18
Disconnect
per
NEC
13
11
13
L1
L2
L3
C
IFC
208/230-3-60
460-3-60
575-3-60
Units Without Disconnect Option
Units With Disconnect Option
L3
L2
L1
L3
L2
L1
T3
T1
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
T2
BLU
BLK
YEL
Ground
(GR)
Equip
GR Lug
Equip GR Lug
Ground
(GR)
C12741
Fig. 24 −
Power Wiring Connections
Field power wires will be connected line−side pressure
lugs on the power terminal block or at factory−installed
option non−fused disconnect.
Field power wires are connected to the unit at line−side
pressure lugs on compressor contactor C and indoor fan
contactor IFC (see wiring diagram label for control box
component arrangement), at factory−installed option
non−fused disconnect switch. Max wire size is #4 AWG
(copper only) per pole on contactors and #2ga AWG
(copper only) per pole on optional non−fused disconnect.
See Fig. 24 and the unit label diagram for field power
wiring connections.
NOTE: TEST LEADS − Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run−test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and air conditioning unit. Use only copper wire.
(See Fig. 25.)
!
WARNING
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 25 −
Disconnect Switch and Unit
Units with Factory−Installed Non−Fused Disconnect —
The factory−installed option non−fused disconnect (NFD)
switch is located in a weatherproof enclosure located
under the main control box (see Fig. 26). The manual
switch handle and shaft are shipped in the disconnect
enclosure. Assemble the shaft and handle to the switch at
this point. Discard the factory test leads (see Fig. 24).
Connect field power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
C12278
Fig. 26 −
Location of Non−Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front panel (see Fig. 2 or Fig. 3).
2. Remove (3) hex screws on the NFD enclosure − (2) on
the face of the cover and (1) on the left side cover. See
Fig. 27.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
6. Measure from the tip of the shaft to the top surface of
the black pointer; the measurement should be 3.75 −
3.88 in. (95 − 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
581J
Summary of Contents for 581J series
Page 4: ...4 C160140 Fig 2 Unit Dimensional Drawing Sizes 07 09 581J ...
Page 5: ...5 C160141 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont 581J ...
Page 6: ...6 C13300A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 581J ...
Page 7: ...7 C13301A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont 581J ...
Page 25: ...25 C160113 Fig 36 Typical RTU Open Controller Wiring Diagram 581J ...