© Brüel & Kjær Vibro
● C106834.002 / V06 ●
Page 91 of 110
Technical alterations reserved!
Brüel & Kjær Vibro
│
Instruction VC-1800 Series
Connecting the VIBROCONTROL 18xx to a
PLC/PC
EN
UNRESTRICTED DOCUMENT
Additional parameters, optional:
40009.5
0.5
u8
configurable_output_1.relay [OK: Relay closed=0]
Relay closed = 0
Relay open = 1
40010
2
float
configurable_output_1.analog
40012
0.5
u8
configurable_output_2.relay [OK: Relay closed=0]
Relay closed = 0
Relay open = 1
40012.5
2
float
configurable_output_2.analog
40014.5
0.5
u8
configurable_output_3.relay [OK: Relay closed=0]
Relay closed = 0
Relay open = 1
40015
2
float
configurable_output_3.analog
40017
0.5
u8
configurable_output_4.relay [OK: Relay closed=0]
Relay closed = 0
Relay open = 1
40017.5
2
float
configurable_output_4.analog
40130.5
2
float
process_input_1.measuring_result
40132.5
0.5
u8
process_input_1.danger_alarm_low
No Alarm = 0
Alarm = 1
40133
0.5
u8
process_input_1.alert_alarm_low
No Alarm = 0 Alarm
= 1
40133.5
0.5
u8
process_input_1.alert_alarm_high
No Alarm = 0 Alarm
= 1
40134
0.5
u8
process_input_1.danger_alarm_high
No Alarm = 0 Alarm
= 1
40136
2
float
tacho_input_1.measuring_result
40138
0.5
u8
tacho_input_1.danger_alarm_speed_low
No Alarm = 0 Alarm
= 1
40138.5
0.5
u8
tacho_input_1.alert_alarm_speed_low
No Alarm = 0 Alarm
= 1
40139
0.5
u8
tacho_input_1.alert_alarm_speed_high
No Alarm = 0 Alarm
= 1
40139.5
0.5
u8
tacho_input_1.danger_alarm_speed_high
No Alarm = 0 Alarm
= 1