Bryant 563C Installation And Start-Up Instructions Manual Download Page 3

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

A.

Outdoor Unit Connected to Factory-Approved

Indoor Unit

Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft of
field-supplied or factory-accessory tubing. Check refrigerant
charge for maximum efficiency.

B.

Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.

C.

Install Liquid-Line Filter Drier (If applicable)

If a filter drier is included refer to Fig. 4 and install filter drier as
follows:

1. Braze 5-in. connector tube to liquid service valve. Wrap

filter drier with damp cloth.

2. Braze filter drier between connector tube and liquid tube to

indoor coil. Flow arrow must point towards indoor coil.

D.

Sweat Connection

CAUTION:

To avoid valve damage while brazing, ser-

vice valves must be wrapped in a heat-sinking material
such as a wet cloth.

Service valves are closed from factory and ready for brazing. After
wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non-silver bearing
brazing material. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.

VII.

INSTALL SOLENOID VALVE IN LIQUID TUBE

(IF REQUIRED)

CAUTION:

Not all applications require use of a liquid

tube solenoid valve. If your unit has been shipped with a
liquid tube solenoid valve in the unit, it must be installed
for performance enhancement. The liquid tube solenoid
valve must be energized during evacuation for complete
removal of refrigerant.

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT

SIZE

LIQUID

VAPOR

VAPOR (LONG LINE)

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

024

3/8

3/8

5/8

5/8

5/8

3/4

030, 036

3/8

3/8

3/4

3/4

3/4

7/8

042, 048

3/8

3/8

7/8

7/8

7/8

1-1/8

060

3/8

3/8

7/8

1-1/8

7/8

1-1/8

NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Long-Line Application Guideline.
2. Do not apply capillary tube indoor coils to these units.

TABLE 2—ACCESSORY USAGE

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(BELOW 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(OVER 50 FT)

REQUIRED FOR

BURIED LINE

APPLICATIONS†

(OVER 3 FT)

REQUIRED FOR

SEA COAST

APPLICATIONS

(WITHIN 2 MILES)

Crankcase Heater

Yes

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

No

Winter Start Control

Yes‡

No

No

No

Accumulator

No

No

Yes

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

Yes

No

Low-Ambient Controller,

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

No

Coastal Filter

No

No

No

Yes

Support Feet

Recommended

No

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

Yes

No

Ball Bearing Fan Motor

Yes**

No

No

No

* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline.
† For buried line applications, refer to Residential Split System Buried-Line Application Guideline.
‡ Only when low-pressure switch is used.
** Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

Fig. 4—Liquid-Line Filter Drier

A98126

LIQUID-LINE
FILTER-DRYER

CONNECTOR

TUBE

—3—

Summary of Contents for 563C

Page 1: ... from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant...

Page 2: ...or unit The piston shipped with outdoor unit is correct for any approved indoor coil combination CAUTION Remove indoor coil piston if unit is to be installed on system with a TXV metering device VI MAKE PIPING CONNECTIONS WARNING Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow control...

Page 3: ...formance enhancement The liquid tube solenoid valve must be energized during evacuation for complete removal of refrigerant TABLE 1 REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 ...

Page 4: ...ute Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING The unit cabinet must have an uninter rupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with exis...

Page 5: ...indoor unit is equipped with a time delay relay circuit the indoor blower will run an additional 90 sec to increase system efficiency XII CHECK CHARGE A Unit Charge Factory charge is shown on unit rating plate Adjust charge by following procedure shown on charging tables located on unit NOTE If superheat or subcooling charging conditions are not favorable charge must be weighed in accordance with ...

Page 6: ...be weighed in NOTE Superheat F is at low side service port TABLE 4 REQUIRED SUCTION LINE TEMPERATURE F SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 82 4 85 7 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 5...

Page 7: ...NSTALLATION INSTRUCTIONS FOR DETAILS 6 TO STAGE ELECTRIC RESISTANCE HEAT CONSULT OUTDOOR THERMOSTAT INSTALLATION INSTRUCTIONS A97365 24 VAC HOT R W Y G R DH W1 W2 Y Y2 OTHER NON PROGRAMMABLE AC THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97363 24 VAC HOT R C W W1 Y Y2 G R DH W2 W1 Y Y2 BRYANT NON PROGRAMMABLE THERMOSTAT M...

Page 8: ...ER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97366 24 VAC HOT R G W Y R C C OTHER NON PROGRAMMABLE AC THERMOSTAT FA FB FC FD FF FAN COIL AIR CONDITIONER SEE NOTE 2 G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97362 24 VAC HOT R G W W1 Y Y2 O W2 R W2 C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NO...

Reviews: