background image

C. Field Control Wiring

Install an approved accessory thermostat assembly accord-
ing to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the condi-
tioned space to sense average temperature in accordance with
thermostat installation instructions.

Route thermostat cable or equivalent single leads of colored
wire from subbase terminals to low-voltage connections
on unit (shown in Fig. 9) as described in following Steps 1
through 3:

1. Pass the control wires through the hole provided in the

corner post. (See Fig. 10.)

2. Feed wire through the raceway built into the corner post

to the 24-v barriers located on the left side of the con-
trol box. The raceway provides the required clearance
between the high- and low-voltage wiring.

3. Connect thermostat wires to screw terminals of low-

voltage connection board.

NOTE:

39 VA is available for field-installed accessories. Con-

trol power requirement for heat pump outdoor unit is 36 VA
(sealed). The factory-supplied control transformer is rated at
75 VA.

NOTE:

For wire runs, use the following insulated wire:

LENGTH

INSULATION

RATING (C)

SIZE

Ft

M

AWG

sq mm

0-50

0-15.2

35

18

0.82

50-75

15.2-22.9

35

16

1.30

Over 75

Over 22.9

35

14

2.08

LEGEND

AWG — American Wire Gage

All wire larger than no. 18 AWG (American Wire Gage) can-
not be directly connected to the thermostat and will require
a junction box and splice at the thermostat.

START-UP

I. PRELIMINARY CHECKS

1. Check that all internal wiring connections are tight and

that all barriers, covers, and panels are in place.

2. Field electrical power source must agree with unit name-

plate rating.

3. Ensure all service valves are open. Ensure all compres-

sor service valves are backseated.

4. Verify that compressor holddown bolts have been loos-

ened and that flat/snubber washers can be rotated by
finger pressure (snug, but not tight).

5. Verify compressor crankcase heater is securely in place.

Crankcase heater must operate for at least 24 hours be-
fore start-up.

6. Note that compressor oil level is visible in the sight glass.

7. Check for leaks in refrigerant system by using soap bubbles

and/or electronic leak detector.

8. Check voltage imbalance as shown in Table 4, Note 2.

9. Check that both outdoor and indoor units are properly

mounted in accordance with installation instructions and
applicable codes.

II. EVACUATE AND DEHYDRATE

Evacuate and dehydrate entire refrigerant system using meth-
ods described in GTAC II, Module 4, System Dehydration.

III. REFRIGERANT AND OIL CHARGE

Refer to GTAC II, Module 5, Charging Recovery, Recycling,
and Reclamation.

NOTE:

Use of a Totalclaim

t

refrigeration recovery unit is highly

recommended when recovering refrigerant.

Unit panels must be in place when unit is operating during
charging procedure.

Unit is shipped with holding charge only. Weigh in 15 lb of
R-22 to start unit.

A. Refrigerant Charging

Use Cooling Charging Chart (see Fig. 11). Vary refrigerant
until the conditions of the chart are met. Note that charging
chart is different from the type normally used. Chart is based
on charging the units to the correct subcooling for the vari-
ous operating conditions. Accurate pressure gage and tem-
perature sensing device are required. Connect the pressure
gage to the service port on the liquid line service valve. Mount
the temperature sensing device on the liquid line, close to the
liquid line service valve, and insulate it so that outdoor am-
bient temperature does not affect the reading. Indoor airflow
must be within the normal operating range of the unit.

Operate unit a minimum of 15 minutes. Ensure pressure and
temperature readings have stabilized. Plot liquid pressure and
temperature on chart and add or reduce charge to meet curve.
Adjust charge to conform with charging chart, using liquid
pressure and temperature to read chart.

LEGEND

C

— Cooling

H

— Heating

HR — Heater Relay
IFC — Indoor Fan Contactor

LLSV — Liquid Line Solenoid

Valve

SUPL — Supplemental
TB

— Terminal Block

Fig. 9 — Control Wiring Connections

CORNER
POST

RACEWAY

THERMOSTAT
FIELD CONNECTION

POWER WIRING
CONNECTIONS

Fig. 10 — Field Control Wiring Raceway

—8—

Summary of Contents for 575A

Page 1: ...al installation requirements WARNING Before installing or servicing system al ways turn off main power to system There may be more than one disconnect switch Electrical shock can cause personal injury INSTALLATION The 575A090 unit uses a semi hermetic compressor See Table 1 for physical data The 575A090 outdoor unit is approved for use only with the 524A H090 indoor unit Use only approved indoor u...

Page 2: ...arance is optional c Overhead 60 in 1524 mm to assure proper outdoor fan operation d Between units control box side 42 in 1067 mm per National Electrical Code NEC e Between unit and ungrounded surfaces control box side 36 in 914 mm per NEC f Between unit and block or concrete walls and other grounded surfaces control box side 42 in 1067 mm per NEC 5 With the exception of the clearance for the outd...

Page 3: ...red if top crating is left on unit All panels must be in place when rigging See Fig 3 As further protection for coil faces plywood sheets may be placed against sides of unit behind cables Run cables to a central suspension point so that angle from the horizontal plane is not less than 45 degrees Raise and set unit down carefully If it is necessary to roll unit into position mount unit on rails usi...

Page 4: ...ed NOTE Unit is shipped with R 22 holding charge System pres sure must be relieved before removing caps Recover refrig erant prior to brazing Pass nitrogen or other inert gas through piping while braz ing to prevent formation of copper oxide C Liquid Line Solenoid Valve A field supplied liquid line solenoid valve LLSV is recom mended when piping system length exceeds 75 feet The LLSV must be of th...

Page 5: ...n are general points of connection guides only and are not intended for or to include all details for a spe cific installation 4 Liquid line solenoid valve solenoid drop control is recom mended to prevent refrigerant migration to the compressor A bi flow type solenoid valve is required 5 Filter drier must be of the biflow type suitable for heat pump duty 6 Internal factory supplied TXV and bypass ...

Page 6: ... for field wire connections Use factory supplied splices or UL approved copper aluminum connector When installing units provide a disconnect per NEC All field wiring must comply with NEC and local requirements Install field wiring as follows 1 Install conduit through side panel openings 2 Install power lines to connections as shown in Fig 8 Wrap connections with electrical tape Voltage to compress...

Page 7: ...balance 100 457 1 53 This amount of phase imbalance is satisfactory as it is below the maximum allowable 2 IMPORTANT If the supply voltage phase imbalance is more than 2 contact your local electric utility company immediately Table 5 Accessory Electric Heater Data UNIT 524A H NOMINAL kW V PH HZ HEATER PART NO HEATER AMPS MCA MOCP 090 5 240 3 60 CAELHEAT001A00 12 0 25 6 30 480 3 60 CAELHEAT002A00 6...

Page 8: ...operate for at least 24 hours be fore start up 6 Note that compressor oil level is visible in the sight glass 7 Check for leaks in refrigerant system by using soap bubbles and or electronic leak detector 8 Check voltage imbalance as shown in Table 4 Note 2 9 Check that both outdoor and indoor units are properly mounted in accordance with installation instructions and applicable codes II EVACUATE A...

Page 9: ...lows through from the liquid header side outlets into the transfer header where it flows upward 4 Refrigerant leaves the transfer header through side con nections in 4 locations and enters the middle coil cir cuits 4 coil circuits above check valve A 5 Refrigerant leaves the 4 middle coil circuits and enters the top portion of vapor header The refrigerant moves up to the top 2 remaining coil circu...

Page 10: ... Observe that compressor outdoor fan indoor fan motor and electric heaters if equipped start Observe that heating cycle shuts down when control set ting is satisfied 4 When using an automatic changeover room thermostat place both SYSTEM and FAN switches in AUTO posi tions Observe that unit operates in Cooling mode when temperature control is set to call for cooling below room temperature and unit ...

Page 11: ... place coil corner post between top panel and side panel See Fig 15 4 Remove bracket holding coil sections together at return end of outdoor coil Carefully separate the outer coil sec tion 3 to 4 in from the inner coil section See Fig 16 5 Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and de bris Clean the outer surfaces with a stiff brush in...

Page 12: ... unit 2 Remove refrigerant from system using refrigerant re moval methods described in Refrigerant Service Tech niques manual 3 Disconnect compressor wiring at compressor terminal box Disconnect high pressure switch 4 Remove bolts from discharge service valve and suction flange CAUTION Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to se...

Page 13: ...TROUBLESHOOTING CHART HEATING CYCLE LEGEND N C Normally Closed 13 ...

Page 14: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND TXV Thermostatic Expansion Valve Copyright 1995 Carrier Corporation CATALOG NO BDP 3357 502 ...

Page 15: ...N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN CONFIRMED Y N PIPING IS LIQUID LINE SOLENOID VALVE LOCATED AT THE OUTDOOR UNIT AS RECOMMENDED Y N HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR OUTDOOR COIL INDOOR COIL TXV Thermostatic Expansion Valve SOLENOID VALVES FILTER DRIER ...

Page 16: ...ESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR AIR TEMP LEAVING OUTDOOR AIR TEMP INDOOR ENTERING AIR DB dry bulb TEMP INDOOR ENTERING AIR WB wet bulb TEMP INDOOR LEAVING AIR DB TEMP INDOOR LEAVING AIR WB TEMP COMPRESSOR AMPS L1 L2 L3 NOTES CUT ALONG DOTTED LINE Copyright 1995 Carrier Corporation CATALOG NO BDP 3357 502 CL 2 ...

Reviews: