Flush Mount Rack Kit Installation Procedure
3 of 10
53-1002127-03
Contents
This document provides instructions to install a Brocade VDX 6710-54 (1U), VDX 6720-24 (1U), VDX 6730-32 (1U),
VDX 6720-60 (2U), VDX 6730-76 (2U), or VDX 6740 (1U)
switch in a telecommunications (Telco) rack using the
Flush Mount Kit. The document is organized as follows.
•
•
•
•
Introduction
The supported switches are listed in
.
Installation requirements
Allow 15 to 30 minutes to complete this procedure. Note the following requirements to ensure correct installation
and operation:
•
Verify that the additional weight of the switch does not exceed the rack’s weight limits.
•
Ensure that an electrical branch circuit with the following characteristics is available:
-
Required voltage and frequency as indicated in the hardware reference manual (200-230 VAC is always
preferred).
-
Protection by a circuit breaker in accordance with local electrical codes.
-
Supply circuit, line fusing, and wire size that conform to the electrical rating on the switch nameplate.
-
Grounded outlet compatible with the power cord and installed by a licensed electrician.
•
Ensure that all equipment installed in the rack is grounded through a reliable branch circuit connection. Do not
rely on a secondary connection to a branch circuit, such as a power strip.
•
Ensure that the rack is mechanically secured to ensure stability.
•
Ensure that the air temperature at the fan inlet is less than 40
o
C (104
o
F) during switch operation.
•
Ensure that the airflow available at the air vents meets the minimum requirements for the switch.
TABLE 1
Supported switches
Switch height
Switch model
1U
Brocade VDX 6710-54
Brocade VDX 6720-24
Brocade VDX 6730-32
Brocade VDX 6740
2U
Brocade VDX 6720-60
Brocade VDX 6730-76