Boiler Control Instruction & Operation Manual
Page 3
6
of
68
Setup & Tuning
Parameter Adjustment
Pumps
Factory
Setting
Range /
Choices
Parameter and Description
0 Min
0 to 60 Min
Overrun Time: System Pump
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
0 Min
0 to 60 Min
Overrun Time: Isolation Valve
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
1 Min
10 seconds to 60 Min
Overrun Time: Boiler Pump (Combustion Air Damper and Standby Loss
Damper)
Time that pump runs after demand is satisfied. Used to dissipate heat within the
system.
7 Days
0 to 40 Days
Pump Exercise Interval
The number of days the pump is inactive before the pump will be activated for
the Pump Exercise Time.
20 Sec
0 to 10 Min
Pump Exercise Time
The amount of time the pump runs for exercise. This feature helps prevent pump
seizing due to inactivity periods.
Press
to adjust the following parameters.