Fig. 10—Typical 24-v Circuit Connections using Other HP Thermostats with Fan Coils and No Outdoor Thermostat, 1 Outdoor

Thermostat, or 2 Outdoor Thermostats

A97404

24 VAC HOT

R

C

W2

Y

G

R

W3

W2

G

RVS COOLING

E

W2

OTHER

HP THERMOSTAT

TWO

OUTDOOR

THERMOSTATS

 FA, FB, FC, 

FD, FF, FH

FAN COIL

HEAT 

PUMP

C

O

R

C

O

INDOOR FAN

HEAT STAGE 2

COOL/HEAT
STAGE 1

24 VAC COM

EMERGENCY 
HEAT

Y

E

  

ODT

  

ODT

NOTE:   Remove wires from crimp nut in indoor fan coil 

when installing outdoor thermostats.

IMPORTANT:  When using outdoor thermostats, W2 must be

          energized when requesting supplemental heat.  

  

EHR

  

EHR

  

EHR

*

*

*

 IF AVAILABLE

*

A97374

24 VAC HOT

R

C

W2

Y

G

R

C

RVS COOLING

C

W2

OTHER

HP THERMOSTAT

 FA, FB, FC, 

FD, FF, FH

FAN COIL

HEAT 

PUMP

G

O

E

W2

E

W3

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT
STAGE 1

INDOOR FAN

EMERGENCY
HEAT

O

*

*

*

 IF AVAILABLE

*

A97373

24 VAC HOT

R

C

W2

Y

G

R

DH

C

RVS COOLING

C

W2

OTHER

HP THERMOSTAT

FK4C

FAN COIL

 HEAT 
PUMP

G

Y/Y2

O

Y1

O

E

W1

W2

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT
STAGE 1

INDOOR FAN

EMERGENCY
HEAT

O

J1 JUMPER

J2 JUMPER

A97403

24 VAC HOT

R

C

W2

Y

G

R

W3

W2

E

G

RVS COOLING

E

W2

OTHER

HP THERMOSTAT

ONE

OUTDOOR

THERMOSTAT

FA, FB, FC,

FD, FF, FH

FAN COIL

 HEAT 
PUMP

C

O

R

C

O

INDOOR FAN

HEAT STAGE 2

COOL/HEAT
STAGE 1

24 VAC COM

EMERGENCY
HEAT

Y

  

ODT

NOTE:   Remove wires from crimp nut in indoor fan coil 

when installing outdoor thermostat.

IMPORTANT:  When using outdoor thermostat, W2 must be

          energized when requesting supplemental heat.  

—7—

Summary of Contents for 663C

Page 1: ...r installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity...

Page 2: ...ing mode is 66 F V ELEVATE UNIT CAUTION Accumulation of water and ice in base pan may cause equipment damage In areas where prolonged freezing temperatures are encountered elevate unit per local clima...

Page 3: ...1 for field tubing equivalent line length Refer to Table 2 for accessory requirements For buried line applications greater than 36 in refer to Table 2 and Residential Split System Buried Line Applicat...

Page 4: ...AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3 8...

Page 5: ...afety glasses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise val...

Page 6: ...P FA FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A97372 24 VAC...

Page 7: ...R C W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A97373 24...

Page 8: ...xiliary heat for even heating comfort via W W1 and Y1 W2 Refer to FK4 Installation Instructions Fig 11 Typical 24 v Circuit Connections using Bryant Model DF Thermostat with Single or 2 Stage Furnace...

Page 9: ...ONNECTION CUT JW1 SHR SHR ODT A97407 24 VAC HOT R G W W1 Y Y2 O W2 RVS COOLING C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL HP FA FB FC FH FAN COIL WITH SMART HEAT HEAT PUMP Y1 W2 L R C Y G O W2T W3...

Page 10: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2D...

Page 11: ...rewdriver immediately otherwise control will terminate normal 10 minute defrost cycle in approximately 2 sec NOTE Length of defrost cycle is dependent on the length of time it takes to remove screwdri...

Page 12: ...rging is necessary during heating season charge must be weighed in accordance with unit rating plate 0 6 oz ft of 3 8 in liquid line above or below 15 ft respectively EXAMPLE To calculate additional c...

Reviews: