Bryant 563C Installation And Start-Up Instructions Manual Download Page 1

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.

WARNING:

Before installing, modifying, or servicing

system, main electrical disconnect switch must be in the
OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warning
label. Electrical shock can cause personal injury or death.

INSTALLATION RECOMMENDATIONS

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

to capacity of unit.

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal

opening with RTV or other pliable silicon-based caulk. (See
Fig. 2.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing. (See Fig. 2.)

8. Ensure that tubing insulation is pliable and completely

surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 2.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

When outdoor unit is connected to factory-approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
indoor unit of the same size when connected by 15 ft of
field-supplied or factory accessory tubing. For proper unit opera-
tion, check refrigerant charge using charging information located
on control box cover.

IMPORTANT:

Maximum liquid-line size is 3/8-in. O.D. for all

residential applications including long line.

IMPORTANT:

Always install a liquid-line filter drier. Refer to

Product Data Sheet for appropriate part number. Obtain filter
driers from service parts.

INSTALLATION

I.

CHECK EQUIPMENT AND JOB SITE

A.

Unpack Unit

Move to final location. Remove carton taking care not to damage
unit.

B.

Inspect Equipment

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.

Fig. 1—Model 563C

A94355

installation and
start-up instructions

12 SEER
SPLIT-SYSTEM
AIR CONDITIONER

Cancels:

II 561C-24-1

II 563C-24-2

2-98

563C

—1—

Summary of Contents for 563C

Page 1: ... from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant...

Page 2: ...or unit The piston shipped with outdoor unit is correct for any approved indoor coil combination CAUTION Remove indoor coil piston if unit is to be installed on system with a TXV metering device VI MAKE PIPING CONNECTIONS WARNING Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow control...

Page 3: ...formance enhancement The liquid tube solenoid valve must be energized during evacuation for complete removal of refrigerant TABLE 1 REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 ...

Page 4: ...ute Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING The unit cabinet must have an uninter rupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with exis...

Page 5: ...indoor unit is equipped with a time delay relay circuit the indoor blower will run an additional 90 sec to increase system efficiency XII CHECK CHARGE A Unit Charge Factory charge is shown on unit rating plate Adjust charge by following procedure shown on charging tables located on unit NOTE If superheat or subcooling charging conditions are not favorable charge must be weighed in accordance with ...

Page 6: ...be weighed in NOTE Superheat F is at low side service port TABLE 4 REQUIRED SUCTION LINE TEMPERATURE F SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 82 4 85 7 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 5...

Page 7: ...NSTALLATION INSTRUCTIONS FOR DETAILS 6 TO STAGE ELECTRIC RESISTANCE HEAT CONSULT OUTDOOR THERMOSTAT INSTALLATION INSTRUCTIONS A97365 24 VAC HOT R W Y G R DH W1 W2 Y Y2 OTHER NON PROGRAMMABLE AC THERMOSTAT FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 Y1 C SEE NOTE 2 G O J1 JUMPER J2 JUMPER A97363 24 VAC HOT R C W W1 Y Y2 G R DH W2 W1 Y Y2 BRYANT NON PROGRAMMABLE THERMOSTAT M...

Page 8: ...ER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97366 24 VAC HOT R G W Y R C C OTHER NON PROGRAMMABLE AC THERMOSTAT FA FB FC FD FF FAN COIL AIR CONDITIONER SEE NOTE 2 G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97362 24 VAC HOT R G W W1 Y Y2 O W2 R W2 C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FAN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NO...

Reviews: