The FT Series, Heating Only, Gas Conversion Kit
pg 4 of 4
Figure E (Conversion label)
14.
Setup your combustion analyzer and place the sensor into the combustion test port
15.
Per
Table B for Max Fire
,
change dip switch 6 to ON and 7 to OFF. The unit will cycle up to MAX fi re.
16.
WAIT for your combustion analyzer to stabilize. This may take up to 3 minutes depending on your
combustion analyzer. Then measure the CO
2
for MAX fi re. Refer to Table D for acceptable MAX fi re
combustion readings
Do NOT adjust CO2 at MAX Fire. ONLY in MIN Fire, so...
17.
Per
Table B for MIN Fire
,
change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
18.
WAIT for your combustion analyzer to stabilize. Then measure the CO
2
for MIN fi re. Refer to Table D for
acceptable MIN fi re combustion readings
19.
Open the Gas Valve Adjustment Port by removing the cap screw with a T15 Star/Torx screwdriver.
20.
Then use the T15 Star/Torx to make a minor adjustment (1/8 turn) to either increase or decrease CO
2
.
21.
It may be necessary to go back and forth between HI Fire and LOW Fire several times (and making
adjustments only at LOW Fire), before
CO2
at both are within acceptable levels. Be sure to put the
adjustment port cap screw back onto the valve when done.
22.
Once the CO2
and manifold pressure measurements for both MIN and MAX Fire are acceptable, set DIP
switches 6 and 7 to the OFF position for Nominal Fire (normal operation).
23.
Write in the correct conversion date and the technicians name to the included gas conversion sticker. See
Figure E. Then apply that sticker adjacent to the rating plate.
24.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
H22415900
Manifold pressure
Propane Gas (LP)
Natural Gas (NG)
MFTHW
100
-0.075
˝
WC
-0.070
˝
WC
-0.003
˝
WC
-0.000
˝
WC
MFTHW
140
-0.130
˝
WC
-0.100
˝
WC
-0.004
˝
WC
-0.002
˝
WC
MFTHW
175
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
MFTHW
199
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
CO
2
value
Propane Gas (LP)
Natural Gas (NG)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTHW
80/100
120/140/175/199
9.5~11%
8.5~10.5%
9~10.5 %
8~10%
Refer to the below table.
Table D
All sizes
(and all altitudes)
Summary of Contents for FT Series
Page 52: ...Page 52 4 20 Ladder Diagram ...
Page 70: ...Page 70 6 2 Fault Tree Analysis 6 2 1 1 Flame detection ...
Page 80: ...Page 80 SECTION 10 Parts 10 1 100 MBH Casing Assembly ...
Page 82: ...Page 82 Heat Exchanger Assembly 100 MBH ...
Page 84: ...Page 84 Blower Assembly 100 MBH ...
Page 86: ...Page 86 Casing Assembly 10 2 140 MBH ...
Page 88: ...Page 88 Heat Exchanger Assembly 140 MBH ...
Page 90: ...Page 90 Blower Assembly 140 MBH ...
Page 92: ...Page 92 Casing Assembly 10 3 199 MBH ...
Page 94: ...Page 94 Heat Exchanger Assembly 199 MBH ...
Page 96: ...Page 96 Blower Assembly 199 MBH ...
Page 98: ...Page 98 Notes ...
Page 99: ...The FT Series Heating Only Boiler Page 99 Notes ...