Burners and Igniters
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION may result in
equipment damage.
When working on gas train, do not hit or plug
orifice spuds.
CAUTION
!
Main Burners
To access the burner section, open the heater access door
below the indoor fan panel. At the beginning of each
heating season, inspect for deterioration or blockage due
to corrosion or other causes. Observe the main burner
flames and adjust, if necessary. Flames should be conical
in shape and enter the heat exchanger tubes with minor
impingement on the sheet metal flame components.
Orifice Projection
Refer to Fig. 50 for maximum projection dimension for
the orifice face to manifold tube.
ORIFICE
1.00-in
(25.4 mm)
MANIFOLD
PIPE
C08211
Fig. 50
−
Orifice Projection
Removal and Replacement of Gas Train
See Fig. 44, Fig. 49 and Fig. 51.
1. Shut off the gas using the manual shutoff switch lo-
cated in the gas supply line.
2. Turn the gas valve ON/OFF knob to the OFF position.
Summary of Contents for 581J-17-28
Page 73: ...73 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 72 581J D17 D28 Power Diagram 208 230 3 60 ...
Page 74: ...74 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 73 581J D17 D28 Power Diagram 460 3 60 ...
Page 75: ...75 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 74 581J D17 D28 Power Diagram 575 3 60 ...
Page 80: ...80 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 79 RTU OPEN Wiring Diagram ...