Table 7 — 551B048 Air Delivery — Vertical Discharge Units
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.6
0.7
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
542
0.16
616
0.21
678
0.27
739
0.32
842
0.44
886
0.50
929
0.56
1300
576
0.20
644
0.25
704
0.31
764
0.37
867
0.50
910
0.56
952
0.62
1400
610
0.24
673
0.30
732
0.36
791
0.42
889
0.55
933
0.62
976
0.69
1500
646
0.28
704
0.35
761
0.42
818
0.48
912
0.61
957
0.69
1001
0.76
1600
681
0.33
735
0.40
790
0.47
845
0.54
920
0.68
931
0.76
1023
0.83
1700
718
0.39
768
0.46
836
0.54
873
0.61
965
0.76
1005
0.84
1045
0.91
1800
754
0.45
801
0.53
851
0.61
900
0.69
992
0.84
1032
0.92
1071
1.00
1900
791
0.52
836
0.60
832
0.69
828
0.77
1019
0.93
1058
1.02
1097
1.10
2000
828
0.60
870
0.68
864
0.77
858
0.86
1046
1.03
1085
1.12
1124
1.21
AIRFLOW
(Cfm)
BELT-DRIVE MOTOR
External Static Pressure (in. wg)
1.0
1.1
1.2
1.4
1.6
1.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1200
1008
0.67
1052
0.73
1096
0.78
1134
0.89
1203
1.00
—
—
1300
1029
0.75
1065
0.81
1101
0.86
1174
1.01
1229
1.15
1277
1.27
1400
1052
0.83
1087
0.90
1121
0.96
1183
1.09
1255
1.22
1305
1.38
1500
1076
0.91
1111
0.99
1145
1.06
1208
1.20
1274
1.33
1337
1.47
1600
1100
1.00
1134
1.08
1168
1.15
1232
1.31
1291
1.46
1350
1.60
1700
1124
1.09
1158
1.17
1192
1.25
1255
1.42
1314
1.58
1370
1.77
1800
1147
1.18
1182
1.27
1217
1.36
1279
1.54
1381
1.71
1393
1.89
1900
1169
1.27
1205
1.37
1240
1.47
1303
1.66
1408
1.85
1417
2.03
2000
1194
1.38
1228
1.48
1262
1.58
1327
1.78
1436
1.98
1440
2.18
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface
indicates
a
field-supplied
drive
is
required.
(See
Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp.
4. Maximum continuous bhp is 1.20. Extensive motor and electrical test-
ing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your
local representative to verify.
7. Motor drive range: 840 to 1185. All other rpms require field-supplied
drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
—22—