Bryant 105A Installation Instructions Manual Download Page 8

8

3--Phase Monitor

In 3--phase units a small circuit board is factory installed to monitor

line voltage. A small led will flash if a phase problem exists. See

code descriptions on monitor. If LED is flashing, disconnect

power to unit and interchange 2 field--wiring leads on unit

contactor.

A00010

Fig. 6 -- 3--Phase Monitor Control

(Applies to 3--Phase Units Only)

Table 5 – Three--Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Ensure compressor rotation is correct.

S

3--phase scroll compressors are rotation sensitive.

S

A flash LED on phase monitor indicates reverse rotation.
(See Table

 5

)

This will not allow contractor to be energized.

S

Disconnect power to unit and interchange 2 field--wiring
leads on unit contactor.

CAUTION

!

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is

energized.
On a call for cooling, thermostat makes circuits R--Y and R--G.

Circuit R--Y energizes contactor, starting outdoor fan motor and

compressor circuit. R--G energizes indoor unit blower relay,

starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de--energizing

contactor and blower relay. Compressor and motors stop.
If indoor unit is equipped with a time--delay relay circuit, the

indoor blower will run an additional 90 seconds to increase system

efficiency.

Check Charge

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist

when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C).

Follow the procedure below:
Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line

above or below 15ft (4.57 m) respectively.

NOTE:

For 15 ft (4.57 m) line set charge, refer to the table below.

some units may require additional charge depending on size. Find
model size in chart below, reference factory charge on unit’s rating
plate and add additional charge if there is a difference. Additional
charge will be needed for longer line sets (charge unit to nameplate
subcooling).

Unit

Size

15 ft. (4.57 m) Line Set Charge lb (kg)

113A

114CNA

114CNC

105A

18

4.10 (1.86)

4.77 (2.16)

4.5 (2.04)

4.87 (2.21)

24

4.22 (1.91)

4.20 (1.91)

4.20 (1.91)

4.60 (2.09)

30

4.90 (2.22)

5.67 (2.57)

5.67 (2.57)

5.67 (2.57)

36

5.00 (2.27)

5.42 (2.46)

5.42 (2.46)

6.40 (2.90)

42

6.07 (2.75)

7.90 (3.58)

7.90 (3.58)

7.46 (3.38)

48

7.00 (3.18)

8.31 (3.77)

8.31 (3.77)

8.31 (3.77)

60

8.80 (3.99)

9.39 (4.26)

9.39 (4.26)

9.39 (4.26)

For standard refrigerant line lengths (80 ft/24.38 m or less), allow

system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then

be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Long Line Guideline for

special charging requirements.

Final Checks

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and

covers.

3. Tighten service valve stem caps to 1/12--turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in

manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this

equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Owner’s Manual for

information.

Summary of Contents for 105A

Page 1: ...CTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or...

Page 2: ...rigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units or 18 in 457 2 mm if no overhang within 12 ft 3 66 m Position so water snow or ice from roof or eaves cannot fa...

Page 3: ...g Set lengths between 50 and 200 ft 15 2 and 61 0 m horizontal or 20 ft 6 1 m vertical differential 250 ft 76 2 m Total Equivalent Length refer to the Residential Piping and Longline Guide line Air Conditioners and Heat Pumps using Puron refrigerant 3 For alternate liquid line options on 18 42 size units see Product Data or Residential Piping and Application Guideline Install Liquid Line Filter Dr...

Page 4: ...d line temperature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The following procedure is valid when indoor airflow is within 21 percent of its rated CFM 1 Operate unit a minimum of 15 minutes before checking charge 2 Measure suction press...

Page 5: ... 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 42 106 41 104 40 102 39 100 38 98 37 395 110 43 108 42 106 41 104 40 102 39 100 38 406 112 44 110 43 108 42 106 41 1...

Page 6: ...ing may occur Charge must be weighed in Note Superheat _F is at low side service port Allow a tolerance of 3_F 1 7_C Note Indoor dry bulb between 70_F and 80_F 21_C and 27_C Table 4 Required Suction Line Temperature SUPERHEAT TEMP _F SUCTION PRESSURE AT SERVICE PORT PSIG 107 8 112 2 116 8 121 2 126 130 8 138 8 140 8 145 8 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 4...

Page 7: ...ds Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connectio...

Page 8: ...arge will be needed for longer line sets charge unit to nameplate subcooling Unit Size 15 ft 4 57 m Line Set Charge lb kg 113A 114CNA 114CNC 105A 18 4 10 1 86 4 77 2 16 4 5 2 04 4 87 2 21 24 4 22 1 91 4 20 1 91 4 20 1 91 4 60 2 09 30 4 90 2 22 5 67 2 57 5 67 2 57 5 67 2 57 36 5 00 2 27 5 42 2 46 5 42 2 46 6 40 2 90 42 6 07 2 75 7 90 3 58 7 90 3 58 7 46 3 38 48 7 00 3 18 8 31 3 77 8 31 3 77 8 31 3 ...

Page 9: ...trol Yes No No For tubing line sets between 50 and 200 ft 15 24 and 60 96 m and or 20 ft 6 10 m vertical differential refer to Residential Piping and Longline Guideline Additional requirement for Low Ambient Controller full modulation feature MotorMasterr Control 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C A C THERMOSTAT Typical FAN COIL AIR CONDITIONER G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN 24...

Page 10: ...uction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do...

Reviews: