The FT Series Heating Only, Boiler
Page 61
These changes are to be made only by a qualified technician.
Index
Numbers
Parameter
Description
1: EH
Error history up to 10
Check last 10 error codes (E0 - E9)
2: cE
Delete Error history
Select “ON” to delete error code history
Range: ON or OFF,Default OFF
3: In
System initialize
Select “ON” to reset to factory setting,Default OFF
4: OH
Maximum Outdoor
Temperature
When used with an outdoor sensor, sets the maximum outdoor
design temperature for the system design. Maximum outdoor
temperature must be set at least 9°F above the minimum outdoor
temperature. Range: (Minimum Outdoor Tempe 9°F) to
110°F , Default 68°F
5: OL
Minimum Outdoor
Temperature
Sets the minimum outdoor design temperature for the system.
Minimum outdoor temperature must be set at least 9°F below the
maximum outdoor temperature.
Range: -4°F to (Maximum Outdoor Temperature - 9°F), Default 30°F
6: cH
Maximum Supply
temperature
Sets the maximum design supply temperature based on the
minimum outdoor design temperature. Maximum supply temperature
must be set at least 9°F above the minimum supply temperature.
Range: (Minimum Supply Tempe 9°F) - 180°F,
Default 180°F
5.7 Installer Mode
61page
B
C
E
A
D
WARNING
For low temperature heating
applications, adjust P6 to
desired value. For cascade
applications, adjust P31 to
desired water temperature.
Call Technical services for
assistance in changing
settings.
To c hange any of the Installer Parameters,
Start by turning
OFF
the Power
(Button A)
to the
Display Control.
Then, with the power OFF, Press and HOLD (more than 5 seconds) the Button B
to get into the Installer Mode.
Rotate Dial E until you find the Installer Parameter (full list on facing page) that you wish to change. Tap Dial E
to enter that Parameter.
Adjust to the setting that you require using Dial E and then press (tap) Dial E to save and to Exit.
Finish by pressing button B
and then turning the power back on to the control (Button A).
Summary of Contents for FT Series
Page 52: ...Page 52 4 20 Ladder Diagram ...
Page 70: ...Page 70 6 2 Fault Tree Analysis 6 2 1 1 Flame detection ...
Page 80: ...Page 80 SECTION 10 Parts 10 1 100 MBH Casing Assembly ...
Page 82: ...Page 82 Heat Exchanger Assembly 100 MBH ...
Page 84: ...Page 84 Blower Assembly 100 MBH ...
Page 86: ...Page 86 Casing Assembly 10 2 140 MBH ...
Page 88: ...Page 88 Heat Exchanger Assembly 140 MBH ...
Page 90: ...Page 90 Blower Assembly 140 MBH ...
Page 92: ...Page 92 Casing Assembly 10 3 199 MBH ...
Page 94: ...Page 94 Heat Exchanger Assembly 199 MBH ...
Page 96: ...Page 96 Blower Assembly 199 MBH ...
Page 98: ...Page 98 Notes ...
Page 99: ...The FT Series Heating Only Boiler Page 99 Notes ...