25
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120 (cont)
LEGEND
569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750
5000
6250
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
121.0
123.0
132.0
143.0
131.0
131.0
138.0
148.0
140.0
138.0
143.0
153.0
SHC
121.0
116.0
96.4
75.6
131.0
131.0
112.0
85.1
140.0
138.0
127.0
94.5
kW
8.00
8.03
8.14
8.29
8.12
8.12
8.21
8.36
8.24
8.22
8.28
8.42
85
TC
119.0
121.0
130.0
141.0
129.0
129.0
135.0
146.0
138.0
137.0
140.0
150.0
SHC
119.0
115.0
95.5
74.8
129.0
129.0
111.0
84.3
138.0
137.0
126.0
93.6
kW
8.45
8.48
8.59
8.74
8.58
8.58
8.67
8.82
8.70
8.68
8.73
8.88
95
TC
115.0
117.0
125.0
136.0
125.0
125.0
131.0
141.0
134.0
133.0
135.0
145.0
SHC
115.0
112.0
93.7
73.1
125.0
125.0
109.0
82.5
134.0
133.0
124.0
91.9
kW
9.35
9.37
9.50
9.66
9.49
9.49
9.57
9.73
9.62
9.60
9.64
9.80
100
TC
113.0
115.0
123.0
133.0
123.0
123.0
128.0
138.0
131.0
131.0
132.0
142.0
SHC
113.0
111.0
92.8
72.1
123.0
123.0
108.0
81.6
131.0
131.0
123.0
91.0
kW
9.86
9.87
10.0
10.20
10.00
9.99
10.10
10.20
10.10
10.10
10.10
10.30
105
TC
112.0
113.0
121.0
131.0
121.0
121.0
125.0
135.0
129.0
129.0
130.0
139.0
SHC
112.0
110.0
91.8
71.2
121.0
121.0
107.0
80.7
129.0
129.0
122.0
90.0
kW
10.40
10.40
10.50
10.70
10.50
10.50
10.60
10.80
10.60
10.60
10.70
10.80
115
TC
108.0
108.0
116.0
126.0
116.0
116.0
120.0
130.0
124.0
124.0
124.0
133.0
SHC
108.0
107.0
89.9
69.4
116.0
116.0
105.0
78.9
124.0
123.0
120.0
88.2
kW
11.40
11.40
11.50
11.70
11.50
11.50
11.60
11.80
11.70
11.70
11.70
11.90
569F120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750
5000
6250
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
114.0
117.0
126.0
137.0
124.0
124.0
131.0
142.0
132.0
130.0
136.0
146.0
SHC
114.0
109.0
91.1
71.7
124.0
124.0
105.0
80.0
132.0
130.0
118.0
88.2
kW
7.93
7.96
8.07
8.20
8.03
8.04
8.13
8.27
8.14
8.12
8.19
8.33
85
TC
113.0
115.0
124.0
134.0
122.0
122.0
129.0
139.0
130.0
129.0
133.0
144.0
SHC
113.0
108.0
90.2
70.8
122.0
122.0
104.0
79.2
130.0
129.0
117.0
87.4
kW
8.37
8.40
8.51
8.65
8.49
8.49
8.58
8.72
8.59
8.57
8.64
8.78
95
TC
109.0
111.0
120.0
130.0
118.0
118.0
124.0
135.0
126.0
125.0
129.0
139.0
SHC
109.0
106.0
88.5
69.2
118.0
118.0
102.0
77.6
126.0
125.0
115.0
85.8
kW
9.27
9.29
9.41
9.56
9.39
9.39
9.48
9.63
9.51
9.48
9.55
9.70
100
TC
107.0
109.0
117.0
127.0
116.0
116.0
122.0
132.0
124.0
123.0
126.0
136.0
SHC
107.0
105.0
87.6
68.3
116.0
116.0
101.0
76.7
124.0
123.0
114.0
84.9
kW
9.77
9.79
9.91
10.10
9.90
9.89
9.99
10.10
10.00
9.99
10.10
10.20
105
TC
106.0
107.0
115.0
125.0
114.0
114.0
119.0
129.0
122.0
121.0
124.0
133.0
SHC
106.0
103.0
86.7
67.4
114.0
114.0
100.0
75.8
122.0
121.0
113.0
84.0
kW
10.30
10.30
10.40
10.60
10.40
10.40
10.50
10.70
10.50
10.50
10.60
10.70
115
TC
102.0
103.0
110.0
120.0
110.0
110.0
114.0
124.0
118.0
117.0
118.0
128.0
SHC
102.0
101.0
84.8
65.7
110.0
110.0
98.1
74.1
118.0
117.0
111.0
82.3
kW
11.30
11.30
11.40
11.60
11.40
11.40
11.50
11.70
11.50
11.50
11.60
11.70
Edb —
Entering Dry Bulb
Ewb —
Entering Wet Bulb
kW
—
Compressor Motor Power Input
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
50
TF
Q
0
0
4
-0
1
2
5
6
9D
07
2-
12
0
, 57
6C
12
0
, 5
6
9F
1
2
0