8

9

www.bromicheating.com

www.bromicheating.com

1.2”

1.2”

22.6” 

24.6” 

2000W & 4000W Models

Mounting Hole Centres & Heater Position

1

36” 

34”

3000W & 6000W Models

2

0.8” 

0.4” 

0.25” 

Suspension Tube

Mounting Hole

3

4

6

7

5

8

9

1. Mark mounting hole centres on ceiling.

    Attach mounting brackets to ceiling using 

    appropriate fasteners (Not supplied).

2. Heater must be installed with heater surface at least

2400mm above the floor level.

Supplied suspension tubes position heater surface

1000mm below the ceiling surface.

If required, cut down length of suspension tubes to

ensure correct installation height.

Minimum distance from front surface of heater to

ceiling surface must be 250mm for 2000W & 3000W 

models & 330mm for 4000W & 6000W models. 

3. If suspension tubes are cut down, drill new mounting

holes in each tube.

4. Make electrical connection in junction box as per 

electrical installation instructions in this manual.
5. Feed power cord through suspension tube.
6. Assemble suspension tubes to rear bracket with M5

screw, spring washer and nut.
7. Rotate heater to required angle. 15° or 30° in either

direction. Lock into position with self tapping screw.
8. Raise heater assembly into position.

Attach suspension tubes to ceiling brackets with 

M5x35mm screws, spring washers & nuts.

9. Make electrical connection from suspension tube 

power cord to power from ceiling as per 

electrical installation instructions in this manual.

TUBE SUSPENSION (SOLD SEPARATELY)

 TUBE SUSPENSION 

(SOLD SEPARATELY)

1.  Mark mounting hole centres on ceiling. Attach

mounting brackets to ceiling using appropriate 
fasteners (Not supplied). 

2. Heater must be installed with heater surface at least

7’10” above the floor level. Supplied suspension
tubes position heater surface 39.4” below the 
ceiling surface. If required, cut down length of 
suspension tubes to ensure correct installation 
height. Minimum distance from front surface of 
heater to ceiling surface must be 9.8” for 2000W & 
3000W models & 13” for 4000W & 6000W models. 

3. If suspension tubes are cut down, drill new

mounting holes in each tube.

4. Make electrical connection in junction box as per

electrical installation instructions in this manual.

5.  Feed power cord through suspension tube.
6.  Assemble suspension tubes to rear bracket with

M5 screw, spring washer and nut.

7.  Rotate heater to required angle. 15° or 30° in either

direction. Lock into position with self tapping 
screw. 

8.  Raise heater assembly into position. Attach

suspension tubes to ceiling brackets with 
M5x35mm screws, spring washers & nuts.

9.  Make electrical connection from suspension tube

power cord to power from ceiling as per electrical 
installation instructions in this manual.

HEATER INSTALLATION 

CONTINUED...

HEATER INSTALLATION 

CONTINUED...

CEILING RECESS KIT 

(SOLD SEPARATELY) 

1.  Prepare ceiling cut out & ceiling box. Minimum

ceiling box dimensions must be as shown in table.
Heater must be installed with heater surface at least
94.4” above the floor level.

2.  From below, bring ceiling frame up and into ceiling

cut out.

3.  Fasten ceiling frame to ceiling box through

mountingholes with fasteners (not supplied).

4.  Prepare heater for installation. Attach mounting

brackets to both ends of heater with supplied fasteners.

19.7”

14.5” 

 A 

2 LAYERS OF 16MM FIREPROOF

INSULATION MUST BE INSTALLED ON ALL

SURFACES OF CEILING BOX

MODEL

DIMENSION "A"

2000W & 4000W

3’ 10”

3000W & 6000W

4’ 8”

Summary of Contents for BH0610001

Page 1: ...T INFORMATION ABOUT THIS MANUAL KEEP INSTRUCTION WITH APPLIANCE FOR FUTURE REFERENCE COBALT SMART HEAT ELECTRIC HEATER BY BROMIC INSTALLATION INSTRUCTION AND SERVICE MANUAL SUITABLE FOR ELECTRIC HEATE...

Page 2: ...ter only as described in this manual Any other use not recommended by manufacturer may cause fire electric shock or injury to persons For Domestic and Commercial Use CONTENTS IMPORTANT NOTES WARNINGS...

Page 3: ...n accordance with Test for Permanence of Cord Tag Section 53 This Installation Operation and Service manual should not be removed from the site of installation Installer should leave manual with the c...

Page 4: ...nts are horizontal Failure to do this will cause the heating element within the tube to sag and cause premature burnout Installing vertically will void the manufacturers warranty WARNING DO NOT MOUNT...

Page 5: ...fasteners Not supplied 2 Heater must be installed with heater surface at least 7 10 above the floor level Supplied suspension tubes position heater surface 39 4 below the ceiling surface If required...

Page 6: ...ck washer Use one spanner to hold the inner nut on the element while fastening the outer nut with a second spanner Repeat for other end of element 4 Put elements in the support bracket For 2000W 3000W...

Page 7: ...ith local electrical code regulations For outdoor installation all connections must be made in accordance with local electrical code regulations for outdoor wiring Only use wiring components approved...

Page 8: ...a soft damp cloth For locations near the coast salt in the air can cause rusting of metal Additional cleaning of the heater with a soft damp cloth fortnightly will increase the life of the products a...

Page 9: ...Long Cobalt electric BH8180036 12 Ceiling recess kit Cobalt electric 2000W 4000W BH3130014 13 Ceiling recess kit Cobalt electric 3000W 6000W BH3130015 14 Tube suspension kit Cobalt electric BH3130016...

Reviews: