LOCATION
DIMENSION
CONDITION
A
48-in (1219 mm)
18-in (457 mm)
18-in (457) mm
12-in (305 mm)
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
B
42-in (1067 mm)
36-in (914 mm)
Special
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Check sources of flue products within 10-ft of unit fresh air intake hood
C
36-in (914 mm)
18-in (457 mm)
Side condensate drain is used
Minimum clearance
D
48-in (1219 mm)
42-in (1067 mm)
36-in (914 mm)
Special
No flue discharge accessory installed, surface is combustible material
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Check for adjacent units or building fresh air intakes within 10-ft (3 m) of this unit's flue outlet
NOTE:
Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
planning overhead obstruction or for vertical clearances.
Fig. 4 −
Service Clearance Dimensional Drawing — Sizes 07−12
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installa-
tion requirements.
2. Determine unit location (from project plans) or select
unit location.
3. Check for possible overhead obstructions which may
interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb
or other) that provides for the minimum clearances
required for safety. This includes the clearance to
combustible surfaces, unit performance and service access
below, around and above unit as specified in unit
drawings. See Fig. 4.
NOTE: Consider also the effect of adjacent units.
Be sure that the unit is installed such that snow will not
block the combustion intake or flute outlet.
Unit may be installed directly on wood flooring or on
Class A, B, or C roof−covering material when roof curb is
used.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air. For proper unit operation, adequate combustion and
ventilation air must be provided in accordance with
Section 5.3 (Air for Combustion and Ventilation) of the
National Fuel Gas Code, ANSI Z223.1 (American
National Standards Institute) and NFPA (National Fire
Protection Association) 54 TIA−−54−−84−−1. In Canada,
installation must be in accordance with the CAN1−−B149
installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto
the unit.
Locate mechanical draft system flue assembly at least 4 ft
(1.2 m) from any opening through which combustion
581J
Summary of Contents for 581J series
Page 4: ...4 C160140 Fig 2 Unit Dimensional Drawing Sizes 07 09 581J ...
Page 5: ...5 C160141 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont 581J ...
Page 6: ...6 C13300A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 581J ...
Page 7: ...7 C13301A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont 581J ...
Page 25: ...25 C160113 Fig 36 Typical RTU Open Controller Wiring Diagram 581J ...