47
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
LEGEND
566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500
6000
7500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
152.0
156.0
169.0
183.0
166.0
166.0
176.0
190.0
175.0
175.0
181.0
195.0
SHC
152.0
145.0
121.0
95.4
166.0
166.0
140.0
107.0
175.0
175.0
157.0
119.0
kW
9.24
9.26
9.35
9.53
9.33
9.33
9.43
9.63
9.42
9.43
9.49
9.69
85
TC
150.0
154.0
166.0
181.0
164.0
164.0
173.0
187.0
173.0
173.0
178.0
191.0
SHC
150.0
144.0
120.0
94.4
164.0
164.0
139.0
106.0
173.0
173.0
156.0
118.0
kW
9.80
9.82
9.92
10.10
9.89
9.89
9.99
10.20
9.98
9.99
10.00
10.20
95
TC
146.0
148.0
161.0
175.0
159.0
159.0
167.0
181.0
167.0
167.0
172.0
185.0
SHC
146.0
141.0
117.0
92.2
159.0
159.0
136.0
104.0
167.0
167.0
154.0
115.0
kW
11.00
11.10
11.10
11.30
11.10
11.10
11.20
11.40
11.20
11.20
11.20
11.40
100
TC
144.0
146.0
158.0
171.0
156.0
156.0
164.0
178.0
165.0
165.0
169.0
181.0
SHC
144.0
140.0
116.0
91.1
156.0
156.0
135.0
103.0
165.0
165.0
152.0
114.0
kW
11.70
11.70
11.80
11.90
11.80
11.80
11.90
12.00
11.80
11.90
11.90
12.10
105
TC
141.0
143.0
155.0
168.0
154.0
154.0
161.0
174.0
162.0
162.0
165.0
178.0
SHC
141.0
138.0
115.0
90.0
154.0
154.0
134.0
102.0
162.0
162.0
151.0
113.0
kW
12.40
12.40
12.50
12.60
12.50
12.50
12.50
12.70
12.50
12.50
12.60
12.80
115
TC
137.0
138.0
148.0
162.0
148.0
148.0
154.0
167.0
156.0
156.0
159.0
170.0
SHC
137.0
135.0
112.0
87.6
148.0
148.0
131.0
99.5
156.0
156.0
148.0
111.0
kW
13.90
13.90
13.90
14.10
13.90
14.00
14.00
14.20
14.00
14.00
14.00
14.20
566E150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500
6000
7500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
143.0
147.0
160.0
174.0
155.0
156.0
166.0
180.0
164.0
164.0
171.0
185.0
SHC
143.0
136.0
113.0
89.9
155.0
155.0
130.0
100.0
164.0
164.0
146.0
110.0
kW
9.19
9.22
9.28
9.42
9.27
9.26
9.34
9.49
9.31
9.33
9.37
9.54
85
TC
141.0
145.0
157.0
171.0
153.0
153.0
164.0
178.0
162.0
162.0
168.0
182.0
SHC
141.0
134.0
112.0
89.0
153.0
153.0
129.0
99.5
162.0
162.0
144.0
109.0
kW
9.75
9.77
9.85
9.98
9.82
9.82
9.90
10.00
9.87
9.89
9.93
10.10
95
TC
137.0
140.0
152.0
165.0
149.0
149.0
158.0
172.0
157.0
157.0
162.0
175.0
SHC
137.0
132.0
110.0
86.9
149.0
149.0
127.0
97.4
157.0
157.0
142.0
107.0
kW
11.00
11.00
11.10
11.20
11.00
11.00
11.10
11.20
11.10
11.10
11.10
11.30
100
TC
135.0
138.0
149.0
162.0
146.0
146.0
155.0
168.0
154.0
154.0
159.0
172.0
SHC
135.0
131.0
109.0
85.8
146.0
146.0
126.0
96.3
154.0
154.0
141.0
106.0
kW
11.60
11.60
11.70
11.80
11.70
11.70
11.80
11.90
11.70
11.80
11.80
11.90
105
TC
133.0
135.0
146.0
159.0
144.0
144.0
152.0
165.0
152.0
152.0
156.0
169.0
SHC
133.0
129.0
108.0
84.7
144.0
144.0
125.0
95.2
152.0
152.0
139.0
105.0
kW
12.30
12.30
12.40
12.50
12.40
12.40
12.50
12.60
12.40
12.50
12.50
12.60
115
TC
129.0
130.0
140.0
153.0
139.0
139.0
146.0
158.0
146.0
146.0
150.0
162.0
SHC
129.0
126.0
106.0
82.5
139.0
139.0
122.0
92.9
146.0
146.0
137.0
103.0
kW
13.80
13.80
13.90
14.00
13.90
13.90
13.90
14.10
13.90
13.90
13.90
14.10
Edb —
Entering Dry Bulb
Ewb —
Entering Wet Bulb
kW
—
Compressor Motor Power Input
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
5
0TF
Q0
04-
0
1
2
56
6D
/E
150
-2
40