background image

VII.

CHECK OUTDOOR CHECK-FLO-RATER® PISTON

Check outdoor unit piston. Remove retainer on liquid service valve
and check piston size with matching number listed on outdoor unit
rating plate.

VIII.

CHECK DEFROST THERMOSTAT

Check defrost thermostat to ensure it is properly located and
securely attached. There is a liquid header with a brass distributor
and feeder tube going into outdoor coil. At the end of 1 of the
feeder tubes, there is a 3/8-in. O.D. stub tube approximately 2 in.
long. (See Fig. 6.) The defrost thermostat should be located on stub
tube. Note that there is only 1 stub tube used with liquid header,
and on most units it is the bottom circuit.

IX.

MAKE PIPING CONNECTIONS

WARNING:

Relieve pressure and recover all refrigerant

before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

CAUTION:

If ANY refrigerant tubing is buried, provide

a 6 in. vertical rise at service valve. Refrigerant tubing
lengths up to 36 in. may be buried without further special
consideration. For lengths above 36 in., refer to Residen-
tial Split System Buried-Line Application Guideline.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the
recommendations in the Residential Split System Long-Line
Application Guideline will reduce these losses. Refer to Table 1
for field tubing equivalent line length. Refer to Table 2 for
accessory requirements.

For buried-line applications greater than 36 in., refer to Table 2
and Residential Split System Buried-Line Application Guideline.
Buried-line applications may not exceed 100 ft.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

A.

Outdoor Unit Connected to Factory-Approved

Indoor Unit

Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft of
field-supplied or factory-accessory tubing. Check refrigerant
charge for maximum efficiency.

B.

Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.

C.

Sweat Connection

CAUTION:

To avoid valve damage while brazing, ser-

vice valves must be wrapped in a heat-sinking material
such as a wet cloth.

Remove plastic retainer holding outdoor piston in liquid service
valve and connect sweat/flare adapter provided to valve. (See Fig.
7.) Connect refrigerant tubing to fittings on outdoor unit vapor and
liquid service valves. Service valves are closed from factory and
ready for brazing. After wrapping service valve with a wet cloth,
tubing set can be brazed to service valve using either silver bearing
or non-silver bearing brazing material. Consult local code require-
ments. Refrigerant tubing and indoor coil are now ready for leak
testing. This check should include all field and factory joints.

Fig. 4—Typical TXV Installation

A88382

THERMOSTATIC
EXPANSION
VALVE

EQUALIZER
TUBE

SENSING
BULB

COIL

Fig. 5—Positioning of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

Fig. 6—Defrost Thermostat Location

A97517

FEEDER TUBE

DEFROST
THERMOSTAT

STUB TUBE

—3—

Summary of Contents for 663C

Page 1: ...r installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity...

Page 2: ...ing mode is 66 F V ELEVATE UNIT CAUTION Accumulation of water and ice in base pan may cause equipment damage In areas where prolonged freezing temperatures are encountered elevate unit per local clima...

Page 3: ...1 for field tubing equivalent line length Refer to Table 2 for accessory requirements For buried line applications greater than 36 in refer to Table 2 and Residential Split System Buried Line Applicat...

Page 4: ...AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3 8...

Page 5: ...afety glasses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise val...

Page 6: ...P FA FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A97372 24 VAC...

Page 7: ...R C W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A97373 24...

Page 8: ...xiliary heat for even heating comfort via W W1 and Y1 W2 Refer to FK4 Installation Instructions Fig 11 Typical 24 v Circuit Connections using Bryant Model DF Thermostat with Single or 2 Stage Furnace...

Page 9: ...ONNECTION CUT JW1 SHR SHR ODT A97407 24 VAC HOT R G W W1 Y Y2 O W2 RVS COOLING C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL HP FA FB FC FH FAN COIL WITH SMART HEAT HEAT PUMP Y1 W2 L R C Y G O W2T W3...

Page 10: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2D...

Page 11: ...rewdriver immediately otherwise control will terminate normal 10 minute defrost cycle in approximately 2 sec NOTE Length of defrost cycle is dependent on the length of time it takes to remove screwdri...

Page 12: ...rging is necessary during heating season charge must be weighed in accordance with unit rating plate 0 6 oz ft of 3 8 in liquid line above or below 15 ft respectively EXAMPLE To calculate additional c...

Reviews: