background image

16

Ta

bl

e

4

--

D

ry

C

oi

lA

ir

D

el

iv

er

y*

--

H

or

iz

ont

al

and

D

ow

nf

low

D

is

char

ge

--

Si

ze

s

24

--60

208/

230V

A

C

1

P

has

e

M

ode

ls

(C

ont

.)

Un

it

Si

ze

Mo

to

r

S

peed

Wi

re

Co

lo

r

Ext

erna

lS

ta

tic

P

ressure

(I

N

.W

.C

.)

0.

1

0.

2

0.

3

0.

4

0.

5

0.

6

0.

7

0.

8

0.

9

1

48

Lo

w

Blu

e

CF

M

1378

1344

1295

1260

1216

1179

1135

1087

1035

995

BH

P

0.26

0.27

0.29

0.31

0.31

0.33

0.34

0.36

0.36

0.38

M

ed

---

Lo

w

1

Pin

k

CF

M

1696

1671

1631

1607

1574

1539

1507

1463

1432

1393

BH

P

0.45

0.47

0.49

0.50

0.52

0.52

0.54

0.55

0.57

0.58

Me

di

um

Re

d

CF

M

1994

1968

1943

1910

1882

1835

1774

1702

1614

1512

BH

P

0.72

0.73

0.75

0.76

0.78

0.78

0.76

0.73

0.70

0.66

M

ed

---

H

ig

h

Or

an

ge

CF

M

2054

2013

1986

1964

1919

1854

1779

1695

1605

1498

BH

P

0.77

0.79

0.80

0.82

0.81

0.80

0.76

0.74

0.69

0.65

Hi

gh

Bla

ck

CF

M

2267

2201

2133

2071

1997

1923

1835

1739

1654

1551

BH

P

1.03

1.00

0.97

0.93

0.89

0.86

0.82

0.78

0.74

0.69

60

Lo

w

Blu

e

CF

M

1330

1277

1232

1191

1147

1103

1060

1004

963

919

BH

P

0.26

0.27

0.29

0.30

0.31

0.32

0.33

0.34

0.36

0.37

M

ed

---

Lo

w

Pin

k

CF

M

1475

1436

1399

1351

1317

1270

1236

1188

1152

1105

BH

P

0.35

0.36

0.37

0.38

0.40

0.41

0.42

0.43

0.45

0.45

Me

di

um

1

Re

d

CF

M

1736

1710

1668

1630

1600

1557

1522

1479

1450

1406

BH

P

0.53

0.54

0.55

0.58

0.59

0.60

0.62

0.63

0.64

0.65

M

ed

---

H

ig

h

Or

an

ge

CF

M

1935

1909

1867

1836

1808

1766

1696

1619

1535

1454

BH

P

0.71

0.73

0.74

0.76

0.78

0.79

0.77

0.75

0.72

0.68

Hi

gh

Bla

ck

CF

M

2205

2150

2078

2011

1941

1852

1779

1672

1572

1473

BH

P

1.04

1.02

0.99

0.95

0.92

0.87

0.85

0.79

0.75

0.70

*A

ir

de

liv

er

y

va

lu

es

ar

e

w

ith

ou

ta

ir

fil

te

ra

nd

ar

e

fo

rd

ry

co

il

(S

ee

W

et

C

oil

Pr

essu

re

D

ro

p

ta

bl

e)

.

1

Fa

ct

or

y-

sh

ip

pe

d

cool

in

g

sp

eed

NO

TE

:D

ed

uc

tf

ie

ld

-s

uppl

ie

d

ai

rf

ilt

er

pr

es

su

re

dr

op

an

d

w

et

co

il

pr

es

su

re

dr

op

to

ob

ta

in

ex

te

rn

al

st

at

ic

pr

es

su

re

av

ai

la

bl

e

fo

rdu

cti

ng.

S

ha

de

d

ar

ea

s

ind

ic

at

e

sp

ee

d/

st

at

ic

co

m

bi

na

tio

ns

tha

ta

re

no

tp

er

m

itt

ed

fo

rd

ehum

id

ifi

ca

tio

n

sp

ee

d.

707C

--

--

(C

,D

)

Summary of Contents for 707C C Series

Page 1: ...cal Controls and Wiring 30 Refrigerant Circuit 31 Evaporator Airflow 31 Puron Items 31 TROUBLESHOOTING 32 START UP CHECKLIST 32 A170030 Fig 1 Unit 707C C 707C D SAFETY CONSIDERATIONS Improper installa...

Page 2: ...downflow panels before rigging and lifting into place The panel removal process may require the unit to be on the ground Step 2 Provide Unit Support IMPORTANT The unit must be secured to the curb by i...

Page 3: ...3 A180287 Fig 2 24 36 Unit Dimensions 707C C D...

Page 4: ...4 Fig 3 42 60 Unit Dimensions 707C C D...

Page 5: ...6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether...

Page 6: ...PLACING UNIT ON ROOF CURB DUCTS DETAIL A VOIR D TAIL A MINIMUM HEIGHT 36 914 4 mm HAUTEUR MINIMUM UNIT HEIGHT HAUTEUR D UNIT SEE DETAIL A VOIR D TAIL A BANDE SCELLANT DOIT TRE EN PLACE AVANT DE PLACER...

Page 7: ...nd any other safety precautions that might apply Training for operators of the lifting equipment should include but not be limited to the following 1 Application of the lifter to the load and adjustme...

Page 8: ...insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Con...

Page 9: ...ied electrical disconnect switch and unit DO NOT USE ALUMINUM WIRE 3 Be sure that high voltage power to unit is within operating voltage range indicated on unit rating plate On 3 phase units ensure ph...

Page 10: ...00 ft 30 5 m from the unit as measured along the control voltage wires use no 16 AWG color coded insulated 35 C minimum wires STANDARD CONNECTION Locate the seven eight for 3 phase low voltage thermos...

Page 11: ...Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279 4x254 1 2 1075 1550 11x10 279 4x254 1 0 1075 1750 11x10 279 4x254 1 0 1040 HIGH PRESSU...

Page 12: ...essurized mixtures of air or gases containing oxygen can lead to an explosion WARNING Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that...

Page 13: ...e is more than 2 F 1 1 C lower than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFL...

Page 14: ...l cap off of the desired speed tap wire Re fer to Table 3 for color coding 5 Connect the desired speed tap wire to the HIGH terminal on the interface fan board IFB UNIT OPERATION HAZARD Failure to fol...

Page 15: ...ck CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 36 Low Blue CFM 1056 982 911 882 812 740 667 564 486 361 BHP 0 24 0 24 0 24 0 26 0 26 0 27 0 28...

Page 16: ...0 82 0 78 0 74 0 69 60 Low Blue CFM 1330 1277 1232 1191 1147 1103 1060 1004 963 919 BHP 0 26 0 27 0 29 0 30 0 31 0 32 0 33 0 34 0 36 0 37 Med Low Pink CFM 1475 1436 1399 1351 1317 1270 1236 1188 1152...

Page 17: ...02 1351 1311 1263 1224 1172 1136 1080 1041 Med Low Pink CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104 Medium 1 Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381 Med High Orange CFM 2149 2111 206...

Page 18: ...66 0 64 0 63 0 61 0 59 High Black CFM 1560 1491 1416 1337 1255 1233 1160 1082 998 911 WATTS 708 699 683 674 660 634 624 606 581 566 BHP 0 76 0 75 0 73 0 72 0 71 0 68 0 67 0 65 0 62 0 61 42 Low Blue CF...

Page 19: ...2 0 88 0 84 60 Low Blue CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061 WATTS 224 239 247 262 270 284 300 307 319 330 BHP 0 24 0 26 0 26 0 28 0 29 0 30 0 32 0 33 0 34 0 35 Med Low Pink CFM 1841...

Page 20: ...600 1400CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 3 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200...

Page 21: ...2 0 14 0 16 0 18 20 kW 0 00 0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 Large Cabinet 42 60 STATIC STANDARD CFM SCFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 25...

Page 22: ...22 A150503 Fig 12 Connection Wiring Diagram 208 230 1 60 707C C D...

Page 23: ...23 A150513 Fig 12 Cont Ladder Wiring Diagram 208 230 1 60 707C C D...

Page 24: ...24 A150504 Fig 13 Connection Wiring Diagram 208 230 3 60 707C C D...

Page 25: ...25 A150514 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 707C C D...

Page 26: ...26 A150505 Fig 14 Connection Wiring Diagram 460 3 60 707C C D...

Page 27: ...27 A150515 Fig 14 Cont Ladder Wiring Diagram 460 3 60 707C C D...

Page 28: ...unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcooling charging Favorable conditio...

Page 29: ...the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean c...

Page 30: ...and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain trough with clear water Do not splash w...

Page 31: ...of charge low airflow across indoor coil dirty filters etc It opens at 50 psig 957 Pa If system pressure is above this switch should be closed To check switch 1 Turn off all power to unit 2 Disconnect...

Page 32: ...cause long term damage to some synthetic roofing materials Exposure even if immediately cleaned up may cause embrittlement leading to cracking to occur in one year or more When performing any service...

Page 33: ...ompressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Deter...

Page 34: ...sig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE synthetic oils S Vacuum pumps will not remove moisture...

Page 35: ...INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL S...

Page 36: ...ue or change at any time specifications or designs without notice and without incurring obligations E2019 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 19 R...

Reviews: