DIMENSIONS 

 

63.5mm

4

5

m

m

6

1

m

m

8

5

m

m

49.5mm

30mm

44mm

 

CONNECTION DIAGRAM  

 

 

 

TECHNICAL SPECIFICATION (continued) 

 

Temperature rating 

Operating: 

-20 to +60

°

Storage: 

-30 to +70

°

Relative humidity: 

+95% max. 

 

Output 

 

RLY1 

RLY2

 

Terminals: 

12, 13, 14

 

10, 11 

Contact arrangement: 

1 x SPDT 

1 x SPNO 

AC1 (250V) 

8A (2000VA) 

8A (2000VA) 

AC15 (250V) 

2.5A 

2.5A 

DC1 (25V) 

8A (200W) 

8A (200W) 

Electrical life: 

 

 

 

 

Switching current (A) 

 

DC load capacity: 

 

 

 

       DC current (A) 

 

Dielectric voltage: 

2kV AC (rms) IEC 60947-1 

Rated impulse withstand voltage: 

4kV (1.2/50

µ

S) IEC 60664 

 

Housing 

Material: 

Grey flame retardant Lexan UL94 V0 

Weight: 

 

 

120g 

Mounting option: 

 

On to 35mm symmetric DIN rail to BS EN 60715 

 

Terminal conductor size 

Cable type: 

 

 

 

 

Nominal cross section: 

0.2 – 4mm

2

 

0.2 – 2.5mm

2

 

0.2 – 2.5mm

2

 

 

30 – 12AWG 

30 – 12AWG 

30 – 12AWG 

Stripping length: 

6mm 

 

 

Standards 

Product: 

IEC 60947-2 / Annex M, IEC 60755, IEC 62020 

EMC: 

IEC 61543, IEC 61000-4 Series, CISPR 22 

 

CE and RoHS Compliant. C-tick 

 

 

Toroid options 

Part number: 

Aperture 

Internal diameter/size: 

I

n (min.) A 

BZCT035 

 

35mm 

 

0.006 

BZCT050 

 

50mm 

 

0.006 

BZCT070 

 

70mm 

 

0.03 

BZCT120 

 

120mm 

 

0.1 

BZCT160 

 

160mm 

 

0.1 

BZCT210 

 

210mm 

 

0.3 

BZCTR305 

 

115 x 305mm 

0.3 

BZCTR350 

 

150 x 350mm 

0.3 

BZCTR470 

 

160 x 470mm 

0.3 

 

 

 

TECHNICAL SPECIFICATION 

 

Auxiliary Power Supply (5, 7) 

Voltage range (Us): 

24 – 230V AC/DC 

1.25A (T) rated fuse should be installed in line with terminal 5 (A1) 

Frequency range (AC supply): 

50/60Hz 

Supply variation: 

85 – 115% of Us 

Auxiliary supply is galvanically isolated from the Toroid and Remote Test/Reset connections 

Overvoltage category: 

III (IEC 60664) 

Rated impulse withstand voltage: 

4kV (1.2/50

µ

S) IEC 60664 

Power consumption (max.): 

AC: 6VA, DC: 5W 

 

 

Monitored input (via external Toroid connected to terminals 8 and 9) 

Unit classification: 

Type A 

Measurement principle: 

True R.M.S. 

Input DSP filter cut-off 

150, 300 or 450Hz 

(factory default = 150Hz) 

External Toroid ratio: 

Selectable between 600:1 and 1000:1 in 100:1 steps 

(factory default 

= 1000:1)

 

Monitored leakage current range: 

ELR01PN 

ELR30PN 

 

1.5mA – 1A 

7.5mA – 30A 

 

 

 

User adjustments 

 

ELR01PN 

ELR30PN 

Trip level settings (I

n): 

6mA, 10mA, 30mA, 50mA, 
100mA, 200mA, 300mA, 
500mA, 750mA, 1A 

30mA, 100mA, 300mA, 500mA, 1A, 
3A, 5A, 10A, 20A, 30A 

Actual trip level: 

85% of I

n (+/- 5%) 

Rated residual non-operating 
current (I

no): 

<80% of I

Reset level: 

 85% tripped level

 

Time delay (Non-operate) settings 
(

t): 

0

1

, 60ms, 150ms, 250ms, 500ms, 800ms, 1s, 2.5s, 5s, 10s 

1

 

actual delay when set to 0 (instantaneous) is <25ms @ 5 x I

n

 

 

Note: 

1.

 

For I

n of 30mA or less (model dependant) the Time delay is fixed to 0 (instantaneous) and is not adjustable 

(i.e. any other delay cannot be set) 

2.

 

The unit is factory set to 30mA (or 6mA) (and instantaneous delay). Adjustment of these settings can be 
made if necessary to suit the requirements of the installation. To prevent tampering of the settings, the clear 
window can be secured in place using a 2mm or 2.5mm wide cable tie (not supplied).

 

 

Reset time: 

<1s (from supply interruption) 

 

 

LED indication 

 

Power Supply 

 

Green x1 

LED is usually permanently lit but will flash if no valid 
profile has been selected or there was a communication 
error with the smartphone 

Tripped 

 

Red x 1 

LED flashes during a time out (i.e. before tripping) or if the 
external toroid is disconnected. LED will also flash prior to 
unit reclosing if “auto-reclosure” mode enabled. 

Bargraph (25, 50, 75%) 

Yellow x3 

 

 

 

Test and Reset 

 

Front push button 

Remote N.O. push button(s) 

“Test” method 

(assuming unit is 

in the non-tripped state)

 

Press once to trip the 
unit 

Press “Test” button to trip the unit 
(connected to terminals 2 and 3) 

“Reset” method 

(assuming unit is 

in the tripped state and fault 
current cleared)

 

Press once to reset 
the unit 

Press “Reset” button to reset the unit 
(connected to terminals 1 and 2) 

Minimum trigger time: 

>∆

>80ms + 

t setting 

(only applicable to remote “Test”) 

 

Auto-reset 

To enable: 

Via app (or place wire link between terminals 1 and 2) 

 

 

Auto-reclosure 

To enable and adjust parameters: 

Via app only 

Reclosure attempts: 

Selectable between 1 and 10 

(factory default = 6)

 

Time between reclosure attempts 
(t

r

): 

t

after first attempt which doubles after each attempt i.e. 2t

r

, 4 t

r

, 8 

t

r

, etc. Options are: 1, 2.5, 5, 7.5 and 10s 

(factory default = 7.5s)

 

Timeout: 

Selectable between 1 and 20mins 

(factory default = 15mins)

 

 

 

Relay operational modes 

 

To change modes: 

Via app only 

 

RLY1 

RLY2 

Key (assuming non-tripped state): 

S.O. 

(factory default) 

P.S.O. 

(factory default) 

S.O. = Standard Output 

S.O. 

Pre-alarm* 

(relay normally de-energised) 

P.S.O. 

P.S.O. 

P.S.O = Positive Safety Output 

S.O. 

S.O. 

(relay normally energised) 

* Relay energises when Pre-alarm threshold exceeded 

(factory 

default = 50% of I

n). Threshold can be changed via app

 

 

 

C

y

cl

e

D

C

 V

o

lt

a

g

e

 (

V

Resistive 
load 

250V AC 

AC1 

Resistive load 

 

Type: ELR01PN/30PN 

Earth Leakage Relay – Type A (with NFC Technology)

 