TYPICAL WIRING SCHEMATICS

569D090, 208/230-3-360 and 460-3-60 Units

NOTES:

1.

If any of the original wire furnished must be
replaced, it must be replaced with type 90° C
wire or its equivalent.

2.

Thermostat: HH07AT170, 172, 174 & P272-
2783
Subbase: HH93AZ176, 178 & P272-1882, 1883
or HH93AZ177 & 179.

3.

Sealed VA for IFC and LLSV is not to exceed
22.

4.

Use copper conductors only.

5.

TRAN is wired for 230 v unit. If unit is to be run
with 200 v power supply, disconnect BLK wire
from 230 v tap and connect to 200 v tap.

6.

If TRAN is wired for 460-3-60 v and unit is to be
run with 400-3-50 v power supply, disconnect
BLK wire from 460 v tap and connect to 400 v
tap.

7.

Three-phase motors are protected under pri-
mary single phasing conditions.

VOLTAGE

RATING

CB

MUST

TRIP

AMPS

Mfg. Part No.

24 V

Potter & Brumfield

3.2

W28X-1024-3.2

AHA

Adjustable Heat Anticipator

C

Contactor, Compressor

CAP

Capacitor

CB

Circuit Breaker

CC

Cooling Compensator

CH

Crankcase Heater

CLO

Compressor Lockout

COMP

Compressor Motor

DGT

Discharge Gas Thermostat

EQUIP

Equipment

GND

Ground

HPS

High-Pressure Switch

IFC

Indoor-Fan Contactor

LLSV

Liquid Line Solenoid Valve

LPS

Low-Pressure Switch

NEC

National Electrical Code

OFM

Outdoor-Fan Motor

QT

Quadruple Terminal

TB

Terminal Block

TC

Thermostat-Cooling

TH

Thermostat-Heating

TRAN

Transformer

Field Splice

Marked Wire

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice
Factory Wiring

— —

Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring

To Indicate Common Potential
Only, Not Represent Wiring

LEGEND

Summary of Contents for 566D

Page 1: ...lation for enhance ment of quiet operation The high pressure switch protects the entire refrigeration system from abnormally high operating pressures A low pressure switch protects the system from low pressure conditions including loss of charge The 569F120 and 566E150 240 units feature 2 scroll compres sors and 2 refrigerant circuits that provide continuous air conditioning and design flexibility...

Page 2: ...ons Galvanized steel fan housings are securely mounted to a die formed galvanized steel fan deck Rugged pillow block bearings 524A150 300 are securely fas tened to the solid steel fan shaft with split collets and clamp locking devices Smaller unit sizes have spider type bearings Coil Flexibility Model 524A direct expansion coils have gal vanized steel casings inlet and outlet connections are on th...

Page 3: ...3 000 10 2 10 3 524A B150 145 000 10 5 10 9 524A C150 153 000 11 1 11 5 524A B180 152 000 10 8 11 0 524A C180 161 000 11 3 11 5 566D180 524A B180 176 000 9 8 12 3 198 000 11 14 9 524A C180 182 000 9 7 12 1 524A B240 184 000 9 8 12 2 524A C240 196 000 10 0 12 5 566E180 524A B150 176 000 10 0 10 4 204 000 11 9 13 9 524A C150 185 000 10 3 10 8 524A B180 187 000 10 2 10 5 524A C180 198 000 10 6 10 9 5...

Page 4: ...ndensing unit This switch also includes a power lockout capability to protect the service person This lockout switch saves the service person time and effort because there is no need to access a distant dis connect switch while servicing the unit FIELD INSTALLED ACCESSORIES Electric Unloader Package 576C120 Only includes hard ware and solenoid valve to convert a pressure operated unloader to elect...

Page 5: ... discharge directly into the occupied space integral horizontal and vertical louvers enable redirection of airflow Accessory is available unpainted or painted Field assembly required Return Air Grille provides a protective barrier over the return air opening and gives a finished appearance to units installed in the occupied space Accessory is available unpainted or painted Subbase provides a stabl...

Page 6: ...PLENUM RETURN AIR GRILLE SUBBASE FAN COIL UNIT ECONOMIZER FAN COIL UNIT FAN COIL UNIT HOT WATER OR STEAM COIL 524A with Economizer 524A with Hot Water or Steam Coil 524A with Discharge Plenum Return Grille and Subbase 524A with Condensate Trap ...

Page 7: ...The sizes shown are based on an equivalent length of pipe This equivalent length is equal to the linear length of pipe indicated at the top of each sizing column plus a 50 allowance for fitting losses For a more accurate determination of actual equivalent length in place of using the estimated 50 value refer to a standard refrigeration piping practice For this example note in the linear length col...

Page 8: ...at opens causing compressor no 2 and outdoor fan motor no 2 to shut down As the cooling continues to decrease stage one of the thermostat opens causing compressor no 1 and outdoor fan motor no 1 to shut down The LLS valve for each compressor will close when the associated compressor stops minimizing the potential for refrigerant migration during the off cycle The indoor fan motor will stop if the ...

Page 9: ...tors are protected under pri mary single phasing conditions VOLTAGE RATING CB MUST TRIP AMPS Mfg Part No 24 V Potter Brumfield 3 2 W28X 1024 3 2 AHA Adjustable Heat Anticipator C Contactor Compressor CAP Capacitor CB Circuit Breaker CC Cooling Compensator CH Crankcase Heater CLO Compressor Lockout COMP Compressor Motor DGT Discharge Gas Thermostat EQUIP Equipment GND Ground HPS High Pressure Switc...

Page 10: ... Indoor Fan Contactor LLSV Liquid Line Solenoid Valve LPS Low Pressure Switch NEC National Electrical Code OFM Outdoor Fan Motor OL Overload Relay R Relay TB Terminal Block TC Thermostat Cooling TH Thermostat Heating TRAN Transformer Field Splice Marked Wire Terminal Marked Terminal Unmarked Terminal Block Splice Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring T...

Page 11: ...nit With Scroll Compressor 569F Dual Circuit Commercial Air Cooled Condensing Unit With Scroll Compressor 576C P X 120 000 576C Commercial Air Cooled Condensing Unit With Semi Hermetic Compressor Voltage Designation E 460 3 60 P 208 230 3 60 T 575 3 60 Heating X None Nominal Tons Cooling 120 10 Heating Capacity 000 No Heat Factory Installed Options Contact your local representative for more detail...

Page 12: ... 0 2 0 2 0 2 0 COMPRESSOR Type Scroll Reciprocating Scroll Qty Model 1 SR_68 1 SR_94 1 ZR125 1 06DH824 2 SR_60 Oil Charge oz 88 90 110 128 72 ea No Cylinders N A 6 N A Speed rpm 3500 1750 3500 CONDENSER FAN Qty Rpm 2 850 2 1100 2 1100 2 1100 2 1100 Motor HP rpm 1 8 1 4 1 4 1 4 1 4 Diameter 22 22 22 22 Nominal Airflow Cfm Total 5400 6500 6500 6500 Watts Total 340 570 570 570 CONDENSER COIL Qty 2 2 ...

Page 13: ...0 195 84 38 166 75 66 30 114 52 812 8 32 00 676 3 26 63 576C120 575 261 55 25 265 120 88 40 167 76 927 1 36 50 647 7 25 50 UNIT ELECTRICAL CHARACTERISTICS 569D072 208 230 3 60 460 3 60 575 3 60 569D090 208 230 3 60 460 3 60 575 3 60 569D120 208 230 3 60 460 3 60 575 3 60 576C120 208 230 3 60 460 3 60 575 3 60 SERVICE VALVE CONNECTIONS Unit Suction mm in Liquid mm in 569D072 28 6 11 8 9 5 3 8 569D0...

Page 14: ...2 8 34 36 582 5 22 93 167 5 6 59 111 7 4 40 O 22 0 0 87 FIELD ENTRY SERVICE PORT BOTTOM OF UNIT 116 7 4 59 SUCTION CONNECTION SEE CHART FOR SIZE LIQUID CONNECTION SEE CHART FOR SIZE LIQUID CONNECTION SEE CHART FOR SIZE 637 9 25 11 1509 3 59 42 644 6 25 38 172 9 6 81 287 8 11 33 226 9 8 93 341 5 13 45 in in 569F120 UNIT ELECTRICAL CHARACTERISTICS ALUMINUM COIL Std Unit Wt Corner A Corner B Corner C...

Page 15: ...4 0 109 0 118 0 123 0 128 0 137 0 40 TC 133 0 130 0 123 0 119 0 115 0 108 0 kW 8 81 9 15 9 85 10 25 10 55 11 35 SDT 106 0 110 0 120 0 125 0 129 0 139 0 45 TC 144 0 141 0 133 0 130 0 126 0 118 0 kW 9 12 9 45 10 15 10 55 10 85 11 65 SDT 108 0 112 0 122 0 126 0 131 0 140 0 50 TC 156 0 152 0 145 0 141 0 137 0 128 0 kW 9 45 9 85 10 55 10 85 11 25 12 05 SDT 109 0 114 0 123 0 128 0 133 0 142 0 576C120 SS...

Page 16: ...4 kW 6 51 6 53 6 63 6 77 6 61 6 61 6 70 6 83 6 69 6 70 6 74 6 88 569D072 524A B072 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 1800 2400 3000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 63 4 66 1 71 7 77 8 69 0 69 8 74 9 81 1 72 9 72 9 76 9 83 1 SHC 63 4 58 4 49 0 39 2 69 0 67 2 56 0 43 6 72 9 72 9 62 5 47 6 kW 4 40 4 45 4 55 4 66 4 50 4 52 4 60...

Page 17: ... 6 kW 6 61 6 61 6 71 6 85 6 73 6 73 6 77 6 90 6 81 6 8 6 81 6 94 569D072 524A B090 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 2400 3000 3750 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 68 4 69 5 74 8 81 0 73 6 73 6 77 6 83 8 77 3 77 3 79 5 85 5 SHC 68 4 65 8 54 8 42 9 73 6 73 6 63 1 48 1 77 3 77 3 70 4 52 9 kW 4 49 4 51 4 61 4 72 4 58 4 58 4 65...

Page 18: ...3 2 kW 8 38 8 38 8 47 8 58 8 43 8 44 8 53 8 66 8 48 8 49 8 58 8 71 569D090 524A B072 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 1800 2400 3000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 75 3 81 2 88 5 96 1 82 5 86 4 93 6 101 0 88 0 89 9 96 8 104 0 SHC 74 3 65 8 56 3 46 4 82 5 75 7 63 5 50 9 88 0 84 1 70 0 54 9 kW 5 77 5 82 5 91 6 00 5 84 5 88 ...

Page 19: ... 1 56 4 kW 8 41 8 42 8 53 8 66 8 50 8 50 8 60 8 73 8 54 8 54 8 62 8 75 569D090 524A B090 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 2205 3000 3750 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 81 7 85 9 93 2 101 0 89 0 90 8 97 5 105 0 91 6 92 6 98 8 106 0 SHC 81 7 74 2 62 4 50 2 89 0 85 2 70 9 55 4 91 6 89 4 74 7 57 7 kW 5 83 5 88 5 97 6 07 5 92 ...

Page 20: ...0 11 40 11 40 11 60 11 90 11 60 11 60 11 70 12 00 569D120 524A B120 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3000 4000 5000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 110 0 115 0 124 0 134 0 119 0 121 0 130 0 139 0 126 0 126 0 133 0 143 0 SHC 110 0 99 4 83 3 66 8 119 0 114 0 94 6 73 6 126 0 125 0 105 0 79 9 kW 8 19 8 32 8 55 8 82 8 41 8 48 8...

Page 21: ...11 60 11 70 11 80 12 10 11 80 11 80 11 90 12 20 569D120 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 119 0 123 0 132 0 142 0 128 0 129 0 137 0 147 0 135 0 135 0 140 0 150 0 SHC 119 0 112 0 93 2 73 4 128 0 127 0 106 0 81 4 135 0 135 0 118 0 88 6 kW 8 42 8 51 8 77 9 05 8 66 8 68 8...

Page 22: ... 11 10 11 10 11 40 11 80 11 40 11 40 11 50 12 00 576C120 524A B120 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3000 4000 5000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 107 0 112 0 123 0 134 0 118 0 119 0 129 0 140 0 125 0 125 0 133 0 144 0 SHC 107 0 98 8 83 3 67 2 118 0 114 0 95 5 74 8 125 0 125 0 107 0 81 8 kW 7 91 8 03 8 25 8 49 8 14 8 18 8 ...

Page 23: ...0 11 50 11 50 11 60 12 10 11 70 11 70 11 80 12 20 576C120 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 115 0 118 0 129 0 140 0 125 0 126 0 134 0 146 0 132 0 132 0 138 0 149 0 SHC 115 0 110 0 92 3 73 1 125 0 125 0 106 0 81 7 132 0 132 0 119 0 89 6 kW 8 08 8 14 8 37 8 62 8 30 8 30...

Page 24: ...11 40 11 40 11 50 11 70 11 50 11 50 11 60 11 70 569F120 524A B120 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3000 4000 5000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 106 0 110 0 119 0 130 0 115 0 116 0 125 0 135 0 121 0 121 0 128 0 138 0 SHC 106 0 97 2 81 5 65 3 115 0 112 0 93 2 72 4 121 0 121 0 104 0 79 0 kW 7 83 7 89 7 98 8 11 7 94 7 95 8 0...

Page 25: ... 50 11 50 11 60 11 80 11 70 11 70 11 70 11 90 569F120 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 114 0 117 0 126 0 137 0 124 0 124 0 131 0 142 0 132 0 130 0 136 0 146 0 SHC 114 0 109 0 91 1 71 7 124 0 124 0 105 0 80 0 132 0 130 0 118 0 88 2 kW 7 93 7 96 8 07 8 20 8 03 8 04 8 1...

Page 26: ...25 6 190 1 5 3 1 35 0 60 CONVENIENCE OUTLET 39 8 60 NONE OR DISCONNECT 460 3 60 418 506 12 8 95 0 7 1 9 17 4 30 CONVENIENCE OUTLET 19 6 30 NONE OR DISCONNECT 575 3 60 523 632 10 2 76 0 7 1 9 13 8 20 CONVENIENCE OUTLET 15 5 20 120 NONE OR DISCONNECT 208 230 3 60 187 254 37 8 239 1 5 3 1 50 3 60 CONVENIENCE OUTLET 55 1 70 NONE OR DISCONNECT 460 3 60 418 506 17 2 125 0 7 1 9 22 9 30 CONVENIENCE OUTLE...

Page 27: ...structions REFRIGERANT SPECIALTIES PART NUMBERS Bushings required Maximum Cooling Outdoor 115 F Minimum Outdoor Ambient See Minimum Outdoor Air Operating Temperature table at right Minimum Return Air Temperature 55 F Maximum Return Air Temperature 95 F Normal Acceptable Saturation Suction Temperature Range 25 to 55 F Maximum Discharge Temperature 275 F Minimum Discharge Superheat 60 F UNIT SIZE R ...

Page 28: ...lectrical Code TXV Thermostatic Expansion Valve NOTES 1 All piping must follow standard refrigerant piping techniques Refer to Carrier System Design Manual for details 2 All wiring must comply with the applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation 4 Liquid lin...

Page 29: ...teel wire safety guards 4 Condenser fan and motor shaft shall be corrosion resistant D Compressor 1 Compressor shall be of the scroll type 569D or semi hermetic reciprocating type 576C 2 Compressors shall be mounted on vibration isolators 3 Compressors shall include overload protection 4 Compressors shall be equipped with a crankcase heater 5 Compressor shall be equipped with internal high dis cha...

Page 30: ...ll be up to a minimum of 1000 and 250 hours respectively ASTM D2247 92 and ASTM D870 92 Corrosion durability shall be con firmed through testing to no less than 1000 hours salt spray per ASTM B117 90 Coil construction shall be aluminum fins mechanically bonded to copper tubes 3 Thermostat Control Accessory a Commercial Electronic Thermostat with 7 day timeclock auto changeover multi stage capabil ...

Page 31: ...etic scroll type 2 Compressors shall be mounted on vibration isolators 3 Compressors shall include overload protection 4 Compressors shall be equipped with a crankcase heater 5 Compressors shall be equipped with high discharge temperature protection E Condenser Coil 1 Condenser coil shall be air cooled and circuited for integral subcooler 2 Coil shall be constructed of aluminum fins copper fins op...

Page 32: ...rrosion dura bility shall be confirmed through testing to no less than 1000 hours salt spray per ASTM B117 90 Coil construction shall be aluminum fins mechani cally bonded to copper tubes 4 Thermostat Controls a Programmable multi stage thermostat with 7 day clock holiday scheduling large backlit display remote sensor capability and Title 24 compliance b Commercial Electronic Thermostat with 7 day...

Page 33: ... Heating X None 566D Commercial Air Cooled Condensing Unit With Semi Hermetic Compressor 566E Dual Circuit Commercial Air Cooled Condensing Unit With Scroll Compressors Voltage Designation E 460 3 60 P 208 230 3 60 T 575 3 60 Contact your local representative for more details Certified to ISO 9001 2000 Quality Assurance 50TFQ004 012 566D E150 240 ...

Page 34: ...8 1 06DD537 1 06E4250 No Cylinders 6 6 4 Speed rpm 1750 1750 1750 Oil Charge pt 10 10 15 5 Capacity Steps Accessory 33 66 100 33 66 100 Standard 66 100 66 100 50 100 Unloader Setting psig Load 70 1 Unload 60 2 Crankcase Heater Watts 125 CONDENSER FANS Axial Flow Direct Drive Qty Rpm 2 1075 Diameter in 26 Nominal Hp 1 2 Nominal Airflow cfm total 11 000 Watts total 1460 CONDENSER COIL Copper Tubes A...

Page 35: ...3 23 28 Shipping Charge lb 3 1 3 1 3 1 COMPRESSOR Scroll Qty Model 2 ZR72 2 ZR94 2 ZR125 Speed rpm 3500 3500 3500 Oil Charge oz 60 ea 85 ea 110 ea Crankcase Heater Watts 70 CONDENSER FANS Qty Rpm 2 1075 Diameter in 26 Nominal Hp 1 2 Nominal Airflow cfm total 11 000 Watts total 1460 CONDENSER COIL Rows Fins in 3 15 Face Area sq ft 29 2 Storage Capacity lb 48 CONTROLS Pressurestat psig High Pressure...

Page 36: ... 566D150 240 NOTES 1 Service clearances are as follows Side compressor 31 2 ft Side opposite compressor 3 ft Ends 2 ft Top 5 ft 2 See page 38 for corner weights and unit center of gravity 50TFQ004 012 566D E150 240 ...

Page 37: ...vice clearances are as follows Side compressor 31 2 ft 1067 mm Side opposite compressor 3 ft 914 mm Ends 2 ft 610 mm Top 5 ft 1524 mm 2 See page 38 for corner weights and unit center of gravity 566E150 240 50TFQ004 012 566D E150 240 ...

Page 38: ... UNIT 566E ALUMINUM COIL Standard Weight lb Operational Weight Points lb A B C D E F 150 676 84 168 72 78 183 91 180 740 86 186 71 82 216 99 240 764 87 192 72 85 226 102 UNIT 566E CENTER OF GRAVITY in Aluminum Coil X Y 150 35 19 180 35 18 240 35 18 NOTES 1 Corner weights are approximate 2 Actual support weights depend on level of unit and evenness of support posts 3 Total weights represent approxi...

Page 39: ... 566E150 SST F Air Temperature Entering Condenser F 80 85 95 100 105 115 20 TC 102 0 99 1 93 2 90 3 87 3 81 1 kW 9 04 9 58 10 80 11 40 12 10 13 50 SDT 103 0 108 0 118 0 123 0 128 0 138 0 25 TC 114 0 111 0 105 0 102 0 98 8 92 2 kW 9 09 9 64 10 90 11 50 12 20 13 60 SDT 103 0 108 0 118 0 123 0 128 0 138 0 30 TC 127 0 124 0 117 0 114 0 110 0 103 0 kW 9 14 9 70 10 90 11 50 12 20 13 70 SDT 103 0 108 0 1...

Page 40: ...12 50 12 50 12 80 13 20 12 80 12 80 12 90 13 30 566D150 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 127 0 134 0 146 0 160 0 140 0 142 0 153 0 167 0 148 0 148 0 158 0 172 0 SHC 127 0 118 0 99 4 80 2 140 0 136 0 114 0 89 0 148 0 148 0 126 0 96 9 kW 8 93 9 01 9 19 9 40 9 09 9 12 9...

Page 41: ... 20 12 80 12 80 13 00 13 40 13 00 13 00 13 10 13 50 566D150 524A B180 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 4500 6000 7500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 140 0 144 0 156 0 170 0 152 0 152 0 162 0 176 0 160 0 160 0 167 0 181 0 SHC 140 0 134 0 112 0 88 3 152 0 152 0 128 0 98 7 160 0 160 0 143 0 108 0 kW 9 09 9 14 9 34 9 55 9 28 ...

Page 42: ... 18 00 18 00 18 60 19 40 18 50 18 50 18 90 19 70 566D180 524A B180 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 4500 6000 7500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 165 0 175 0 190 0 207 0 180 0 185 0 200 0 217 0 191 0 193 0 206 0 223 0 SHC 165 0 149 0 126 0 102 0 180 0 172 0 143 0 113 0 191 0 190 0 159 0 123 0 kW 13 00 13 30 13 80 14 30 13...

Page 43: ...00 19 20 19 20 19 50 20 30 19 70 19 70 19 80 20 50 566D180 524A B240 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 6 000 8 000 10 000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 186 0 190 0 205 0 222 0 201 0 201 0 212 0 230 0 211 0 211 0 218 0 235 0 SHC 186 0 178 0 148 0 117 0 201 0 201 0 171 0 130 0 211 0 211 0 190 0 143 0 kW 13 70 13 80 14 20 14...

Page 44: ... 25 30 25 30 25 80 26 90 26 00 26 00 26 10 27 20 566D240 524A B300 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 7 500 10 000 12 500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 230 0 236 0 255 0 277 0 249 0 249 0 266 0 287 0 262 0 262 0 272 0 293 0 SHC 230 0 219 0 183 0 144 0 249 0 248 0 209 0 161 0 262 0 262 0 233 0 176 0 kW 18 40 18 60 19 40 20 ...

Page 45: ...90 13 80 13 80 13 80 13 90 13 80 13 80 13 90 14 00 566E150 524A B120 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3000 4000 5000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 119 0 128 0 140 0 153 0 131 0 136 0 148 0 161 0 140 0 142 0 153 0 166 0 SHC 119 0 106 0 90 4 74 3 131 0 122 0 103 0 82 0 140 0 136 0 114 0 89 0 kW 9 09 9 15 9 18 9 23 9 15 9 1...

Page 46: ...0 14 00 13 80 13 90 13 90 14 00 13 90 13 90 13 90 14 10 566E150 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 130 0 137 0 150 0 163 0 143 0 145 0 157 0 171 0 151 0 151 0 162 0 176 0 SHC 130 0 120 0 101 0 81 6 143 0 138 0 115 0 90 5 151 0 151 0 128 0 98 5 kW 9 14 9 18 9 22 9 32 9 ...

Page 47: ...14 10 13 90 14 00 14 00 14 20 14 00 14 00 14 00 14 20 566E150 524A B180 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 4500 6000 7500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 143 0 147 0 160 0 174 0 155 0 156 0 166 0 180 0 164 0 164 0 171 0 185 0 SHC 143 0 136 0 113 0 89 9 155 0 155 0 130 0 100 0 164 0 164 0 146 0 110 0 kW 9 19 9 22 9 28 9 42 9 ...

Page 48: ...0 17 30 17 40 17 80 18 20 17 60 17 60 17 90 18 40 566E180 524A B150 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 3750 5000 6250 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 154 0 166 0 181 0 196 0 168 0 176 0 191 0 206 0 179 0 183 0 197 0 213 0 SHC 152 0 134 0 115 0 94 7 168 0 154 0 129 0 104 0 179 0 171 0 143 0 112 0 kW 12 40 12 60 13 00 13 30 12...

Page 49: ...8 40 17 80 17 80 18 10 18 60 18 10 18 10 18 30 18 80 566E180 524A B180 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 4500 6000 7500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 169 0 180 0 195 0 211 0 185 0 190 0 204 0 221 0 196 0 197 0 211 0 227 0 SHC 169 0 152 0 128 0 104 0 185 0 175 0 146 0 115 0 196 0 193 0 162 0 125 0 kW 12 70 12 90 13 30 13 7...

Page 50: ...80 18 30 18 30 18 50 19 00 18 60 18 60 18 70 19 10 566E180 524A B240 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 6 000 8 000 10 000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 190 0 194 0 209 0 226 0 205 0 205 0 217 0 233 0 215 0 215 0 222 0 238 0 SHC 190 0 181 0 150 0 118 0 205 0 204 0 173 0 132 0 215 0 215 0 193 0 145 0 kW 13 20 13 30 13 60 14...

Page 51: ... 24 10 24 10 24 60 25 40 24 60 24 60 24 90 25 60 566E240 524A B240 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 6 000 8 000 10 000 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 219 0 229 0 248 0 267 0 237 0 241 0 259 0 278 0 250 0 251 0 265 0 285 0 SHC 219 0 199 0 167 0 134 0 237 0 228 0 190 0 148 0 250 0 250 0 211 0 161 0 kW 17 30 17 70 18 30 19 0...

Page 52: ...50 24 70 24 70 25 00 25 80 25 20 25 20 25 30 26 00 566E240 524A B300 WITH STANDARD 3 ROW COIL Temp F Air Entering Condenser Edb Evaporator Air Cfm 7 500 10 000 12 500 Evaporator Air Ewb F 57 62 67 72 57 62 67 72 57 62 67 72 80 TC 236 0 242 0 260 0 280 0 254 0 254 0 269 0 290 0 266 0 266 0 276 0 296 0 SHC 236 0 223 0 185 0 146 0 254 0 252 0 212 0 162 0 266 0 266 0 236 0 178 0 kW 17 90 18 10 18 70 1...

Page 53: ...ioning and Refrigeration ICF Maximum Instantaneous Current Flow During Start Up LRA of compressor plus total FLA of fan motors kW Total Fan Motor Input kilowatts LRA Locked Rotor Amps MCA Minimum Circuit Amps per NEC Section 430 24 MOCP Maximum Overcurrent Protection amps RLA Rated Load Amps compressor UNIT SIZE FACTORY INSTALLED OPTION NOMINAL VOLTAGE 3 Ph 60 Hz VOLTAGE RANGE COMPRESSOR 1 COMPRES...

Page 54: ...imum Return Air Temperature 95 F Normal Acceptable Saturation Suction Temperature Range 25 to 55 F Maximum Discharge Temperature 295 F Minimum Discharge Superheat 60 F UNIT 566D NO OF CYLINDERS FULL LOAD CAPACITY MINIMUM OUTDOOR AIR OPERATING TEMPERATURE F Base Unit With Low Ambient Control 150 6 100 20 20 4 67 31 2 33 40 180 6 100 20 4 67 33 2 33 47 240 4 100 15 2 50 20 UNIT 566E FULL LOAD CAPACI...

Page 55: ...5 16 25 26 50 51 75 76 100 Line Size in OD L S L S L S L S L S 150 1 2 11 8 1 2 13 8 5 8 13 8 5 8 15 8 7 8 15 8 180 1 2 13 8 5 8 13 8 5 8 15 8 7 8 15 8 7 8 21 8 240 5 8 15 8 5 8 15 8 7 8 15 8 7 8 21 8 7 8 21 8 UNIT 566E LINEAR LENGTH OF INTERCONNECTING PIPING FT 0 25 25 50 50 75 75 100 Line Size in OD L S L S L S L S 150 1 2 11 8 1 2 11 8 1 2 11 8 1 2 11 8 180 1 2 13 8 1 2 13 8 1 2 13 8 5 8 13 8 2...

Page 56: ...TIPLE CONDENSING UNIT ARRANGEMENTS Space for Service and Airflow For clearances between controls and grounded surfaces check local codes 566D 566E DIMENSIONS ft 150 240 A B 4 4 566D 566E150 240 566D 566E150 240 566D 566E150 240 50TFQ004 012 566D E150 240 ...

Page 57: ... with the applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation 4 Liquid line solenoid valve solenoid drop control is recom mended to prevent refrigerant migration to the compressor 5 Internal factory supplied TXVs not shown Rooftop Installation 566D150 240 50TFQ004 0...

Page 58: ... with the applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation 4 Liquid line solenoid valve solenoid drop control is recom mended to prevent refrigerant migration to the compressor 5 Internal factory supplied TXVs not shown Ground Level Installation 566D150 240 50TFQ...

Page 59: ... D Compressors 1 566D150 240 Units a Compressor shall be serviceable reciprocating semi hermetic type b Compressor shall be equipped with an automati cally reversible oil pump operating oil charge suction and discharge shutoff valves and an insert type factory sized crankcase heater to control oil dilution c Compressor shall be mounted on spring vibration isolators with an isolation efficiency of ...

Page 60: ...minum Fin Coils Shall have a durable epoxy phenolic coating to provide protection in mildly corrosive coastal envi ronments Coating shall be applied to the alumi num fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube Epoxy phenolic barrier shall minimize galvanic action between dissimilar metals b E Coated Aluminum Fin Coils Shall have a...

Page 61: ...e ED Painted Standard Motor and Standard Drive FD Painted Standard Motor and Medium Static Drive not available for 300 size RD Painted Alternate Motor and Medium Static Drive 300 size only WD Painted Alternate Motor and High Static Drive Nominal Heating Btuh 000 Not applicable 524A B and 524A C Cooling Only Units LEGEND The YC and WD option codes for all 090 size units with 208 230 1 60 voltage de...

Page 62: ...2 0 2 5 2 5 3 5 3 5 4 5 4 5 DIRECT EXPANSION COIL Enhanced Copper Tubes Aluminum Sine Wave Fins Max Working Pressure psig 435 Face Area sq ft 6 67 8 33 10 01 13 25 17 67 19 88 24 86 No of Splits 1 1 2 2 2 2 2 Split Type Percentage Face 50 50 No of Circuits per Split 3 Row 4 Row 12 12 15 15 9 9 9 12 12 16 13 18 15 20 Fins in 15 15 17 15 15 17 15 STEAM COIL Max Working Pressure psig at 400 F 175 Tot...

Page 63: ... in millimeters 2 Direction of airflow 3 Recommended clearance Rear 3 76 2 mm 2 6 762 mm with electric heat accessory Front 2 6 762 mm Right Side 2 6 762 mm Left Side 2 6 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Bryant 5 Duct flange is factory supplied and field installed TXV Thermostatic Expansion Valve 50TFQ004 012 524A072 300 ...

Page 64: ...eters 2 Direction of airflow 3 Recommended clearance Rear 3 76 2 mm 2 6 762 mm with electric heat accessory Front 2 6 762 mm Right Side 2 6 762 mm Left Side 2 6 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Bryant 5 Duct flange is factory supplied and field installed TXV Thermostatic Expansion Valve 50TFQ004 012 524A072 300 ...

Page 65: ...TES 1 Dimensions in are in millimeters 2 Direction of airflow 3 Recommended clearance Rear 3 76 2 mm 2 6 762 mm with electric heat accessory Front 2 6 762 mm Right Side 2 6 762 mm Left Side 2 6 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Bryant 5 Duct flange is factory supplied and field installed TXV Thermostatic Expansion Valve 50TFQ004 012 524A072 300 ...

Page 66: ... 1180 3 54 1064 3 82 1109 4 11 150 3 750 394 0 40 453 0 52 558 0 80 643 1 10 717 1 39 785 1 71 848 2 04 4 300 436 0 57 487 0 70 586 1 00 670 1 34 742 1 67 806 2 01 867 2 36 5 000 492 0 86 535 0 99 623 1 31 704 1 69 775 2 08 838 2 47 896 2 86 5 700 550 1 23 587 1 37 664 1 71 740 2 11 809 2 55 872 2 99 929 3 43 6 250 596 1 59 630 1 74 700 2 09 770 2 51 837 2 97 899 3 45 955 3 94 180 4 500 428 0 59 4...

Page 67: ...3 1 79 1150 1 99 1064 2 20 1113 2 42 1159 2 64 3 400 998 2 18 1045 2 39 1092 2 61 1137 2 83 1182 3 07 3 750 1360 2 58 1078 2 80 1122 3 03 1164 3 27 120 3 000 949 1 74 1000 1 93 1050 2 14 1099 2 36 1147 2 58 1192 2 81 3 500 990 2 21 1037 2 42 1083 2 64 1128 2 86 1172 3 10 4 000 1040 2 80 1084 3 03 1126 3 26 1167 3 50 4 500 1094 3 53 1136 3 78 1176 4 03 5 000 1151 4 39 1191 4 66 150 3 750 909 2 37 9...

Page 68: ...0 893 2 84 946 3 14 997 3 43 1046 3 72 1092 4 00 1135 4 28 150 3 750 410 0 43 467 0 55 567 0 83 649 1 12 721 1 41 788 1 72 851 2 05 4 300 455 0 62 504 0 74 599 1 05 679 1 38 748 1 70 811 2 04 871 2 39 5 000 514 0 92 556 1 06 641 1 39 718 1 76 786 2 14 847 2 52 903 2 91 5 700 575 1 32 612 1 47 686 1 82 759 2 23 825 2 66 884 3 09 939 3 52 6 250 624 1 71 657 1 87 725 2 24 793 2 66 856 3 12 915 3 59 9...

Page 69: ...005 1 72 1057 1 92 1107 2 13 1154 2 33 3 000 980 1 86 1031 2 06 1081 2 27 1129 2 49 1175 2 72 3 400 1018 2 26 1065 2 48 1111 2 70 1156 2 93 3 750 1057 2 69 1101 2 92 1144 3 15 1186 3 39 120 3 000 961 1 78 1120 1 98 1062 2 19 1111 2 41 1158 2 64 3 500 1005 2 27 1052 2 49 1098 2 71 1142 2 94 1186 3 18 4 000 1058 2 90 1101 3 13 1143 3 36 1184 3 60 4 500 1116 3 66 1157 3 91 1196 4 16 5 000 1176 4 56 1...

Page 70: ... 150 X 0 50 UNIT 524A AIRFLOW Cfm DISCHARGE PLENUM RETURN AIR GRILLE HEATING COILS ECONOMIZER Hot Water Steam Electric 072 1 800 2 400 3 000 0 06 0 10 0 14 0 01 0 01 0 02 0 10 0 16 0 23 0 10 0 16 0 23 0 04 0 06 0 10 0 05 0 07 0 09 090 2 250 3 000 3 750 0 09 0 14 0 21 0 01 0 02 0 03 0 15 0 23 0 35 0 15 0 23 0 35 0 06 0 10 0 15 0 06 0 09 0 15 102 2 550 3 400 4 250 0 11 0 17 0 24 0 02 0 03 0 04 0 18 ...

Page 71: ...6 8 2 150 3 750 5 000 6 250 370 425 465 150 137 128 362 0 409 0 456 0 149 136 128 36 2 40 9 45 6 4 2 5 1 6 0 180 4 500 6 000 7 500 402 458 479 141 129 118 412 0 471 0 529 0 145 133 125 41 2 47 1 52 9 4 5 5 5 6 6 240 6 000 8 000 10 000 458 487 499 129 115 105 506 0 584 0 652 0 138 128 120 50 6 58 4 65 2 5 1 6 3 7 5 300 7 500 10 000 12 500 511 575 626 122 112 106 649 0 752 0 842 0 140 130 122 64 9 7...

Page 72: ...632 2 0 1 49 2 3 2 9 15 120 208 230 3 60 187 253 2 4 1 79 5 2 6 5 15 460 3 60 414 506 2 4 1 79 2 6 3 3 15 575 3 60 518 632 2 0 1 49 2 3 2 9 15 150 208 230 3 60 187 253 2 9 2 16 7 5 9 4 15 460 3 60 414 506 2 9 2 16 3 4 4 3 15 575 3 60 518 632 3 0 2 24 3 8 4 8 15 180 208 230 3 60 187 253 3 7 2 76 10 2 12 8 20 460 3 60 414 506 3 7 2 76 4 8 6 0 15 575 3 60 518 632 3 0 2 24 3 8 4 8 15 240 208 230 3 60 ...

Page 73: ... company immediately UNIT 524A B 524A C V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA Minimum Circuit Amps MOCP 072 208 230 1 60 187 253 2 4 1 79 11 0 13 8 20 208 230 3 60 187 253 2 9 2 16 7 5 9 4 15 460 3 60 414 506 2 9 2 16 3 4 4 3 15 575 3 60 518 632 2 0 1 49 2 3 2 9 15 090 208 230 1 60 187 253 2 4 1 79 11 0 13 8 15 208 230 3 60 187 253 2 9 2 16 7 5 9 4 15 460 3 60 414 506 2 9 2 16 3 ...

Page 74: ...8 35 4 40 3 7 2 76 10 2 10 7 5 7 5 20 8 38 8 40 240 3 60 1 3 0 97 7 6 10 10 0 10 0 24 1 39 6 40 2 4 1 79 11 0 10 10 0 10 0 24 1 43 8 50 2 4 1 79 5 2 10 10 0 10 0 24 1 36 6 40 2 9 2 16 7 5 10 10 0 10 0 24 1 39 4 40 3 7 2 76 10 2 10 10 0 10 0 24 1 42 8 50 CAELHEAT005A00 480 3 60 2 4 1 79 2 6 10 10 0 10 0 12 0 18 3 20 2 9 2 16 3 4 10 10 0 10 0 12 0 19 3 20 3 7 2 76 4 8 10 10 0 10 0 12 0 21 0 25 CAELH...

Page 75: ... 77 9 80 240 3 60 1 3 0 97 7 6 25 15 0 10 0 25 0 60 1 84 7 90 2 4 1 79 11 0 25 15 0 10 0 25 0 60 1 88 9 90 2 4 1 79 5 2 25 15 0 10 0 25 0 60 1 81 7 90 2 9 2 16 7 5 25 15 0 10 0 25 0 60 1 84 6 90 3 7 2 76 10 2 25 15 0 10 0 25 0 60 1 87 9 90 CAELHEAT011A00 480 3 60 2 4 1 79 2 6 25 15 0 10 0 25 0 30 1 40 8 50 2 9 2 16 3 4 25 15 0 10 0 25 0 30 1 41 8 50 3 7 2 76 4 8 25 15 0 10 0 25 0 30 1 43 6 50 CAEL...

Page 76: ... 9 41 5 78 7 80 240 3 60 2 9 2 16 7 5 20 19 9 19 9 47 9 69 2 70 3 7 2 76 10 2 20 19 9 19 9 47 9 72 6 80 5 0 3 73 12 8 20 19 9 19 9 47 9 75 8 80 7 5 5 59 19 4 20 19 9 19 9 47 9 84 1 80 CAELHEAT020A00 480 3 60 2 9 2 16 3 4 20 20 0 20 0 24 1 34 3 35 3 7 2 76 4 8 20 20 0 20 0 24 1 36 1 40 5 0 3 73 6 4 20 20 0 20 0 24 1 39 1 40 7 5 5 59 9 7 20 20 0 20 0 24 1 43 2 50 CAELHEAT021A00 575 3 60 3 0 2 24 3 8...

Page 77: ...9 4 50 30 0 20 0 50 0 120 3 174 6 200 CAELHEAT026A00 480 3 60 3 7 2 76 4 8 50 30 0 20 0 50 0 60 1 81 2 90 5 0 3 73 6 4 50 30 0 20 0 50 0 60 1 83 2 90 7 5 5 59 9 7 50 30 0 20 0 50 0 60 1 87 3 90 CAELHEAT027A00 575 3 60 3 0 2 24 3 8 50 30 0 20 0 50 0 50 2 67 5 70 5 0 3 73 5 1 50 30 0 20 0 50 0 50 2 69 1 70 7 5 5 59 7 8 50 30 0 20 0 50 0 50 2 72 5 80 CAELHEAT028A00 524A B300 524A C300 208 3 60 7 5 5 ...

Page 78: ...4A00 524A B300 524A C300 208 3 60 7 5 5 59 19 8 50 22 6 15 0 37 6 104 3 157 2 175 10 0 7 46 28 0 50 22 6 15 0 37 6 104 3 165 6 175 240 3 60 7 5 5 59 19 4 50 30 0 20 0 50 0 120 3 174 6 200 10 0 7 46 26 8 50 30 0 20 0 50 0 120 3 183 9 200 CAELHEAT035A00 480 3 60 7 5 5 59 9 7 50 30 0 20 0 50 0 60 1 87 3 90 10 0 7 46 13 4 50 30 0 20 0 50 0 60 1 91 9 100 CAELHEAT036A00 575 3 60 7 5 5 59 7 8 50 30 0 20 ...

Page 79: ... Association UNIT COIL TYPE TXV Qty Part No DISTRIBUTOR Qty Part No FEEDER TUBES PER DISTRIBUTOR Qty Size in NOZZLE Qty Part No 524A B C 072 3 4 Row 1 TDEBX8 1 1116 12 1 4 1 E5 524A B C 090 3 4 Row 1 TDEBX8 1 1126 15 1 4 1 C6 524A B C 120 3 4 Row 2 TDEX6 2 1115 9 1 4 2 E4 524A B 150 3 Row 2 TDEBX8 2 1115 9 1 4 2 E5 524A C 150 4 Row 2 TDEBX8 2 1115 12 3 16 2 E5 524A B 180 3 Row 2 TDEBX8 2 1116 12 1...

Page 80: ...in 7 8 7 8 7 8 11 8 11 8 13 8 13 8 UNIT SIZE 524A 072 090 120 150 180 240 300 MOTOR DRIVE Motor Pulley Pitch Diameter in 2 4 3 4 2 8 3 8 3 4 4 4 2 8 3 8 2 8 3 8 3 7 4 7 4 3 5 3 Pulley Factory Setting Full Turns Open 2 5 2 5 2 5 2 5 2 5 3 0 3 0 FAN DRIVE Pulley Pitch Dia in 8 8 8 8 8 8 9 0 9 0 9 4 11 0 Pulley Bore in 1 1 1 17 16 17 16 17 16 115 16 Belt No Section 1 A 1 A 1 A 1 A 1 A 1 B 2 B Belt Pi...

Page 81: ... 984 Max Allowable Speed rpm 1200 1200 1200 1200 1200 1200 1100 Change per 1 2 Turn of Moveable Motor Pulley Flange 19 7 21 6 21 6 21 1 16 7 15 3 15 3 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 6 6 6 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 9 16 10 99 6 67 9 43 UNIT SIZE 524A 072 090 120 150 180 240 300 MOTOR DRIVE Motor Pulley Pitch Diameter in 3 4 4 ...

Page 82: ...o facilitate field connection Drain pans shall have the ability to be sloped toward the right or left side of the unit to prevent standing water from accumulating in pans 4 Unit shall have factory supplied 2 in throwaway type filters installed upstream from the cooling coil Filter access shall be from either the right or left side of the unit B Coils Coils shall consist of 3 rows 524A B or 4 rows ...

Page 83: ...ngeover multi stage capabil ity and large LCD temperature display b Commercial Electronic Non programmable Ther mostat with auto changeover multi stage capac ity and large LCD display 11 Overhead Suspension Package Package shall include necessary brackets to support units in a horizontal ceiling installation 12 Condensate Drain Trap Trap shall have transparent serviceable design for easy cleaning ...

Page 84: ...s 524A072 300 66 69 Features Benefits 1 2 Gage panel 4 Guide specifications 569D072 120 576C120 29 30 569F120 31 32 566D E150 240 59 60 524A072 300 82 83 Hail guard 4 Hot water coil 5 6 71 Hydronic heat 71 Indoor air quality IAQ 1 Liquid line piping 27 55 Low ambient controls 4 Maximum temperature 27 54 Minimum ambient operating temperature 27 54 Minimum temperature 27 54 Model number nomenclature...

Reviews: