Table 12 — 551B060 Air Delivery — Horizontal Discharge Units
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
665
0.31
729
0.35
843
0.47
940
0.60
1026
0.74
1600
703
0.36
763
0.40
872
0.53
965
0.66
1049
0.81
1700
741
0.40
801
0.47
902
0.60
993
0.75
1077
0.89
1800
765
0.45
821
0.51
923
0.65
1019
0.81
1099
0.96
1900
802
0.45
854
0.58
953
0.73
1046
0.90
1126
1.06
2000
840
0.60
888
0.66
984
0.82
1073
0.99
1154
1.16
2100
878
0.69
923
0.75
1015
0.91
1101
1.08
1182
1.27
2200
916
0.78
958
0.85
1046
1.01
1129
1.19
1209
1.39
2300
954
0.89
993
0.96
1079
1.13
1160
1.31
1237
1.51
2400
993
1.00
1029
1.07
1112
1.25
1190
1.43
1264
1.63
2500
1031
1.13
1066
1.20
1145
1.39
1220
1.57
1292
1.77
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1108
0.89
1187
1.06
1202
1.18
1079
1.10
1600
1130
0.97
1206
1.14
1275
1.32
1281
1.44
1700
1152
1.05
1226
1.23
1298
1.41
1359
1.60
1800
1178
1.14
1249
1.32
1316
1.52
1382
1.72
1900
1201
1.23
1274
1.43
1338
1.62
1402
1.83
2000
1226
1.33
1297
1.53
1363
1.73
1424
1.94
2100
1252
1.45
1320
1.64
1388
1.85
1448
2.07
2200
1280
1.58
1345
1.77
1410
1.97
1473
2.20
2300
1309
1.71
1372
1.91
1434
2.11
1496
2.34
2400
1336
1.85
1400
2.06
1459
2.26
1519
2.48
2500
1363
2.00
1428
2.22
1486
2.43
1543
2.65
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface
indicates
a
field-supplied
drive
is
required.
(See
Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp.
4. Maximum continuous bhp is 1.80. Extensive motor and electrical
testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your
local representative to verify.
7. Motor drive range: 1020 to 1460. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
—27—