background image

4

not rubbing against each other or any sheet metal or wires. Pay
close attention to feeder tubes, making sure wire ties on feeder
tubes are secure and tight.

Installing with Indoor Piston

Air Conditioner Matched with Factory Approved Piston
Indoor

Air conditioners may be installed with piston fan coils as a system
when the air conditioner and fan coil are listed as a system in the

AHRI directory. All rated piston fan coils are shipped with the
appropriate size piston for the equal tonnage air conditioner.

Matching air conditioners with piston indoors of larger tonnage

size requires a TXV.

Air Conditioner Applied as Replacement Component

If the air conditioner is installed as a replacement component in an

existing piston indoor system, the piston size in the indoor unit

should be changed to the size required for the air conditioner which
can be found in the Product Data

CAUTION

!

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If using a TXV in conjunction with a single--phase

reciprocating compressor, a compressor start capacitor and

relay are required.

Units with Cooling Mode TXV

Units installed with cooling mode TXV require charging by the
subcooling method.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accur-

ate gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid line near
outdoor coil.

4. Refer to unit rating plate for required subcooling temperat-

ure.

5. Refer to Table 2 --

Rating Plate (required) Subcooling Tem-

perature

. Find the point where required subcooling temper-

ature intersects measured liquid service valve pressure.

6. To obtain required subcooling temperature at a specific

liquid line pressure, add refrigerant if liquid line temperature

is higher than indicated or reclaim refrigerant if temperature

is lower. Allow a tolerance of

3

_

F (

1.7

_

C).

Units with Indoor Piston

Units installed with indoor pistons require charging by the

superheat method.
The following procedure is valid when indoor airflow is within

21 percent of its rated CFM.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure suction pressure by attaching an accurate gage to

suction valve service port.

3. Measure suction temperature by attaching an accurate ther-

mistor type or electronic thermometer to suction line at ser-
vice valve.

4. Measure outdoor air

dry bulb temperature with thermo-

meter.

5. Measure indoor air (entering indoor coil) wet--bulb temper-

ature with a sling psychrometer.

6. Refer to Table 3 --

Superheat Charging -- AC Only

. Find

outdoor temperature and evaporator entering air wet--bulb
temperature. At this intersection, note superheat. Where a
dash (----) appears on the table, do not attempt to charge sys-

tem under these conditions or refrigerant slugging may oc-
cur. Charge must be weighted in, adding or removing 0.6

oz/ft of 3/8 liquid line above or below 15 feet (4.6m) re-
spectively.

7. Refer to Table 4 --

Required Suction--Line Temperature

.

Find superheat temperature (from #6 above) and suction
pressure. At this intersection, note suction line temperature.

8. If unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is

reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is

reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow--restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated

on chart.

12. Optimum performance will be achieved when the operating

charge produces 10

_

F suction superheat at suction service

valve with 95

_

F (35

_

C) outdoor ambient and 80

_

F (27

_

C)

dry bulb (67

_

F / 19

_

C) wet bulb) indoor temperature (DOE

“A” test conditions) at rated airflow.

Summary of Contents for 105A

Page 1: ...CTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or...

Page 2: ...rigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remaining sides must be maintained Maintain a distance of 24 in 609 6 mm between units or 18 in 457 2 mm if no overhang within 12 ft 3 66 m Position so water snow or ice from roof or eaves cannot fa...

Page 3: ...g Set lengths between 50 and 200 ft 15 2 and 61 0 m horizontal or 20 ft 6 1 m vertical differential 250 ft 76 2 m Total Equivalent Length refer to the Residential Piping and Longline Guide line Air Conditioners and Heat Pumps using Puron refrigerant 3 For alternate liquid line options on 18 42 size units see Product Data or Residential Piping and Application Guideline Install Liquid Line Filter Dr...

Page 4: ...d line temperature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The following procedure is valid when indoor airflow is within 21 percent of its rated CFM 1 Operate unit a minimum of 15 minutes before checking charge 2 Measure suction press...

Page 5: ... 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 42 106 41 104 40 102 39 100 38 98 37 395 110 43 108 42 106 41 104 40 102 39 100 38 406 112 44 110 43 108 42 106 41 1...

Page 6: ...ing may occur Charge must be weighed in Note Superheat _F is at low side service port Allow a tolerance of 3_F 1 7_C Note Indoor dry bulb between 70_F and 80_F 21_C and 27_C Table 4 Required Suction Line Temperature SUPERHEAT TEMP _F SUCTION PRESSURE AT SERVICE PORT PSIG 107 8 112 2 116 8 121 2 126 130 8 138 8 140 8 145 8 0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 4...

Page 7: ...ds Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connectio...

Page 8: ...arge will be needed for longer line sets charge unit to nameplate subcooling Unit Size 15 ft 4 57 m Line Set Charge lb kg 113A 114CNA 114CNC 105A 18 4 10 1 86 4 77 2 16 4 5 2 04 4 87 2 21 24 4 22 1 91 4 20 1 91 4 20 1 91 4 60 2 09 30 4 90 2 22 5 67 2 57 5 67 2 57 5 67 2 57 36 5 00 2 27 5 42 2 46 5 42 2 46 6 40 2 90 42 6 07 2 75 7 90 3 58 7 90 3 58 7 46 3 38 48 7 00 3 18 8 31 3 77 8 31 3 77 8 31 3 ...

Page 9: ...trol Yes No No For tubing line sets between 50 and 200 ft 15 24 and 60 96 m and or 20 ft 6 10 m vertical differential refer to Residential Piping and Longline Guideline Additional requirement for Low Ambient Controller full modulation feature MotorMasterr Control 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C A C THERMOSTAT Typical FAN COIL AIR CONDITIONER G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN 24...

Page 10: ...uction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do...

Reviews: