34
Table 7 – LEDs
The LEDs on the RTU Open Controller show the status of certain functions
If this LED is on...
Status is...
Power
The RTU Open controller has power
Rx
The RTU Open controller is receiving data from the network segment
Tx
The RTU Open controller is transmitting data over the network segment
BO#
The binary output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes, alternating with
Run
LED
Five minute auto-restart delay after system error
2 flashes per second
3 flashes, then off
Control module has just been formatted
2 flashes per second
4 flashes, then pause
Two or more devices on this network have the
same MSTP network address
2 flashes per second
On
Exec halted after frequent system errors or
control programs halted
5 flashes per second
On
Exec start-up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating
with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
S
Turn the RTU Open controller off, then on.
S
Format the RTU Open controller.
S
Download memory to the RTU Open controller.
S
Replace the RTU Open controller.
Outdoor Air Enthalpy Control
(P/N 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field−installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field−installed accessory
return air enthalpy sensor (33CSENTSEN) is required for
differential enthalpy control. See Fig. 54.)
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory
harness and connect the gray lead labeled “ESL” to the
terminal labeled “LOW”. See Fig. 54. Connect the enthalpy
control power input terminals to economizer actuator power
leads RED (connect to 24V) and BLK (connect to GND).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
7
CTB ECON
(RTU Open: to J2-6)
LOW
GND
24V
Enthalpy
Switch
GRA
BLK
RED
Factory Wiring Harness
PL6-1 (24-V)
PL6-4 (COM)
C11169
Fig. 54 −
Enthalpy Switch (33CSENTHSW) Connections
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and
comparing the outside air and return air enthalpy
conditions. Install the outdoor air enthalpy control as
described above. Add and install a return air enthalpy
sensor.
Return Air Enthalpy Sensor —
Mount the return−air enthalpy sensor (33CSENTSEN) in
the return−air section of the economizer. The return air
sensor is wired to the enthalpy controller
(33CSENTHSW). See Fig. 55.
GRA
BLK
RED
–
4-20
Main
+
VDC
Out
–
4-20 Main
Out
+
24-36
VDC In
LOW
GND
24V
7
CTB ECON
(RTU Open: to J2-6)
PL6-1 (24-V)
PL6-4 (COM)
Outside Air
Enthalpy Switch
Return Air
Enthalpy
Sensor
C11170
Fig. 55 −
Outside and Return Air Enthalpy Sensor
Wiring
581J
Summary of Contents for 581J series
Page 4: ...4 C160140 Fig 2 Unit Dimensional Drawing Sizes 07 09 581J ...
Page 5: ...5 C160141 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont 581J ...
Page 6: ...6 C13300A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 581J ...
Page 7: ...7 C13301A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont 581J ...
Page 25: ...25 C160113 Fig 36 Typical RTU Open Controller Wiring Diagram 581J ...