Boiler Control Instruction & Operation Manual
Page
17
of
68
Installation
Quick Setup
The Quick Setup Menu is accessed from the Main Menu Screen. The Quick Setup menu allows the
user to review and adjust the most commonly adjusted parameters, such as Setpoints and pump output
settings, from one location. Refer to Parameter Adjustment section for additional information.
Setpoints
Factory
Setting
Range /
Choices
Parameter and Description
180
50
to
190 (ºF)
Central Heat Setpoint
10
3
to
29 (ºF)
Central Difference Above
5
3
to
29 (ºF)
Central Difference Below
180
50
to
190 (ºF)
Domestic Hot Water Setpoint
10
3
to
29 (ºF)
Domestic Difference Above
5
3
to
29 (ºF)
Domestic Difference Below
32
-50
to
50 (ºF)
CH Frost Protection Setpoint
70
20
to
100 (ºF)
Warm Weather Shutdown Setpoint
195
50
to
195 (ºF)
Stop All Boilers
Comfort
Factory
Setting
Range /
Choices
Parameter and Description
30 (ºF)
-50
to
32 (ºF)
Minimum Outdoor Temperature
70 (ºF)
35
to
100 (ºF)
Maximum Outdoor Temperature
110 (ºF)
70
to
180 (ºF)
Low Water Temperature
130 (ºF)
50
to
185 (ºF)
Minimum Boiler Water Temperature
Response
Factory
Setting
Range /
Choices
Parameter and Description
3
1 to 5
Central Heat Response Speed
0
0 to 30 Minutes
Central Heat Low Fire Hold Time
3
1 to 5
Domestic Heat Response Speed
0
0 to 30 Minutes
Domestic Heat Low Fire Hold Time
Hydronic System
Factory
Setting
Range /
Choices
Parameter and Description
Boiler Pump
Any Demand
Never
Any Demand
CH, OFF DHW Demand
Boiler Pump
System Pump
Any Demand
System Pump: Never
System Pump: Any Demand System Pump:
Central Heat, No Priority System Pump:
Central Heat, Optional Priority Fresh Air
Damper
Spare Output J4, 6-7
DHW Pump Primary
Loop Piped IWH
DHW Pump: Never
DHW Pump: Primary Loop Piped IWH
DHW Pump: Boiler Piped IWH
Fresh Air Damper
Spare Output J4, 6-7