1344
6.22
5232
1368
6.41
5391
7,000
1258
5.88
4942
1307
6.25
5253
1355
6.62
5569
1378
6.81
5729
1402
7.00
5890
7,500
1299
6.52
5480
1346
6.89
5794
1392
7.27
6113
1415
7.46
6273
1437
7.65
6435
8,000
1341
7.21
6065
1387
7.59
6383
1392
7.97
6704
1453
8.16
6866
1475
8.36
7028
8,500
1385
7.97
6699
1429
8.35
7019
1472
8.73
7343
1493
8.93
7506
1514
9.12
7670
9,000
1431
8.78
7382
1473
9.15
7705
1515
9.55
8032
1535
9.75
8196
—
—
—
9,500
1478
9.65
8114
1519
10.04
8441
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
941
3.35
2769
1002
3.80
3140
1061
4.27
3528
1117
4.76
3934
1171
5.27
4356
1224
5.80
4794
7,500
999
4.05
3348
1057
4.53
3742
1112
5.02
4152
1166
5.54
4579
1218
6.07
5020
1268
6.63
5478
8,000
1058
4.85
4007
1113
5.35
4424
1165
5.87
4856
1216
6.41
5304
1266
6.97
5766
1314
7.55
6243
8,500
1117
5.74
4750
1169
6.28
5190
1219
6.83
5645
1268
7.40
6114
1315
7.98
6597
1361
8.58
7094
9,000
1177
6.75
5583
1226
7.31
6047
1274
7.89
6524
1320
8.48
7015
1365
9.09
7520
1410
9.72
8037
9,500
1237
7.98
6511
1284
8.46
6999
1329
9.07
7499
1374
9.69
8012
1417
10.33
8538
1459
10.98
9076
10,000
1297
9.12
7450
1342
9.74
8051
1385
10.37
8574
1428
11.02
9110
1469
11.68
9657
1510
12.36
10217
10,500
1358
10.49
8674
1400
11.14
9209
1442
11.80
9755
1483
12.47
10314
1523
13.16
10883
—
—
—
11,000
1418
12.00
9919
1459
12.67
10478
—
—
—
—
—
—
—
—
—
—
—
—
11,250
1449
12.80
10585
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
1.6
1.8
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
1274
6.35
5248
1323
6.92
5718
1371
5.54
6204
7,500
1316
7.20
6960
1364
7.79
6437
1410
6.41
6939
8,000
1360
8.14
6734
1406
8.76
7239
1450
7.40
7759
8,500
1406
9.20
7605
1449
9.83
8129
1492
8.48
8666
9,000
1453
10.36
8568
1495
11.02
9111
1536
9.69
9667
9,500
1501
11.64
9627
1541
12.32
10190
—
—
—
10,000
—
—
—
—
—
—
—
—
—
10,500
—
—
—
—
—
—
—
—
—
11,000
—
—
—
—
—
—
—
—
—
11,250
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor