24
1.
Using a Puron
(R410) gauge set, recover all refrig
erant from the system.
2.
Use a tubing cutter to remove the filter drier from the
line.
NOTE
:
Do Not use a torch to remove the old filter drier.
The heat from the torch will allow contaminants into the
air and into the open refrigeration system.
3.
Sweat a new replacement filter drier into the refriger
ant line.
4.
Re-charge the refrigerant system.
Adjusting the Condenser
−
Fan
1. Shut off the unit power supply. Apply the appropriate
lockout/tagout procedures.
2. Remove the condenser
−
fan assembly (grille, motor,
and fan).
3. Loosen the fan hub setscrews.
4. Adjust the fan height as shown in Fig. 30.
5. Tighten the setscrews.
6. Replace the condenser
−
fan assembly.
C10323
Fig. 30
−
Condenser Fan Adjustment