66
APPENDIX III. FAN PERFORMANCE
Table 24 – 581J*D17
VERTICAL SUPPLY / RETURN
15 TON
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
4500
494
0.77
583
1.09
662
1.43
732
1.80
796
2.19
4900
522
0.93
605
1.27
681
1.64
750
2.03
813
2.44
5250
547
1.10
626
1.45
700
1.84
766
2.24
828
2.67
5650
577
1.32
651
1.68
721
2.09
786
2.51
846
2.96
6000
603
1.53
674
1.91
741
2.33
804
2.78
863
3.24
6400
634
1.81
701
2.20
765
2.64
826
3.10
883
3.59
6750
662
2.07
725
2.49
787
2.94
846
3.42
902
3.92
7150
694
2.42
754
2.85
813
3.31
869
3.81
923
4.33
7500
722
2.74
779
3.19
836
3.67
890
4.19
943
4.72
CFM
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
4500
856
2.60
911
3.02
963
3.46
1012
3.92
1059
4.39
4900
871
2.86
926
3.30
977
3.76
1026
4.23
1072
4.72
5250
885
3.11
939
3.57
990
4.05
1038
4.54
-
-
5650
903
3.43
956
3.91
1006
4.40
-
-
-
-
6000
918
3.72
971
4.22
1020
4.73
-
-
-
-
6400
937
4.09
988
4.61
-
-
-
-
-
-
6750
954
4.44
-
-
-
-
-
-
-
-
7150
975
4.87
-
-
-
-
-
-
-
-
7500
-
-
-
-
-
-
-
-
-
-
Boldface
indicates alternate standard static drive package required.
Medium Static Motor and Drive - 697-863 RPM, Max BHP 3.7
Std Static Motor and Drive - 514-680 RPM, Max BHP 2.9
High Static Motor and Drive - 826-1009 RPM, Max BHP 4.9
-
Outside operating range
Italics
-
requires high static drive package with different motor pulley.
Table 25 – 581J*D20
VERTICAL SUPPLY / RETURN
17.5 TON
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5250
547
1.10
626
1.45
700
1.84
766
2.24
828
2.67
5700
581
1.35
655
1.72
724
2.12
789
2.55
849
3.00
6150
615
1.63
684
2.02
750
2.44
812
2.90
871
3.37
6550
646
1.92
711
2.32
774
2.77
834
3.24
891
3.73
7000
682
2.28
743
2.71
803
3.17
860
3.66
915
4.17
7450
718
2.70
775
3.14
832
3.62
887
4.13
940
4.67
7900
755
3.16
809
3.62
863
4.12
915
4.65
966
5.21
8300
787
3.62
839
4.09
891
4.61
941
5.16
990
5.73
8750
825
4.18
874
4.68
923
5.22
971
5.78
1018
6.38
CFM
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5250
885
3.11
939
3.57
980
4.05
1038
4.54
1084
5.04
5700
905
3.47
958
3.95
1008
4.45
1055
4.96
1100
5.48
6150
925
3.86
977
4.36
1026
4.88
1073
5.42
1118
5.96
6550
945
4.24
995
4.76
1043
5.30
1090
5.86
1134
6.42
7000
967
4.71
1017
5.26
1064
5.82
1109
6.39
-
-
7450
991
5.22
1039
5.79
1085
6.38
-
-
-
-
7900
1015
5.78
1062
6.38
-
-
-
-
-
-
8300
1038
6.33
-
-
-
-
-
-
-
-
8750
-
-
-
-
-
-
-
-
-
-
Boldface
indicates alternate standard static drive package required.
Medium Static Motor and Drive - 713-879 RPM, Max BHP 4.9
Std Static Motor and Drive - 622-822 RPM, Max BHP 3.7
High Static Motor and Drive - 882-1078 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575V
-
Outside operating range
Requires high static drive package with different motor pulley. Confirm Max BHP coverage based on unit voltage selected.
Summary of Contents for 581J-17-28
Page 73: ...73 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 72 581J D17 D28 Power Diagram 208 230 3 60 ...
Page 74: ...74 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 73 581J D17 D28 Power Diagram 460 3 60 ...
Page 75: ...75 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 74 581J D17 D28 Power Diagram 575 3 60 ...
Page 80: ...80 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 79 RTU OPEN Wiring Diagram ...