14
1. Using Fig. 11, move the two pin DEHUM jumper from the
“STD” position to the “DEHUM” position.
2. Remove fan speed tap wire from the “LOW” terminal on
the interface fan board (IFB) (See Fig. 11).
3. Determine correct normal cooling fan speed for unit and
application. Add the wet coil pressure drop in Table 7 to
the system static to determine the correct cooling airflow
speed in Table 5 that will deliver the nominal cooling
airflow as listed in Table 1 for each size.
NOTE
: If accessory electric heat is installed, the dry
airflow must meet or exceed the minimum airflow speed
specified in Table 2 for the specific size unit. The electric
heat fan speed will be the same as the normal cooling fan
speed.
4. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 3 for color coding) for the normal cooling
fan speed and place desired speed tap wire on “HIGH” on
the interface board.
5. Refer to airflow tables (Table 5) to determine allowable
speeds for the dehumidification cooling fan speed. In Table
5, speeds that are not allowed for dehumidification cooling
are shaded.
6. Remove the vinyl cap off of the desired speed tap wire
(Refer to Table 3 for color coding) for the dehumidification
cooling fan speed and place desired speed tap wire on the
“LOW” connection on the interface board (IFB). Verify
that static pressure is in the acceptable range for the speed
tap to be used for dehumidification cooling.
7. Use any spare vinyl plugs to cap any unused speed tap
wires.
HIGH
LOW
COM
QC5
QC4
QC3
KZ
KL
07
09
08
0L0
ALO
R13 C8
R11
Q1
Q3
D2
AL2
DCR
QCR
QC1
C
RL
01
G1
G2
Z1
A7
R9
AB A15
C4
C9
C0
QIL
Z2
06
04
U1
C3
R4
RL4
JWZ
C7
D5
D3
R3 R5
R6
R2
JW5
QCB
Y
R
W2 Y
C
W3 W3 W2 W2 C
JW4
P2
JW3
P4
P1
W2
W3
Y2
Y1
Y
DH
G
C
R
SSTZ-8
P3
SDL
24V
AC/R
3AMP
CDM/C
F1
STD
DEHUM
A09059
Fig. 11 -- Interface Fan Board (IFB)
SINGLE SPEED COOLING WITH HIGHER
ELECTRIC HEAT SPEED
This unit can also be configured to operate with single speed
cooling and a higher speed for an accessory electric heater.
1. Using Fig. 11, move the two pin DEHUM jumper from the
“STD” position to the “DEHUM” position.
2. See Table 2 for minimum airflow for electric heat operation.
Add electric heater and filter pressure drop to duct system
static pressure to determine total external static pressure.
3. Select speed tap from Table 5 that will achieve required air-
flow from Table 2.
4. Remove the vinyl cap off of the desired speed tap wire (Re-
fer to Table 3 for color coding).
5. Connect the desired speed tap wire to the “HIGH” terminal
on the interface fan board (IFB).
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit component
damage or improper operation.
To use this mode, a speed connection must be made on the
“HIGH” terminal that meets or exceeds the minimum
airflow found in Table 2.
!
CAUTION
Table 3 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med--High Speed
Red = Med Speed
Pink = Med--Low Speed
Blue = Low Speed
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect electrical power to the unit and install lockout
tag before changing blower speed.
!
WARNING
CONTINUOUS FAN OPERATION
When the DEHUM feature is not used, the continuous fan speed
will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed
when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized (see Fig. 11).
COOLING SEQUENCE OF OPERATION
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of
operation is as follows:
When the room temperature rises to a point that is slightly above
the cooling control setting of the thermostat, the thermostat
completes the circuit between thermostat terminal R to terminals Y
and G. These completed circuits through the thermostat connect
contactor coil (C) (through unit wire Y) and time delay relay
(TDR) (through unit wire G) across the 24--V secondary of
transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to
condenser (outdoor) fan motor (OFM). Both motors start instantly.
A set of normally open contacts on the interface fan board (IFB)
are closed which energizes a circuit to the indoor fan motor (IFB).
NOTE
: Once the compressor has started and then has stopped, it
should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to a
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between
thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C and IFB. The condenser and
compressor motors stop. After a 90--second delay, the blower
motor stops. The unit is in a standby condition, waiting for the next
call for cooling from the room thermostat.
707C
--
--
(C
,D
)
Summary of Contents for 707C C Series
Page 3: ...3 A180287 Fig 2 24 36 Unit Dimensions 707C C D...
Page 4: ...4 Fig 3 42 60 Unit Dimensions 707C C D...
Page 22: ...22 A150503 Fig 12 Connection Wiring Diagram 208 230 1 60 707C C D...
Page 23: ...23 A150513 Fig 12 Cont Ladder Wiring Diagram 208 230 1 60 707C C D...
Page 24: ...24 A150504 Fig 13 Connection Wiring Diagram 208 230 3 60 707C C D...
Page 25: ...25 A150514 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 707C C D...
Page 26: ...26 A150505 Fig 14 Connection Wiring Diagram 460 3 60 707C C D...
Page 27: ...27 A150515 Fig 14 Cont Ladder Wiring Diagram 460 3 60 707C C D...