Bryant 563C Installation And Start-Up Instructions Manual Download Page 2

II.

INSTALL ON A SOLID, LEVEL MOUNTING PAD

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 3
to determine base pan size and knockout hole location.

On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult Low-Ambient Guideline for wind baffle
construction.

NOTE:

Unit must be level to within

±

2° per compressor

manufacturer specifications.

III.

CLEARANCE REQUIREMENTS

When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. above roof
surface.

IV.

OPERATING AMBIENTS

The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F.

V.

CHECK INDOOR CHECK-FLO-RATER® PISTON

Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace
indoor coil piston with piston shipped with outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor
coil combination.

CAUTION:

Remove indoor coil piston if unit is to be

installed on system with a TXV metering device.

VI.

MAKE PIPING CONNECTIONS

WARNING:

Relieve pressure and recover all refrigerant

before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

CAUTION:

To prevent compressor damage DO NOT

bury more than 36 in. of refrigerant tubing. If ANY
tubing is buried, provide 6-in. vertical rise at service
valve.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor unit using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the
recommendations in the Residential Split System Long-Line
Application Guideline will reduce these losses. Refer to Table 1
for field tubing equivalent line length. Refer to Table 2 for
accessory requirements.
For buried-line applications greater than 36 in., refer to Table 2
and Residential Split System Buried-Line Application Guideline.
Buried line applications may not exceed 100 ft.

Fig. 2—Connecting Tubing Installation

A94028

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 MIN.

SUSPENSION

Fig. 3—Mounting Unit to Pad

DIMENSIONS (IN.)

UNIT

SIZE

MINIMUM

MOUNTING PAD

DIMENSIONS

TIEDOWN KNOCKOUT LOCATIONS

A

B

C

024–060

30 X 30

6-1/2

23-1/2

20

A94199

C

B

A

3

8

D. (9.53) TIEDOWN 

KNOCKOUTS (2) PLACES

—2—

Summary of Contents for 563C

Page 1: ... from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant...

Page 2: ...or unit The piston shipped with outdoor unit is correct for any approved indoor coil combination CAUTION Remove indoor coil piston if unit is to be installed on system with a TXV metering device VI MAKE PIPING CONNECTIONS WARNING Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow control...

Page 3: ...formance enhancement The liquid tube solenoid valve must be energized during evacuation for complete removal of refrigerant TABLE 1 REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 ...

Page 4: ...ute Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING The unit cabinet must have an uninter rupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with exis...

Page 5: ...indoor unit is equipped with a time delay relay circuit the indoor blower will run an additional 90 sec to increase system efficiency XII CHECK CHARGE A Unit Charge Factory charge is shown on unit rating plate Adjust charge by following procedure shown on charging tables located on unit NOTE If superheat or subcooling charging conditions are not favorable charge must be weighed in accordance with ...

Page 6: ...be weighed in NOTE Superheat F is at low side service port TABLE 4 REQUIRED SUCTION LINE TEMPERATURE F SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 82 4 85 7 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 5...

Page 7: ...NSTALLATION INSTRUCTIONS FOR DETAILS 6 TO STAGE ELECTRIC RESISTANCE HEAT CONSULT OUTDOOR THERMOSTAT INSTALLATION INSTRUCTIONS A97365 24 VAC HOT R W Y G R DH W1 W2 Y Y2 OTHER NON PROGRAMMABLE AC THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97363 24 VAC HOT R C W W1 Y Y2 G R DH W2 W1 Y Y2 BRYANT NON PROGRAMMABLE THERMOSTAT M...

Page 8: ...ER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97366 24 VAC HOT R G W Y R C C OTHER NON PROGRAMMABLE AC THERMOSTAT FA FB FC FD FF FAN COIL AIR CONDITIONER SEE NOTE 2 G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97362 24 VAC HOT R G W W1 Y Y2 O W2 R W2 C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NO...

Reviews: