Boiler Control Instruction & Operation Manual
Page 6
5
of
68
Specifications
Parameter Summary
USB
Parameter
Range
Security
Page
System Menu
X
Temperature Units
F / C
Basic
30
X
Outdoor Sensor Source
Not Installed / Modbus / Wired / Wireless
Basic
30
X
Outdoor Sensor Calibration
- 50 to 50 °
Basic
30
X
Antishort Cycle Time
0 - 20 minutes
Basic
30
X
CH Frost Protection
Enable / Disable
Basic
30
X
CH Frost Protection Setpoint
- 50 to 50 °F
Basic
30
X
Installer Password
none
Factory
31
X
Warm Weather Shutdown Enable
Enable / Disable
Basic
31
X
Warm Weather Shutdown Setpoint
20 to 100 °F
Basic
31
System Date
Basic
31
System Time
Basic
31
X
Auto Jump To Home Page
Enable / Disable
Basic
31
Modulation Menu
Boiler Type
NA
Factory
32
CH Max Modulation Rate
(Min Mod Rate + 100) to Absolute Max Mod
Factory
32
DHW Max Modulation Rate
(Min Mod Rate + 100) to Absolute Max Mod
Factory
32
Minimum Modulation Rate
Absolute Min Mod to (CH Max Mod Rate - 100)
Factory
32
Lightoff Rate
Min Modulation to Default Lightoff Rate
Factory
32
Operation Menu
Auto/Manual
Auto / Manual
Supervisor
28
Rate
Min Mod Rate to CH Max Mod Rate
Supervisor
28
Pump Menu
X
System Pump
Never / Any Demand / Central heat, No Priority /
Central Heat Optional Priority / Fresh Air Damper
Supervisor
33
X
Boiler Pump
Never / Any Demand / Central Heat, Off DHW
Supervisor
33
X
DHW Pump
Never / Primary loop Piped IWH / Boiler Piped IWH /
Fresh Air Damper
Supervisor
34
X
CH pump overrun time
0 to 60 minutes
Supervisor
34
X
DHW pump overrun time
0 to 60 minutes
Supervisor
34
X
Boiler pump overrun time
0 to 60 minutes
Supervisor
34
X
Pump exercise interval
0 to 40 days
Supervisor
34
X
Pump exercise time
0 to 600 seconds
Supervisor
34
Central Heat Menu
X
CH Setpoint
50 to 190 °F
Basic
36
X
CH TOD Setback Setpoint
50 to 190 °F
Basic
36
X
CH Difference Above
3 to 29 °F
Basic
36
X
CH Difference Below
3 to 29 °F
Basic
36
X
CH Response Speed
1 to 5
Supervisor
36
X
CH Modulation Sensor
Outlet Sensor / Header Sensor
Supervisor
37
X
Central Heat Low Fire Hold Time
0 to 30 minutes
Supervisor
37
X
Central Heat Low Fire Hold Rate
Absolute Min Mod to Lightoff Rate Default
Supervisor
37
Domestic Hot Water Menu
X
DHW Priority Time
0 to 90 minutes
Basic
37
X
DHW Setpoint
50 to 190 °F
Basic
37
X
DHW TOD Setback Setpoint
50 to 190 °F
Basic
37
X
DHW Difference Below
3 to 29 °F
Basic
37
X
DHW Difference Above
3 to 29 °F
Basic
37
X
DHW Response Speed
1 to 5
Supervisor
38
X
Domestic Low Fire Hold Time
0 to 30 minutes
Supervisor
38
X
Domestic Low Fire Hold Rate
Absolute Min
Supervisor
38
X
DHW Demand/Modulation
DHW Switch & Outlet Sensor /
DHW Sensor & DHW Sensor
Basic
38
Outdoor Reset Menu
X
Outdoor Reset Enable/Disable
Enable / Disable
Basic
39
X
Minimum Outdoor Temperature
- 50 to 32 °F
Basic
39
X
Maximum Outdoor Temperature
35 to 100 °F
Basic
39
X
Low W ater Temperature
70 to 180 °F
Basic
39
X
Minimum Boiler Water Temperature
50 to 185 °F
Basic
39